2. Installation. 
 

2.1 Requirements. 

The  stabilized  PSU  is  to  be  mounted  by  a  qualified  installer,  holding  relevant  permits  and  licenses 

(applicable  and  required  for  a  given  country)  for  230V/AC  interference  and  low-voltage  installations.  The  unit 
should  be  mounted  in  confined  spaces,  in  accordance  with  the  2nd  environmental  class,  with  normal  relative 
humidity (RH=90% maximum, without condensation) and temperature from -

10°C to +50°C. The PSU shall work in 

a vertical position that guarantees sufficient convectional air-flow through ventilating holes of the enclosure. 
 

During normal operation the total current consumption of the receivers cannot exceed 

I=8x1A 

 
 

As  the  PSU  module  is  designed  for  a  continuous  operation  and  is  not  equipped  with  a  power-switch, 

therefore  an  appropriate  overload  protection  shall  be  guaranteed  in  the  power  supply  circuit.  Moreover,  the  user 
shall  be  informed  about  the  method  of  unplugging  (most  frequently  through  separating  and  assigning  an 
appropriate fuse in the fuse-box). The electrical system shall follow valid standards and regulations. 

 
2.2  Installation procedure. 

 

1. Before installation, make sure that the voltage in the 230V power-supply circuit is cut off. 

2. Mount the PSU in a selected location and connect the wires. 
3. Connect the power cables (~230VAC) to L-N terminals of the PSU. Connect the ground wire to the terminal 
marked by the earth symbol. Use a three-core cable (with a yellow and green PE protection wire 

) to make the 

connection. Lead the cables to the appropriate terminals of the connection board through the bushing. 

 

The shock protection circuit shall be performed with a particular care, i.e. the yellow 

and green wire coat of the power cable shall stick to one side of the terminal marked with the 

’ earth symbol in the PSU enclosure. Operation of the power supply without a properly 

made and fully operational shock protection circuit is UNACCEPTABLE! It can result in 
device damage or an electric shock. 

 

 
4

. Connect the receivers’ cables to the 

AUX1…AUX8 

connectors

 

on the

 LB8/AW ) strips. 

5

. If necessary, connect the device’s wires (of an alarm panel, controller, indicator, etc.) to the technical outputs: 

     - 

FPS (LB8/AW )

 output indicating a fuse failure (outputs of the LB8/AW fuse strips). 

     - 

TAMPER 

output indicating unwanted opening of the PSU’s enclosure. 

6. In electrical installations with significant voltage drops in the resistance of the wires that lead to the receivers, the 
voltage value can be corrected with the P1 potentiometer 

(12V÷15V DC). 

7. Check the PSU operating status indication 
8. Once the installation and operation control have been completed, the enclosure can be locked. 

 

3. Operating status indication. 

The PSU is equipped with LED indication of operation status. The presence of power at the outputs of the 

PSU is indicated by the illumination of green LEDs on the front panel of the device. 

L

FPS

 red LED [!] indicates a 

failure. The status of the PSU can be remote controlled by the FPS technical output. 

3.1. LED indication (fig.4.). 

 

LED1…LED8

 green diodes indicate power at the outputs: 

LB8AUX1…..AUX8. 

In case of a power loss at the output (fuse activation), an appropriate diode goes out. (L1 for AUX1, L2 for 
AUX2 etc.) 

 

L

FPS

 red

 LED [!] 

indicates a failure of at least one AUX output (the output’s number is indicated by the 

green diode). 

 

Содержание PSDC 08128

Страница 1: ...PSDC 08128 v 1 2 PSDC 12V 8A 8x1A Power supply for up to 8 analog cameras PTC TOPIC EN Edition 10 from 17 10 2016 Supersedes the edition 9 from 25 05 2015...

Страница 2: ...ion surge protection OLP overload protection against tampering warranty 3 year from the production date Example of power supply of up 8 analog cameras All channels adjustable in the range 12V 15V DC 8...

Страница 3: ...U The PSU is housed in a metallic enclosure with an indication panel featuring a microswitch indicating unwanted opening of the door faceplate 1 2 Block diagram fig 1 Fig 1 Block diagram of the PSU 1...

Страница 4: ...30V AC power connectors PE protection connector 2 LED indication of DC power status main module of the PSU 3 PSU module 4 VADJ potentiometer output voltage adjustment within the range of 12V 15V DC 5...

Страница 5: ...V or PTC 1A manual selection Mechanical specifications tab 4 Enclosure dimensions 280 x 256 x 60 8 WxHxD mm 2 Fixing See figure 3 Net gross weight 1 96 2 25 kg Enclosure Steel plate DC01 0 7mm colour...

Страница 6: ...the connection board through the bushing The shock protection circuit shall be performed with a particular care i e the yellow and green wire coat of the power cable shall stick to one side of the te...

Страница 7: ...tected against a short circuit by glass fuses or polymer fuses If a fuse assisted protection has been chosen replace the fuse of the same parameters in case of a failure If the polymer fuses assisted...