PSBEN101A2D/LCD 

 

 

 

 

 
 

22 

 
 
- with ‘>’ or ‘<’ set the contrast 
 
 
 
- approve your choice with the ‘SET’ button 
 
 
 
 
 

3.5 Acoustic indication. 

Emergency  situations  are  acoustically  indicated.  The  frequency  and  the  number  of  signals  depend  on  an 

event type (see chapter 9). The acoustic indication is off after removing an appropriate jumper (fig. 2, [5]). 

Table 8. Acoustic indication. 

No. 

Description 

Event 

1 signal per 10s, battery-assisted 
operation 

No 230V AC supply 

1 signal per 10s, mains operation 

Battery fault, undercharged battery 

2 signals per 10s, battery-assisted 
operation 

Low level of battery charge 

Fast signals, battery-assisted operation 

The PSU will be disconnected due to the battery discharge 

Continuous indication 

PSU failure [see chapter 9] 

1 signal 

Breaking the battery test 

2 signals 

Activation of the battery test 

 
3.6 Technical outputs. 

The  PSU  feature  indication  outputs,  with  galvanic  isolation,  which  change  state  if  any  of  the  following  event 

occur: 

 

 

EPS FLT – output indicating AC power loss

The  output  indicates  AC  power  loss.  Under  normal  status  –  with  the  230V  AC  supply,  the  output  is 

close.  In  case  of  a  power  failure  the  PSU  will  switch  the  output  into  the  open  state  after  a  period  of  time 
determined by the ‘EPS output lag’ facility (see 3.4.2, table 7). 

 

 

APS FLT - output indicating battery failure.  

The output  indicates a failure in the  battery circuit. Under normal status (during correct operation) the 

output is close. In case of a failure the PSU will switch the output into the open state. Any failures can be 
triggered by the following events: 

 

 

- a faulty or undercharged battery 

 

 

- battery voltage below 11,5V during battery-assisted operation 
- battery fuse fault 
- no continuity in the battery circuit 

 

 

PSU FLT - output indicating PSU failure.  

The output indicates the PSU failure. Under normal status (during correct operation) the output is close. 

In case of a failure the PSU will switch the output into the open state. Any failures can be triggered by the 
following events: 

 

 

 

- low output voltage Uaux<11,8V 

 

 

- high output voltage Uaux>14,7V 

 

 

- high battery voltage Uaku>14V (during battery test) 

 

 

- polymer fuse  PTC activation 
- exceeding the PSU nominal current 
- failure in the battery charging circuit  
- activation of the over voltage protection OVP 

 

 

 

The technical outputs have been implemented with galvanic isolation between the PSU’s systems and the 

attached devices. 

Содержание PSBEN 10A12D/LCD

Страница 1: ...PSBEN 10A12D LCD v 1 0 PSBEN 13 8V 10A 40Ah EN LCD Buffer switched mode power supply unit EN Edition 4 from 01 02 2013 Supersedes the 3 from 20 11 2012edition...

Страница 2: ...g the EPS output lag 17 Setting the communication address 18 3 4 3 Desktop 18 Setting the language of messages 19 Setting the date 19 Setting the time 20 Setting the highlighting 20 Setting the contra...

Страница 3: ...EQUIREMENTS 31 7 2 INSTALLATION PROCEDURE 31 8 OPERATION AND USE 32 8 1 OVER VOLTAGE PROTECTION OVP AT THE PSU OUTPUT 32 8 2 OVERLOAD OF THE PSU 32 8 3 SHORT CIRCUIT AT THE PSU OUTPUT 32 8 4 BATTERY R...

Страница 4: ...s operation history failure history real time clock battery backed optical indication of PSU overload OVL acoustic indication of failure adjustable times indicating AC power failure technical inputs o...

Страница 5: ...ource are reported to the Alarm Receiving Centre ARC in accordance with 9 2 PN EN 50131 1 Output voltage 0 66A 3A battery charge General use if the PSU is not mounted within an installation which is P...

Страница 6: ...ion on indication off Caption jumper on jumper off 6 VADJ potentiometer DC voltage adjustment 7 BUZZER acoustic indicator 8 FBAT fuse in the battery circuit 9 Connectors AC AC power input BAT DC power...

Страница 7: ...ement no Description 1 Insolation transformer 2 PSU board tab 1 fig 2 3 TAMPER micro switch contacts of tamper resistance NC 4 FMAIN fuse in the supply circuit 230 V AC 5 L N 230V AC power connector P...

Страница 8: ...atus indication 3 1 Control panel The PSU is equipped with a panel with buttons and an LCD display which enables reading all available parameters of the device The buttons are for selecting and approv...

Страница 9: ...lay The main screen of the LCD display shows basic electrical parameters and informs about the current PSU state Fig 5 The main screen Table 4 Description of the symbols on the main screen Screen fiel...

Страница 10: ...status during operation Highlighting of an element informs about an active state and reflects the status of LEDs on the pcb of the PSU see table 1 12 Fig 7 Screen parameters of the PSU Table 5 Descrip...

Страница 11: ...analysis of the values shown on the chart the time range of the chart screen can be adjusted in the bottom axis Here are the available ranges 8h 24h 2days week weekly In order to change the displayed...

Страница 12: ...erates 3 levels of access to configuration which limit the possibility of changing the PSU s settings from the level of the LCD desktop They are protected with separate passwords Keypad password locks...

Страница 13: ...ear with or choose the right level of the password confirm your choice with the SET button with or enter the first digit confirm your choice with the SET button with or enter the second digit confirm...

Страница 14: ...sswords have been lost there is a procedure that will allow reassigning the passwords Please do as follows a unplug the PSU from the AC network and the battery for at least 10 seconds b press the STOP...

Страница 15: ...to the PSU NO battery not connected to the PSU see chapter 4 6 Battery test YES battery test on NO battery test off see chapter 4 3 Battery protection YES battery protection function disconnection on...

Страница 16: ...onfirm your choice with the SET button Setting the battery test with or choose the Battery test menu press the SET button you will see the prompt at the end of the line with or set YES or NO YES batte...

Страница 17: ...nction disconnection on NO battery protection function disconnection off confirm your choice with the SET button Setting the EPS output lag with or choose the EPS output lag menu press the SET button...

Страница 18: ...mputer confirm your choice with the SET button 3 4 3 Desktop The facility is only available after entering the correct user s or installer s password The Desktop menu enables setting the current date...

Страница 19: ...you will see the prompt at the end of the line with or choose the language of messages confirm your choice with the SET button Setting the date with or choose the Date menu press the SET button the pr...

Страница 20: ...section with or set the minutes press the SET button the prompt will move to the second section with or set the seconds approve the settings with the SET button Setting the highlighting Intensity of t...

Страница 21: ...xt to the constant option with or change the setting into 60 s press the SET button the prompt will move to the end of the line with or set the demanded screen brightness approve your choice with the...

Страница 22: ...y the output is close In case of a power failure the PSU will switch the output into the open state after a period of time determined by the EPS output lag facility see 3 4 2 table 7 APS FLT output in...

Страница 23: ...IN technical input has been implemented with galvanic isolation between the PSU s systems and the devices attached Fig 16 Electrical diagram of the EXT IN input The electrical diagram below shows the...

Страница 24: ...attery test facility can be switched off Deactivating activating the test enter the PSU settings from the level of the LCD desktop by pressing the SET button Then choose PSU Battery protection YES NO...

Страница 25: ...2 J3 16h24m 2 2 J1 J2 J3 24h 1 5 J1 J2 J3 0 6 J1 J2 J3 4 6 Operation without a battery In case of an expected PSU operation without an attached battery make a necessary configuration setting from the...

Страница 26: ...aces 5 1 Communication in the wi fi wireless network The Wi Fi wireless communication is to be implemented on the basis of additional interfaces WI Fi INTW and RS485 WiFi operating within 2 4GHz frequ...

Страница 27: ...Ethernet communication with the use of the INTE interface The RS485 ETHERNET INTRE interface is a device intended for converting signals between the RS485 bus and the Ethernet network To work correct...

Страница 28: ...ation with the use of the interfaces INTR and INTUR 5 4 USB TTL communication If the PSU does not cooperate with any of previously mentioned network and the access to the parameters adjustment and mem...

Страница 29: ...battery charge Io 9 1A 1 5A battery charge Io 8 4A 2 2A battery charge Io 7 6A 3A battery charge Output voltage setting escalation and keeping time 8ms 3ms 25ms Output voltage adjustment range 12 V 14...

Страница 30: ...x 355 x 170 8 WxHxD mm 2 Fixing 300 x 318 x 6 x4 WxH Fitting battery 40Ah 12V SLA max Net gross weight 8 2 8 7 kg Enclosure Steel plate DC01 1 2mm colour RAL 9005 black Closing Cheese head screw x2 a...

Страница 31: ...and assigning an appropriate fuse in the fuse box The electrical system shall follow valid standards and regulations 7 2 Installation procedure CAUTION Before installation cut off the voltage in the 2...

Страница 32: ...Operation and use 8 1 Over voltage protection OVP at the PSU output In case of voltage exceeding 15 5V 0 5V at the regulator s output the system cuts off the power at the outputs to protect the batter...

Страница 33: ...high output voltage Output voltage 14 7V F07 ON 2 flashes ON PSU FLT Too high battery voltage Battery voltage 14V F08 ON 3 flashes ON PSU FLT Battery charging circuit failure Too low output voltage of...

Страница 34: ...ssibilities to carry out the repairs or if the equipment has been conditionally accepted due to the breaking warranty terms by the claimant 7 All the services rendered by force of the warranty are car...

Отзывы: