Pulsar PSBOC1552455 Скачать руководство пользователя страница 5

www.pulsar.pl 

 

 

 

 

PSBOC1552455 

 

 

 

 

 
 

Mechanical specifications (tab. 3). 

Dimensions 

L=199, W=110, H=78 [+/- 2mm]

 

Net/gross weight 

0,89kg / 0,94kg 

Connectors 

power supply, technical outputs

: Φ0,63÷2,5   I/O PCB: Φ0,41÷1,63   

BAT battery outputs: 6,3F-2,5/40cm, 
Led indication output: 3-pin 5 mm  

 

Operation safety (tab.4). 

Protection class PN-EN 60950-1:2007 

I (first) 

Degree of Protection PN-EN 60529: 2002 (U) 

IP20 

Electrical strength of insulation: 
- between PSU input circuit and output circuits (I/P-O/P) 
- between input circuit and PE protection circuit (I/P-FG) 
- between output circuit and PE protection circuit (O/P-FG) 

 
3000 V/AC min. 
1500 V/AC min. 
  500 V/AC min. 

Insulation resistance: 
- between input circuit and output or protection circuit 

 
100 MΩ, 500V/DC  

Operating specifications (tab.5). 

Operating temperature 

-

10ºC...+40ºC  

Storage temperature 

-

20ºC...+60ºC 

Relative humidity 

20%...90%, without condensation 

Vibrations during operation 

unacceptable 

Impulse waves during operation 

unacceptable 

Direct insolation 

unacceptable 

Vibrations and impulse waves during transport 

PN-83/T-42106 

 

2. Installation. 
 

2.1 Requirements 

The buffer PSU is to be mounted by a qualified installer, holding relevant permits and licenses (applicable 

and  required  for  a  given  country)  for  230V/AC  interference  and  low-voltage  installations.  The  unit  should  be 
mounted  in  confined  spaces,  in  accordance  with  the  2nd  environmental  class,  with  normal  relative  humidity 
(RH=90% maximum, without condensation) and temperature from -

10°C to +40°C. 

 
The device shall be mounted in a metallic enclosure (a cabinet, an intended case). In order to fulfil LVD and 

EMC requirements, the rules for: power-supply, encasing and screening shall be followed, according to application. 
The PSU provides voltage of 

U=27,6V 

DC with current capacity: 

 

                                               1. Output current 5A + 0,5A battery charging

*

 

                                               2. Output current 3,5A + 2A battery charging

*

 

 

                                       Total device c battery: 5,5A max

*

 

2.2. Installation procedure. 

1. Before installation of the power supply unit, make sure that 230VAC power if cut off.  
2. Mount the unit in the intended location.  
3. Connect the 230VAC power cables. Connect the PE cable (yellow-green) to an appropriate PSU terminal 
(marked with 

 - earth symbol).

 

                                                 

*

 

See chart 1

 

Содержание PSBOC1552455

Страница 1: ...PSBOC1552455 v 1 1 PSBOC 27 6V 5 5A OC Enclosed buffer switch mode power supply unit with technical outputs EN Edition 9 from 01 03 2018 Supercedes edition 8 from 01 06 2016...

Страница 2: ...ption 1 1 General description 1 2 Block diagram 1 3 Description of PSU components and connectors 1 4 Specifications 2 Installation 2 1 Requirements 2 2 Installation procedure 3 Operating status indica...

Страница 3: ...ating DC absence PSU failure relay type 6 LoB output indicating battery low voltage relay type 7 EPS AC absence technical output OC type 8 PSU output indicating DC absence PSU failure OC type 9 LoB ou...

Страница 4: ...tection SCP electronic automatic recovery Overload protection OLP 105 150 of power supply automatic recovery Battery circuit protection SCP and reverse polarity connection polymer fuse Surge protectio...

Страница 5: ...tions and impulse waves during transport PN 83 T 42106 2 Installation 2 1 Requirements The buffer PSU is to be mounted by a qualified installer holding relevant permits and licenses applicable and req...

Страница 6: ...accordance with the signs colours 7 Once the tests and operation control have been completed the enclosure cabinet can be locked Fig 3 Mechanical view of the PSU 3 Operating status indication 3 1 LED...

Страница 7: ...In case of decrease of battery voltage UBAT 23V the output is switched into high impedance state hi Z relay output In case of a battery voltage drop UBAT 23V the contacts of the relay change over The...

Страница 8: ...e and to collect such WEEE separately The power supply unit is adapted for a sealed lead acid battery SLA After the operation period it must not be disposed of but recycled according to the applicable...