RSFUPS108
RACK POWER
6
Battery circuit protection SCP and reverse
polarity connection
melting fuse
Excessive discharge protection UVP
U<19V (+/-5%)
– disconnect of connection battery
Optical indication of operation:
LED: AC, DC, TEMP, LoB, ALARM, LINK, PoE
Acoustic operation indication:
Piezoelectric indicator ~75dB/0,3m
The ALARM technical output of collective failure
Relay type: 1A@ 30VDC/50VAC
The
F
MAINS
fuse in the 230V power supply circuit
T 3,15A
Mechanical parameters (tab. 5).
Enclosure dimensions
W=19”, H=2U; 482 x 88 x 324 [mm] (±2) (WxHxD)
Fixation
four-point butt mounting to RACK profiles
– the set include 4 M6 cage nuts
Net weight
7,3kg / 7,9kg
Enclosure
Steel plate RAL 9005, black
Connectors
230V AC
input: the IEC C14 socket with a fuse, power cable 1,5m
(included)
Technical output
ALARM
:
Φ0,5-2,1 (AWG 24-12) 0,5-1,5mm
2
Outputs of cameras
PoE
: sockets RJ45 8P8C
Data output of the
UPLINK
recorder: RJ45 8P8C jack
Battery output
BAT
: 6,3F-2,5
Notes
Forced cooling (fan).
Operation safety (tab.6).
Protection class PN-EN 60950-1:2007
I (first)
Protection grade PN-EN 60529: 2002 (U)
IP20
Electrical strength of insulation:
- between input and output circuits of the PSU (I/P-O/P)
- between input circuit and PE protection circuit (I/P-FG)
- between output circuit and PE protection circuit (O/P-FG)
3000 V/AC min.
1500 V/AC min.
500 V/AC min.
Insulation resistance:
- between input circuit and output or protection circuit
100 MΩ, 500V/DC
Operating parameters (tab.7).
Environmental class
II
Operating temperature
-
10ºC...+40ºC
Storage temperature
-
20ºC...+60ºC
Relative humidity
20%...90%, without condensation
Vibrations during operation
unacceptable
Impulse waves during operation
unacceptable
Direct insulation
unacceptable
Vibrations and impulse waves during transport
According to PN-83/T-42106
2. Installation.
2.1. Requirements.
The PSU RACK shall be mounted by a qualified installer with appropriate permissions and qualifications for
230V/AC installations and low-voltage installations (required and necessary for a given country). The device shall
be mounted in confined spaces, according to the environment class II, with normal air humidity (RH=90% max.
without condensation) and the temperature from -
10°C do +40°C.
Before installation, prepare a Switch'a load balance.
The given value of 15,4W per port is the maximum value referring to a single output. The total
power consumption should not exceed 96W when all PoE ports are being used
. The increased demand for
power is particularly evident in the case of cameras with heaters or infrared illuminators - when launching these
features, the power consumption increases rapidly, which may adversely affect the operation of the switch.
As the PSU is designed for a continuous operation and is not equipped with a power-switch, therefore an
appropriate overload protection shall be guaranteed in the power supply circuit. Moreover, the user shall be
informed about the method of unplugging (usually through assigning an appropriate fuse in the fuse-box). The
electrical system shall follow valid standards and regulations.