
www.pulsar.pl MSRK2512
4
Electrical parameters (tab. 3).
Supply voltage
20V÷22V AC
50VA min. (np. AWT5161820, AWT037)
Current consumption
2,5A max.
Power frequency
50Hz
Supply power
34 W
Efficiency
83%
Output voltage
11,0 V÷ 13,8 V DC – buffer operation
10,0 V÷ 13,8 V DC – battery assisted operation
Output current
2,0A + 0,5A battery charging
2,0A + 0,2A battery charging
Output voltage setting, escalation and keeping
time
20ms / 30ms / 10ms
Voltage adjustment range
12,0 V÷ 14,5 V
Ripple voltage
40 mV p-p max.
Current consumption by PSU systems
16 mA – battery assisted operation
Battery charging current
0,2A /0,5A - changed with jumper I
BAT
Short-circuit protection SCP
200% ÷ 250% of supply power - limitation of current and/or fuse
failure in the battery circuit (fuse-element replacement required)
Overload protection OLP
110% ÷ 150% (@25ºC) of power supply - limitation with the PTC
automatic fuse, manual restart (the fault requires the
disconnection of the DC output circuit)
Protection of the battery circuit SCP and reverse
polarity protection
3,15A - current limitation, F
BAT
fuse (failure requires replace of
the fuse-element)
Excessive discharge protection UVP
U<10,0 V (± 5%) – disconnection of (- BAT) battery,
configuration with jumper P
BAT
Technical outputs:
- FAC; output indicating failure of AC power supply
R-relay type, 1A@ 30Vdc/50Vac max.
Time lag about 5s/140s/1040s/2h20m30s (+/-5%)
F
BAT
fuse
F3,15A / 250V
Mechanical parameters (tab. 4).
Casing dimensions
85 x 63 x 40 (WxLxH) [mm] (+/- 2)
Fixation
Fixing dowels x 4 (PCB fi=4,2 mm)
Net/gross weight
0,08kg/0,13kg
Connectors
Outputs: Ф0,41÷1,63 (AWG 26-14)
Battery output BAT: 6,3F-2,5, 30cm
Operation parameters (tab.5).
Operation temperature
-10ºC...+40ºC
Storage temperature
-20ºC...+60ºC
Relative humidity
20%...90%, without condensation
Vibrations during operation
unacceptable
Impulse waves during operation
unacceptable
Direct insolation
unacceptable
Vibrations and impulse waves during transport
According to PN-83/T-42106
2. Installation
2.1. Requirements
The buffer PSU module is dedicated for installation by the qualified electrician, holding relevant permits and
licenses (applicable and required for the specific country) for connecting (interference with) the 230V/AC and low-voltage
systems. The unit should be mounted in the non-open premises, in accordance with the II-nd environmental class, with
the normal relative humidity (RH=90% maximum, without condensing) and temperature within the range -10°C to +40°C.
The should be operated in the position ensuring that the air may freely flow through ventilation openings in a
convectional way.
1. Output current 2,0A + 0,2A battery charging
2. Output current 2,0A + 0,5A battery charging
Total device c battery: 2,5A max.
As the PSU module is designed for constant operation, it is not equipped with supply isolator, the proper overload
protection in the supply circuit should be ensured. Also the user should be advised of the methods of disconnecting the
PSU module from the supply voltage (most frequently through the separation and indication of the relevant fuse in the
fuse box). The wiring system should be completed in accordance with the applicable standards and regulations.