4
1.3. Description of elements and connection links of the power-supply unit (tab.1, tab.2, fig.2).
Table 1.
Element no.
[Fig. 2]
Description
[1]
F1
fuse in the battery circuit
[2]
START
pushbutton (power activation without AC supply)
[3]
JP-B, dip switch
- configuration of UVP battery protection function
•
JP-B =
protection function (disconnection) of the battery off
•
JP-B =
protection function (disconnection) of the battery on
Legend:
dip switch installed
dip switch removed
[4]
P1
potentiometer, voltage adjustment
[5]
OUTPUTS
connector (Tab.2)
[6]
AC, LB, AUX
optical indication of the power-supply unit operation
[7]
J1, J2 dip switch
– battery charging current configuration
•
J1=
J2=
Ibat =0,3A
•
J1=
J2=
Ibat =0,9A
•
J1=
J2=
Ibat =1,5A
•
J1=
J2=
Ibat =2,0A
Legend:
dip switch installed
dip switch removed
[8]
BAT+/BAT-:
outputs, battery connBAT=red, - BAT=black
[9]
TAMPER x2,
microswitches (contacts) contact of antisabotage protection
(NC)
[10]
F2
witch in the Power supply circuit (230V/AC)
[11]
L-N
power-supply connector
230V/AC,
PE protection connector
[12]
Connector to an external optical signalization: AC and AUX.
Tab.1. The elements of the power-supply unit.
Table 2.
[5]
Description of power-supply unit outputs
~AC~
AC supply input
+BAT
-BAT
DC supply output of the battery
(+BAT= red, -BAT=black)
+AUX
-AUX
DC supply output
(+AUX= +U, -AUX=GND)
BS
AC absence technical output –OC type
level hi-Z = state: AC power supply
level L = state: AC power supply failure
AW
Technical output of voltage converter (regulator) operation status:
PWR OK –OC type
level hiZ = state: failure, overload
level L = state: normal operation
Tab.2. Output terminals of the power-supply unit.
Содержание PSBD 5012