www.pulsar.pl
PSDC161224T
4
1.4. Specifications:
- electrical specifications (tab.3)
- mechanical specifications (tab.4)
- operation safety (tab.5)
- operating specifications (tab.6)
Electrical specifications (tab. 3).
Supply voltage
88
÷ 264V AC
Current consumption
2A @230VAC max.
PSU power
320Wmax.
Efficiency
88%
Output voltage
12V DC
Output current
16x 1,5A
(Σ I = 24A) max. @12V
Output voltage adjustment range
12V÷ 15VDC
Ripple voltage
150mV p-p max.
Short-circuit protection SCP
LB4 STRIP (A,B,C,D)
16x F 1,5A fuse
PSU MODULE
105% ÷ 135% of PSU power, electronic current limiting
Overload protection OLP
105% ÷ 135% of PSU power, electronic current limiting
Surge protection
varistors
Overvoltage protection OVP
15,7 ÷ 18,4V (automatic recovery)
F1÷ F4 fuses
F 1,5A/250V
Mechanical specifications (tab. 4).
Enclosure dimensions
360 x 211 x 70+8
(WxHxD) [mm] (+/- 2)
Fixing
See figure 3
Net/gross weight
2,45/2,65 kg
Enclosure
Steel plate, DC01 0,7mm colour: RAL 9003
Closing
Cheese-head screw: at the front
Connectors
Power supply: 230V AC:
Φ0,63-2,05 (AWG 22-12)
AUX outputs: Φ0,51- 2,05 (AWG 24-12)
LB4:
Φ0,51- 2,05 (AWG 24-12)
Notes
The enclosure does not adjoin the assembly surface so that cables can be led.
Convectional cooling.
Operation safety (tab.5).
Protection class PN-EN 60950-1:2007
I (first)
Protection grade PN-EN 60529: 2002 (U)
IP20
Electrical strength of insulation:
- between input (network) circuit and output circuits of the PSU (I/P-O/P)
- between input circuit and PE protection circuit (I/P-FG)
- between output circuit and PE protection circuit (O/P-FG)
3000V/AC min.
2000V/AC min.
500V/AC min.
Insulation resistance:
- between input circuit and output or protection circuit
100 MΩ, 500V/DC
Operating specifications (tab.6).
Operating temperature
-
10ºC...+40ºC
Storage temperature
-
25ºC...+60ºC
Relative humidity
20%...90%, without condensation
Vibrations during operation
unacceptable
Impulse waves during operation
unacceptable
Direct insolation
unacceptable
Vibrations and impulse waves during transport
PN-83/T-42106