INTU 

 

 

 

 

 
 

3. Configuring the connection in the PowerSecurity program. 

 
The “PowerSecurity” program can be downloaded at: 

http://www.pulsar.pl/pliki/PowerSecurity.exe

 

 

1.  Run the PowerSecurity program. 
2. Choose  the  Power  Supplies  >  New  Power  Su

pply  option  from  the  menu  bar.  The  “Configuration  of 

connection” window, that allows configuring the settings, will be displayed. Enter the same settings as in 
the picture below. 

 

The power supply units of the EN54 series allow higher transmission speeds - instead of 19.2k 8E1 it 
can be set to 115.2k 8E1. The changed values apply to all settings. 

 

 

Fig. 4. The connection configuration window

 

PSU 

Description

 

Name 

The name of the PSU 
The name that should be assigned individually to each PSU. 

Address 

1 ÷ 247;  
Enter the address assigned to the PSU in the RS485 bus 

Refresh period of 
the preview [ms] 

100 ÷ 60 000ms;  
Refresh period of the parameters in the preview window. 

 

 

CONNECTION 

 

Type 

Modbus RTU 
 

Port 

Enter the COM port number the same as assigned in the device manager, or select 
AUTO for automatic assignment

.

 

Transmission 
speed 

Max 19 200 bauds 

– PSU of the PSBEN series 

Max 115 200 bauds 

– PSU of the EN54 series 

Parity check 

Parity 
 

Response time [ms] 

100 ÷ 60 000ms;  
The response time from the power supply  

The interval 
between the 
transmissions [ms] 

The minimal interval between transmissions. 

The number of 
retransmissions 

The number of retransmissions after which the program reports a connection error. 
 

 
 