background image

 

indication set PKAZ168) 

LED DC 

– presence of  DC voltage on power supply output 

LED CHARGE 

– battery charging process 

Optional equipment 

A set for optical indication LED PKAZ168  

Operation conditions                                            

2-nd enviromental class,  temperature: -10

o

C÷40

o

relative humidity 20%...90%, without condensation 

Dimensions  

L=237, W= 168, H=54 [±2mm] 

Net/gross weight 

1,25 / 1,31 [kg] 

Protection class electric shock protection 

I (first) 

– requires a protective conductor  

Connectors

 

I/O PCB: 0,5 

– 2,5 mm

2

 (AWG 26 

– 12) 

output of optical signalization: 4 pins micromatch socket 

Additional accessories 

Battery wire 6,3F 

– 45cm, angle muffs ML062 (hole 

5,2mm) 

Electrical strength of insulation: 
-  between  input  (network)  circuit  and  output  circuits 
of power-supply  
- between input circuit and protection circuit  
- between output circuit and protection circuit  

 
 
2500 V AC min. 
1500 V AC min. 
  500 V AC min. 

Insulation resistance: 
-  between  input  circuit  and  output  or  protection 
circuit 

 
100 

MΩ, 500 V DC  

Storage temperature 

-

20ºC...+60ºC 

Vibrations and impulse waves during transport 

according to PN-83/T-42106 

 
 
1.3.  Description of terminals. 

 

 

 

 

Elements/connectors [Fig.1] 

Description 

[1] 

LED for DC output voltage 

[2] 

Potentiometer - output voltage adjust 

[3] 

Connector of optical signalization LED 

[4] 

Power supply output (

V+

V-)

 

[5] 

Battery connector  (

B+, B-)

 

[6] 

Jumper - battery charging current configuration: 

 

J1= 

  J2= 

  J3= 

   Ibat =0,5A 

 

J1= 

  J2= 

  J3= 

   Ibat =1A 

 

J1= 

  J2= 

  J3= 

   Ibat =2A 

Legend: 

 jumper installed, 

  jumper removed 

[7] 

Battery fuse 

[8] 

L-N  

- input voltage connectors  230 V AC,  

 

– protective conductor connector 

 
 
 
 
 
 
 

Содержание PSB-48V5A

Страница 1: ...tery charging 2 Output current of 4 A 1 A battery charging 3 Output current of 3 A 2 A battery charging Total device current battery 5 A max In case of power voltage decay prompt switching to battery supply occurs The power supply unit is protected against a short circuit an overload a surge or over voltage protection 1 2 Technical parameters Supply voltage 200 240 V 1 5 A 50 60 Hz Inrush current ...

Страница 2: ...etween input network circuit and output circuits of power supply between input circuit and protection circuit between output circuit and protection circuit 2500 V AC min 1500 V AC min 500 V AC min Insulation resistance between input circuit and output or protection circuit 100 MΩ 500 V DC Storage temperature 20ºC 60ºC Vibrations and impulse waves during transport according to PN 83 T 42106 1 3 Des...

Страница 3: ...in the disconnection state is not less than 3mm 1 Mount the PSU in a selected location and connect the wires 2 Connect the power cables 230 V to L N clips of the PSU The shock protection circuit shall be performed with a particular care i e the yellow and green wire coat of the power cable shall stick to one side of the terminal in the PSU enclosure Operation of the PSU without a properly made and...

Страница 4: ...e of significant dust accumulation dusting using compressed air is recommended Pulsar sp j Siedlec 150 32 744 Łapczyca Polska Tel 48 14 610 19 40 Fax 48 14 610 19 50 e mail biuro pulsar pl sales pulsar pl http www pulsar pl www zasilacze pl WEEE MARKING According to the EU WEE Directive It is required not to dispose of electric or electronic waste as unsorted municipal waste and to collect such WE...

Отзывы: