19 

  

5.5 Acoustic indication. 

Emergency  situations  are  acoustically  indicated.  The  frequency  and  the  number  of  signals  depend  on  an 

event type (see chapter. 5.4.6). The acoustic indication is off after removing an appropriate jumper (fig. 2, [5]). 

 

Table 11. Acoustic indication. 

 

No.

 

Description

 

Event

 

1 signal per 10s, battery-assisted 
operation 

No 230V AC supply 

1 signal per 10s, mains operation 

Battery fault, undercharged battery 

2 signals per 10s, battery-assisted 
operation 

Low level of battery charge 

Fast signals, battery-assisted 
operation 

The PSU will be disconnected due to the battery discharge 

Continuous indication 

PSU failure [see chapter

. 5.4.6] 

1 signal 

Breaking the battery test 

2 signals 

Activation of the battery test 

 

5.6  Technical outputs. 

The  PSU  feature  indication  outputs,  with  galvanic  isolation,  which  change  their  state  if  any  of  the  following 

events occur: 

 

 

EPS FLT - output indicating AC power loss

The output indicates 230V AC power loss. Under normal status, with the 230V AC power on, the output 

is  closed.  In  case  of  power  failure,  the  PSU  will  switch  the  output  into  the  open  position  after  a  time  lag 
determined in the „ Delay time for EPS output” menu (see section. 6.2.4). 

 

 

 

APS FLT - output indicating battery failure.

  

The output  indicates a failure in the  battery circuit. Under normal status (during correct operation) the 

output is close. In case of a failure the PSU will switch the output into the open state. Any failures can be 
triggered by the following events: 

 

 

- a faulty or undercharged battery 

 

 

- battery voltage below 11,5V during battery-assisted operation 
- battery fuse failure 
- no continuity in the battery circuit 

 

 

PSU FLT - output indicating PSU failure

.  

The output indicates the PSU failure. Under normal status (during correct operation) the output is close. 

In case of a failure the PSU will switch the output into the open state. Any failures can be triggered by the 
following events: 

 

 

- low output voltage Uaux<11,8V 

 

 

- high output voltage Uaux>14,7V 

 

 

- high battery voltage Uaku>14V (during battery test) 

 

 

- polymer fuse PTC activation 
- exceeding the PSU nominal current 
- failure in the battery charging circuit 
- activation of the over voltage protection OVP   

 

- enclosure opening - TAMPER 
- internal damage of the PSU 
- EXT IN input activation 

 

 

The technical outputs have been implemented with galvanic isolation between the PSU’s systems and the 

attached devices. 
 

 

Fig. 15. Electrical diagram of the technical outputs.  

Содержание PSBEN 2012B/LCD

Страница 1: ...PSBEN 2012B LCD v 1 1 PSBEN 13 8V 2A 7Ah EN LCD Buffer switch mode power supply unit EN Edition 5 from 18 06 2014 Supercedes edition 4 from 01 02 2013 LCD Version...

Страница 2: ...STIC INDICATION 19 5 6 TECHNICAL OUTPUTS 19 5 7 INPUT OF COLLECTIVE FAILURE EXT IN 20 5 8 ENCLOSURE TAMPER INDICATION TAMPER 21 5 9 OVERVOLTAGE PROTECTION OF THE PSU OUTPUT OVP 21 5 10PSU OVERLOAD 21...

Страница 3: ...ERY 35 8 REMOTE MONITORING OPTIONS WI FI ETHERNET RS485 USB 36 8 1 COMMUNICATION VIA THE USB TTL INTERFACE 36 8 2 ETHERNET NETWORK COMMUNICATION 36 8 3 THE WI FI WIRELESS COMMUNICATION 37 8 4 RS485 NE...

Страница 4: ...reverse polarity connection jumper selectable battery charging current 0 2A 0 6A 1A 1 5A remote battery test additional module required START button for battery activation STOP button for disconnecti...

Страница 5: ...re YES YES No battery charge YES YES Low output voltage YES YES High output voltage YES YES PSU failure YES YES Surge protection YES YES Short circuit protection YES YES YES YES Overload protection YE...

Страница 6: ...ain power source are reported to the Alarm Receiving Centre ARC in accordance with 9 2 EN 50131 1 standard Output voltage 0 116A 1 5A battery charge General use if the PSU is not mounted in an install...

Страница 7: ...dication off Caption jumper on jumper off VADJ potentiometer DC voltage adjustment BUZZER acoustic indicator FBAT fuse in the battery circuit Connectors AC AC power input BAT DC power battery output A...

Страница 8: ...t no Description Insolation transformer PSU board see Tab 1 fig 2 TAMPER micro switch contacts of tamper resistance NC FMAINS fuse in the supply circuit 230V AC L N power supply connector 230V AC PE p...

Страница 9: ...m 1 Mount the PSU in a selected location It is particularly important to bolt the tamper grip to the mounting surface The grip is located in the central part of the enclosure see fig 3 7 and guarantee...

Страница 10: ...the PSU failure indication at the APS FLT output but it does not affect the protection system against complete battery discharge 11 Check the current consumption of the receivers taking into account...

Страница 11: ...ntering the overview menu mode red LED indicating the presence of AC voltage green LED indicating power at the AUX output of the PSU red LED indicating the PSU failure 5 2 First run of the PSU languag...

Страница 12: ...symbols Screen field Operating status Failure status Blinking FAIL message Information about the current voltage and power consumption at the AUX output The parameter which value has been exceeded is...

Страница 13: ...www pulsar pl PSBEN2012B LCD BLACK POWER 13 current failures of the PSU see section 5 4 3 parameters of the PSU stored in the memory see section 5 4 4 History of events see section 5 4 5...

Страница 14: ...ry charging indication highlighted battery charging PSU overload indication highlighted PSU overload Sections 5 10 PSU failure indication highlighted PSU failure Sections 5 4 6 5 6 Battery failure ind...

Страница 15: ...of the highest priority If there are more than five failures at the same time use the or buttons to display the next failure 5 4 4 LCD screen history of the parameters To set the screen press the ESC...

Страница 16: ...output current IAUX MIN output current minimum IAUX MAX output current maximum To optimally read and analyze the values shown in the chart it is possible to change the time range on the bottom axis of...

Страница 17: ...The codes are divided into two groups marked with the initial letters F or I The codes beginning with the letter F indicate a failure The codes that begin with the letter I indicate the correct opera...

Страница 18: ...s F60 No communication PSU FLT no communication with LCD panel F61 F64 Control panel fail PSU FLT service codes F65 Access unlocked passwords unlocked Table 9 List of PSU message codes Message code De...

Страница 19: ...o the open position after a time lag determined in the Delay time for EPS output menu see section 6 2 4 APS FLT output indicating battery failure The output indicates a failure in the battery circuit...

Страница 20: ...e EXT IN input The electrical diagram below shows the way of connecting external devices to the EXT IN input Outputs such as OC open collector relay may be used as a source of the signal Fig 17 Exampl...

Страница 21: ...n of the PSU output OVP In case of voltage exceeding 15 5V 0 5V at the switching regulator s output the system cuts off the power at the outputs to protect the battery and the receivers from damage Th...

Страница 22: ...e password full access to the PSU s settings User s password locked access to the PSU settings menu Table 12 Access ranges PASSWORD Access range Control panel settings PSU settings SERVICE USER Preset...

Страница 23: ...nge it To do this choose a password that will be changed user s password or service password and enter the new one 6 1 3 Disabling the password If the password is not required it can be turned off The...

Страница 24: ...m by pressing the SET button When on the keyboard will be locked automatically if no buttons are pressed within 5 minutes After this time pressing any button on the control panel will display a window...

Страница 25: ...N OFF battery test OFF Section 6 2 2 and 7 3 Battery protection ON battery protection disconnection ON OFF battery protection disconnection OFF Section 6 2 3 Delay time for EPS output Setting the dela...

Страница 26: ...test menu press the SET button the prompt will appear at the end of the line use the or buttons to select ON battery test ON OFF battery test OFF confirm by pressing the SET button Enabling disabling...

Страница 27: ...disconnection ON OFF battery protection disconnection OFF confirm by pressing the SET button 6 2 4 Setting the delay time for EPS output indicating 230V AC power loss The PSU features adjustable delay...

Страница 28: ...tion between the PSU and the computer namely the address parity and speed should have the same settings for both the PSU and the PowerSecurity program Communication address allows to identify power su...

Страница 29: ...ave the same settings for both the PSU and the PowerSecurity program The PSU has preset transmission parameters of 115200 baud 8E1 if these values were changed they should be restored to original sett...

Страница 30: ...mode the screen will turn off if no buttons are pressed within 5 minute Fig 23 Control panel screen Table 14 The description of the Control panel screen Position Description Language Available langua...

Страница 31: ...the prompt will appear next to the day position use the or buttons to set the current day confirm by pressing the SET button 6 3 3 Setting the time The Time menu in the Control panel menu enables sett...

Страница 32: ...option use the or buttons to change the setting to 5 min press the SET button the prompt will appear at the end of the line use the or buttons to set the required brightness confirm by pressing the S...

Страница 33: ...during failure indication When on the blinking light will indicate a failure use the or buttons to display the Blinking light indicating failure menu press the SET button the prompt will appear at the...

Страница 34: ...e SET button and select PSU Battery protection ON OFF see section 6 2 3 Caution Deactivating of the UVP function is not recommended since a deep discharge of the battery limits its capability of stori...

Страница 35: ...a battery circuit charged with direct current The current selection is done with use of the IBAT jumpers The table below shows how long does it take to charge a fully discharged battery up to min 80 o...

Страница 36: ...e power supply unit power supply current consumption used for the calculation of standby time should be taken into account see section 7 4 8 1 Communication via the USB TTL interface The easiest way o...

Страница 37: ...ng against adverse environmental conditions Fig 27 Ethernet network communication using the RS485 INTRE interface 8 3 The Wi Fi wireless communication The Wi Fi wireless communication can be implement...

Страница 38: ...ainst adverse environmental conditions Fig 29 The Wi Fi communication using the RS485 WIFI INTRW interface 8 4 RS485 network communication Another type of network communication is the RS485 communicat...

Страница 39: ...of the program into smaller areas depending on the number of monitored power supplies The program is equipped with manager mode which allows the grouping of power supplies for easier analysis and orie...

Страница 40: ...5 5V disconnection of the output voltage automatic return AUX disconnection Short circuit protection SCP Electronic current limitation and or FBAT fuse failure in the battery circuit requires fuse rep...

Страница 41: ...dimensions 270 x 250 x 80 8 WxHxD mm 2 Mounting See Fig 3 Battery space 7Ah 12V SLA max 150 x 110 x 75mm WxHxD max Net gross weight 3 4 3 7 kg Enclosure Steel plate DC01 1mm color RAL 9005 black Closi...

Страница 42: ...once per year During the inspection check the batteries and run the battery test 4 weeks after installation re tighten all screw connections see Fig 2 9 10 1 Battery replacement of the LCD panel Estim...

Страница 43: ...www pulsar pl PSBEN2012B LCD BLACK POWER 43...

Страница 44: ...the claim be accepted the manufacturer is obliged to provide warranty repairs at the earliest convenience however not later that within 14 days from the delivery to the service centre of the manufactu...

Отзывы: