www.pulsar.pl                                                                                        MSRK2512 

   

 

 

Electrical parameters (tab. 3). 

Supply voltage 

20V÷22V AC  
50VA min. (np. AWT5161820, AWT037) 

Current consumption 

2,5A max.  

Power frequency 

50Hz 

Supply power 

34 W 

Efficiency 

83% 

Output voltage 

11,0 V÷ 13,8 V DC – buffer operation 
10,0 V÷ 13,8 V DC – battery assisted operation 

Output current 

2,0A + 0,5A battery charging 
2,0A + 0,2A battery charging 

Output voltage setting, escalation and keeping 
time 

20ms / 30ms / 10ms 
 

Voltage adjustment range 

12,0 V÷ 14,5 V  

Ripple voltage 

40 mV p-p max. 

Current consumption by PSU systems 

16 mA – battery assisted operation 

Battery charging current 

0,2A /0,5A  -  changed with jumper I

BAT

  

Short-circuit protection SCP  

200% ÷ 250% of supply power - limitation of current and/or fuse 
failure in the battery circuit (fuse-element replacement required) 

Overload protection OLP 

110% ÷ 150% (@25ºC) of power supply - limitation with the PTC  
automatic fuse, manual restart (the fault requires the 
disconnection of the DC output circuit) 

Protection of the battery circuit SCP and reverse 
polarity protection 

3,15A - current limitation, F

BAT

 fuse (failure requires replace of 

the fuse-element) 

Excessive discharge protection UVP 

U<10,0 V (± 5%) – disconnection of (- BAT) battery, 
configuration with jumper P

BAT

 

Technical outputs: 
- FAC; output indicating failure of AC power supply 

R-relay type, 1A@ 30Vdc/50Vac max. 
Time lag about 5s/140s/1040s/2h20m30s (+/-5%) 

F

BAT  

fuse 

F3,15A / 250V  

 
Mechanical parameters (tab. 4). 

Casing dimensions 

85 x 63 x 40 (WxLxH) [mm] (+/- 2) 

Fixation 

Fixing dowels x 4 (PCB fi=4,2 mm) 

Net/gross weight 

0,08kg/0,13kg 

Connectors 

Outputs: Ф0,41÷1,63 (AWG 26-14) 
Battery output BAT: 6,3F-2,5, 30cm 

 
Operation parameters (tab.5). 

Operation temperature 

-10ºC...+40ºC  

Storage temperature 

-20ºC...+60ºC 

Relative humidity 

20%...90%, without condensation 

Vibrations during operation 

unacceptable 

Impulse waves during operation 

unacceptable 

Direct insolation 

unacceptable 

Vibrations and impulse waves during transport 

According to PN-83/T-42106 

 

2. Installation 
 

2.1. Requirements 

The  buffer  PSU  module    is  dedicated  for  installation  by  the  qualified  electrician,  holding  relevant  permits  and 

licenses (applicable and required for the specific country) for connecting (interference with) the 230V/AC and low-voltage 
systems. The  unit  should be mounted  in the  non-open premises,  in accordance with the  II-nd environmental class, with 
the normal relative humidity (RH=90% maximum, without condensing) and temperature within the range -10°C to +40°C. 
The    should  be  operated  in  the  position  ensuring  that  the  air  may  freely  flow  through  ventilation  openings  in  a 
convectional way.  

 

1. Output current 2,0A + 0,2A battery charging 
2. Output current 2,0A + 0,5A battery charging                         

                       Total device c battery: 2,5A max. 

 

           As the PSU module  is designed for constant operation, it is not equipped with supply isolator, the proper overload 
protection in the supply circuit should be ensured. Also the user should be advised of the methods of disconnecting the 
PSU module  from the supply voltage (most frequently through the separation and indication of the relevant fuse in the 
fuse box). The wiring system should be completed in accordance with the applicable standards and regulations.  

Содержание MSRK 2512

Страница 1: ...MSRK 2512 v 1 1 MSRK 13 8V 2A Buffer PSU module swith mode EN Issue 3 from 16 09 2013 Supersedes the edition 2 from 16 12 2011 ...

Страница 2: ...ram 1 3 Description of elements and connection links of the PSU module 1 4 Technical parameters 2 Installation 2 1 Requirements 2 2 Installation procedure 3 PSU module operation indication 3 1 Optical indication 3 2 Technical output 4 Handling and operation 4 1 Over loads or short circuits to the PSU module 4 2 Battery assisted operation 4 3 Maintenance 1 Technical description 1 1 General descript...

Страница 3: ...eter voltage adjustment DC 4 FBAT fuse in the battery circuit 5 Connectors BAT DC supply output of the battery BAT red BAT black AUX DC supply output AUX U AUX GND FAC technical output for no AC network relay type In Figure 2 configuration of contacts shows relay voltage free state which corresponds to the state signalling no AC network 6 Optical signaling LED AC LED diode that indicates the prese...

Страница 4: ...wels x 4 PCB fi 4 2 mm Net gross weight 0 08kg 0 13kg Connectors Outputs Ф0 41 1 63 AWG 26 14 Battery output BAT 6 3F 2 5 30cm Operation parameters tab 5 Operation temperature 10ºC 40ºC Storage temperature 20ºC 60ºC Relative humidity 20 90 without condensation Vibrations during operation unacceptable Impulse waves during operation unacceptable Direct insolation unacceptable Vibrations and impulse ...

Страница 5: ...osure cabinet etc 3 PSU module operation indication 3 1 Optical indication The PSU module is equipped with three diodes indicating operation status AC LB AUX AC red diode under normal status AC supply the diode is permanently illuminated The absence of AC supply is indicated by the AC diode going off LB red diode indicates the battery charging process the intensity of illumination is dependent on ...

Страница 6: ...the defect 5 Should the claim be accepted the manufacturer is obliged to provide warranty repairs at the earliest convenienve however not later that within 14 days from the delivery to the service centre of the manufacturer 6 The repair period mentioned in item 5 may be prolonged if there are no technical possibilities to carry out the repairs or if the equipment has been conditionally accepted du...

Отзывы: