Pulsar MSRK 1024 Скачать руководство пользователя страница 6

www.pulsar.pl                                                                                        MSRK1024 

   

 

 

10.  Connect the ~ 230V AC power to the transformer. The corresponding LEDs on the PCB of the power supply module 

should be ON: red AC and green AUX LED.

 The yellow LB LED should be ON during battery charging. 

11. Check the output voltage (the PSU voltage 

without load should amount to 27,2V÷ 27,8V, during battery  

    

charging 22V÷ 27,6V). If the value of the voltage requires adjustment, it should be set by the V

ADJ

 potentiometer, 

    monitoring the voltage at the AUX output of the PSU module. 
 12. Check the current consumption of the receivers, taking into account the battery charging current, so as not to  
    exceed the total current efficiency of the PSU (section 1.1). 
13. Once the tests and control operation have been completed, close the enclosure/cabinet.

 

 
3. Operating status indication. 

 

3.1 LED indication. 

The PSU module is equipped with three diodes indicating operating status: AC, LB, AUX.  

 

AC- red diode

: under normal status (AC supply) the diode is permanently illuminated. The absence of AC 

supply is indicated by the AC diode going off.    

 

LB - yellow diode

: indicates the battery charging process; the intensity of illumination is dependent on the 

charging current. 

 

AUX

green diode

: indicates the DC supply status in the output of the PSU module. Under normal status, 

the diode is permanently illuminated and in case of a short-circuit or overload, the diode goes off.

 

 
3.2. Technical outputs. 

The PSU module is equipped with indication outputs: 
 

 

EPS - technical output indicating AC power failure

The output indicates AC power failure. Under normal status 

– with the AC supply on, the output is shorted 

to ground GND. In case of power failure, the PSU will switch the output into hi-Z high impedance state after 
a time set by the T

AC 

jumper. 

 

 

PSU 

– output indicating  failure PSU module

.  

The output indicates failure PSU module. Under normal status (correct operation) the output is shorted to 
ground GND. If there is no DC voltage at the output (eg short circuit), the output is switched into hi-Z high 
impedance state.  

PSU failure can be caused by the following events: 
- Short circuit at the output 
- Output overload 
- DC/DC voltage converter failure 
- Under voltage protection activation 

 

 

LoB 

– output indicating low battery voltage.

  

The output indicates low battery voltage. Under normal status (U

BAT

 > 23V) the output is shorted to ground 

GND, when the battery voltage drops too low (U

BAT

 < 23V) the output is switched into hi-Z high impedance 

state. 

 
              The power supply technical outputs are open collector (OC) type, as shown schematically below. 

 

 

Fig. 3. Electrical diagram of OC technical outputs. 

 
 

 
 
 

 
 

 
 

 
 
 

Содержание MSRK 1024

Страница 1: ...MSRK 1024 v 1 0 MSRK 27 6V 1A OC Buffer switch mode power supply module with automatic operation control EN Edition 1 from 11 06 2014 Supersedes the edition ...

Страница 2: ...ar from the production date CONTENTS 1 Technical description 1 1 General description 1 2 Block diagram 1 3 Description of components and connectors 1 4 Specifications 2 Installation 2 1 Requirements 2 2 Installation procedure 3 Operating status indication 3 1 LED indication 3 2 Technical outputs 4 Operation and use 4 1 Overload or short circuit of the PSU module output 4 2 Running the PSU module f...

Страница 3: ... 24 29V adjustment 4 FBAT fuse in the battery circuit F2A 250V 5 Terminals AC AC power input EPS technical output of AC power failure indication hi Z state AC power failure 0V state AC power O K PSU technical output of PSU failure indication hi Z state failure 0V state PSU status O K LoB technical output of low battery voltage indication hi Z state battery voltage UBAT 23V 0V state battery O K BAT...

Страница 4: ...atic return Overload protection OLP 110 150 25ºC of power supply manual restart the fault requires disconnection of the DC output circuit Battery circuit SCP and reverse polarity protections F 2A current limitation FBAT fuse in case of a failure fuse element replacement required Surge protection varistors Excessive discharge protection UVP U 20V 5 disconnect of connection battery configuration by ...

Страница 5: ...nsformer isolation 1 Output current 1A without battery 2 Output current 0 8A 0 2A battery charge 3 Output current 0 5A 0 5A battery charge Total device current battery 1A max As the PSU module is designed for a continuous operation and is not equipped with a power switch therefore an appropriate overload protection shall be guaranteed in the power supply circuit Moreover the user shall be informed...

Страница 6: ...diode indicates the DC supply status in the output of the PSU module Under normal status the diode is permanently illuminated and in case of a short circuit or overload the diode goes off 3 2 Technical outputs The PSU module is equipped with indication outputs EPS technical output indicating AC power failure The output indicates AC power failure Under normal status with the AC supply on the output...

Страница 7: ...n on the PCB allowing to run the PSU from the battery when needed To do that press and hold the START button on the unit board for 1 second 4 3 Deep discharge battery protection UVP The power supply is equipped with deep discharge battery protection UVP If the voltage at the battery terminals drops below 20V 0 5V during battery assisted operation the batteries will be disconnected The battery prot...

Страница 8: ...ities to carry out the repairs or if the equipment has been conditionally accepted due to the breaking warranty terms by the claimant 7 All the services rendered by force of the warranty are carried out at the service centre of the manufacturer exclusively 8 The warranty does not cover the defects of the equipment resulting from reasons beyond the manufacturer s control mechanical damage improper ...

Отзывы: