Pulsar PSDC161224T Скачать руководство пользователя страница 5

www.pulsar.pl 

 

 

 

 

PSDC161224T 

 

 

 

 

 
 

2. Installation. 
 

2.1 Requirements. 

The  stabilized  PSU  is  to  be  mounted  by  a  qualified  installer,  holding  relevant  permits  and  licenses 

(applicable  and  required  for  a  given  country)  for  230V/AC  interference  and  low-voltage  installations.  The  unit 
should  be  mounted  in  confined  spaces,  in  accordance  with  the  2nd  environmental  class,  with  normal  relative 
humidity (RH=90% maximum, without condensation) and temperature from -

10°C to +40°C. The PSU shall work in 

a vertical position that guarantees sufficient convectional air-flow through ventilating holes of the enclosure. 
 

During normal operation the total current consumption of the receivers cannot exceed 

I=24A 

 
 

As  the  PSU  module  is  designed  for  a  continuous  operation  and  is  not  equipped  with  a  power-switch, 

therefore  an  appropriate  overload  protection  shall  be  guaranteed  in  the  power  supply  circuit.  Moreover,  the  user 
shall  be  informed  about  the  method  of  unplugging  (most  frequently  through  separating  and  assigning  an 
appropriate fuse in the fuse-box). The electrical system shall follow valid standards and regulations. 

 
 
2.2  Installation procedure. 

 

1. Before installation, make sure that the voltage in the 230V power-supply circuit is cut off. 

2. Mount the PSU in a selected location and connect the wires. 
3. Connect the power cables (~230VAC) to L-N terminals of the PSU. Connect the ground wire to the terminal 
marked by the earth symbol. Use a three-core cable (with a yellow and green PE protection wire 

) to make the 

connection. Lead the cables to the appropriate terminals of the connection board through the bushing. 

 

The shock protection circuit shall be performed with a particular care, i.e. the yellow 

and green wire coat of the power cable shall stick to one side of the terminal marked with the 

’ earth symbol in the PSU enclosure. Operation of the power supply without a properly 

made and fully operational shock protection circuit is UNACCEPTABLE! It can result in 
device damage or an electric shock. 

 

 
4

. Connect the receivers’ cables to the 

AUX1…AUX4 

connectors

 

on the

 LB4 (A,B,C,D) strips.

 

5. In electrical installations with significant voltage drops in the resistance of the wires that lead to the receivers, the 
voltage value can be corrected with the P1 potentiometer 

(12V÷15V DC). 

6. Check the PSU operating status indication 
7. Once the installation and operation control have been completed, the enclosure can be locked. 

 

3. Operating status indication. 

The PSU is equipped with LED indication of operation status. The presence of power at the outputs of the 

PSU is indicated by the illumination of green LEDs on the front panel of the device.  

3.1. LED indication  

 

LED1…LED4

 

LB4-

A ÷

 

LED1…LED4

 

LB4-D

 green diodes indicate power at the outputs: 

LB4-

A AUX1…..AUX4, LB4-D AUX1…..AUX4. 

In case of a power loss at the output (fuse activation), an appropriate diode goes out. (L1 for AUX1, L2 for 
AUX2 etc.) 

 

4. Operation and use. 
 

4.1 Overload or short circuit at the PSU output. 

The  AUX1  ÷  AUX4  PSU  outputs  of  the  LB4  (A,B,C,D)  strips  are  protected  against  a  short  circuit  by  glass 

fuses. If a fuse-assisted protection has been chosen, replace the fuse (of the same parameters) in case of a failure.  

 
4.2 Activation of the OVP system of the PSU. 

When  the  OVP  system  is  activated,  the  output  voltage  is  automatically  cut  off.  Restart  is  possible  after 
disconnecting the PSU from the mains supply 230V for at least 20 seconds.

 

 
 
 