PSACH01244 

   

 

 

      

Operation safety (tab.4).

 

Protection class PN-EN 60950-1:2004 

I (first) 

Protection grade PN-EN 60529: 2002 (U) 

IP65 

Electrical strength of insulation: 
- between input (network) circuit and output circuits of the PSU (I/P-O/P) 
- between input circuit and PE protection circuit (I/P-FG) 
- between output circuit and PE protection circuit (O/P-FG) 

 
3000V AC min. 
1500V AC min. 
  500V AC min. 

Insulation resistance: 
- between input circuit and output or protection circuit 

 
100 MΩ, 500V/DC  

Operating specifications (tab.5). 

Operating temperature 

-

25ºC...+40ºC 

Storage temperature 

-

25ºC...+60ºC 

Relative humidity 

10%...90% without condensation 

Vibrations during operation 

unacceptable 

Impulse waves during operation 

unacceptable 

Direct insolation 

unacceptable 

Vibrations and impulse waves during transport 

PN-83/T-42106 

 
2. Installation. 
 

2.1 Requirements 

The  AC/AC  power  supply  is  to  be  mounted  by  a  qualified  installer,  holding  relevant  permits  and  licenses 

(applicable  and  required  for  a  given  country)  for  230V/AC  interference  and  low-voltage  installations.  The  unit 
should  be  mounted  in  confined  spaces,  in  accordance  with  the  2nd  environmental  class,  with  normal  relative 
humidity  (RH=90%  maximum,  without  condensation)  and  temperature  from  -25

°C  to  +40°C  (table  5).  The  PSU 

shall work in a vertical or horizontal position.  

            Before mounting the PSU module, perform a load balance. During normal operation, total current drawn by 
the receivers cannot exceed

 I=4A@24V AC.  

           As  the  PSU  is  designed  for  a  continuous  operation  and  is  not  equipped  with  a  power-switch,  therefore  an 
appropriate  overload  protection  shall  be  guaranteed  in  the  power  supply  circuit.  Moreover,  the  user  shall  be 
informed  about  the  method  of  unplugging  (usually  through  assigning  an  appropriate  fuse  in  the  fuse-box).  The 
electrical system shall follow valid standards and regulations. 

 
2.2 Installation procedure. 

 

1). Before installation, make sure that the voltage in the 230V power-supply circuit is cut off. 

2). Mount the PSU in a selected location and connect the wires (tighten cable glands). 
3). Connect the power cables to the L-N terminals. Connect the ground wire to the terminal marked by the earth 
symbol 

– “

”. Use a three-core cable (with a yellow and green PE protection wire) to make the connection. Lead 

the cables to the appropriate terminals of the connection board through the bushing. 

 

 

The shock protection circuit shall be performed with a particular care, i.e. the yellow and green 
wire coat of the power cable shall stick to one side of the terminal  marked with the '

' earth 

symbol in the PSU enclosure. Operation of the power supply without a properly made and fully 
operational shock protection circuit is UNACCEPTABLE! It can result in device damage or an 
electric shock. 

 

 
4). Connect the conductors of consumers to the terminals U1-0V and/or U2-0V  of the terminal box on the  power-
supply unit (the balance of the power-supply load shall be performed). 
5). Restore the mains power ~230V AC. 
6). Once the tests and control operation have been completed, close the PSU. 
 
 
 
 
 
 
 

 