Fig.2. View of the PSU module 

 
1.4 Specifications: 

- electrical parameters (tab.3) 
- mechanical parameters (tab.4) 
- operating parameters (tab.5)

 

 
Electrical parameters (tab. 3). 

Mains supply 

30V

÷32V AC 

50VA min. (

e.g. 

AWT5172430, AWT049

Current up to 

2 A max.  

Power frequency 

50Hz 

Power 

28 W 

Efficiency 

89% 

Output voltage 

22V÷ 27,6V DC – buffer operation 
20V÷ 27,6V DC – battery-assisted operation 

Output current 

1A (without battery) 
0,8A + 0,2A battery charge 
0,5A + 0,5A battery charge 

Voltage adjustment range 

24V÷ 29V DC  

Ripple 

30 mV p-p max. 

Current consumption by PSU module systems 

20 mA  

Battery charging current 

0,2A /0,5A  -  jumper selectable 

Short-circuit protection SCP  

Electronic - current limitation and/or activation of the F

BAT

 

melting fuse in the battery circuit (failure requires fuse 
replacement). Automatic return. 

Overload protection OLP 

110% ÷ 150% (@25ºC) of power supply, manual restart (the 
fault requires disconnection of the DC output circuit) 

Battery circuit SCP and reverse polarity protections 

F 2A - current limitation, F

BAT

 fuse (in case of a failure, fuse-

element replacement required) 

Surge protection 

varistors 

Excessive discharge protection UVP 

U<20V (

± 5%) – disconnect of connection battery,  

configuration by the P

BAT

 jumper 

LED indication:  
- AC diode indicating AC power 
- AUX diode indicating DC at the PSU output 
 
- LB diode indicating battery charging process 
 

 
- red, normal status: permanently illuminated, failure: off 
- green, normal status: permanently illuminated, failure: off 
 
- yellow, the light intensity depends on battery charging 
current  

Technical outputs: 
- EPS; output indicating AC power failure  
 
 
 
 
- PSU; output indicating DC absence /

 

PSU 

module failure  
 

 
-  OC type: 50mA max.  
 

Normal operation: L state (0V), 

 

failure: hi-Z state, 

- delay time 10s/60s (+/-20%) 

– jumper selectable 

T

AC

  

 
- OC type: 50mA max.  
 

Normal operation: L state (0V), 

 

failure: hi-Z state,  

Содержание MSRK 1024

Страница 1: ...MSRK 1024 v 1 0 MSRK 27 6V 1A OC Buffer switch mode power supply module with automatic operation control EN Edition 1 from 11 06 2014 Supersedes the edition ...

Страница 2: ...ar from the production date CONTENTS 1 Technical description 1 1 General description 1 2 Block diagram 1 3 Description of components and connectors 1 4 Specifications 2 Installation 2 1 Requirements 2 2 Installation procedure 3 Operating status indication 3 1 LED indication 3 2 Technical outputs 4 Operation and use 4 1 Overload or short circuit of the PSU module output 4 2 Running the PSU module f...

Страница 3: ... 24 29V adjustment 4 FBAT fuse in the battery circuit F2A 250V 5 Terminals AC AC power input EPS technical output of AC power failure indication hi Z state AC power failure 0V state AC power O K PSU technical output of PSU failure indication hi Z state failure 0V state PSU status O K LoB technical output of low battery voltage indication hi Z state battery voltage UBAT 23V 0V state battery O K BAT...

Страница 4: ...atic return Overload protection OLP 110 150 25ºC of power supply manual restart the fault requires disconnection of the DC output circuit Battery circuit SCP and reverse polarity protections F 2A current limitation FBAT fuse in case of a failure fuse element replacement required Surge protection varistors Excessive discharge protection UVP U 20V 5 disconnect of connection battery configuration by ...

Страница 5: ...nsformer isolation 1 Output current 1A without battery 2 Output current 0 8A 0 2A battery charge 3 Output current 0 5A 0 5A battery charge Total device current battery 1A max As the PSU module is designed for a continuous operation and is not equipped with a power switch therefore an appropriate overload protection shall be guaranteed in the power supply circuit Moreover the user shall be informed...

Страница 6: ...diode indicates the DC supply status in the output of the PSU module Under normal status the diode is permanently illuminated and in case of a short circuit or overload the diode goes off 3 2 Technical outputs The PSU module is equipped with indication outputs EPS technical output indicating AC power failure The output indicates AC power failure Under normal status with the AC supply on the output...

Страница 7: ...n on the PCB allowing to run the PSU from the battery when needed To do that press and hold the START button on the unit board for 1 second 4 3 Deep discharge battery protection UVP The power supply is equipped with deep discharge battery protection UVP If the voltage at the battery terminals drops below 20V 0 5V during battery assisted operation the batteries will be disconnected The battery prot...

Страница 8: ...ities to carry out the repairs or if the equipment has been conditionally accepted due to the breaking warranty terms by the claimant 7 All the services rendered by force of the warranty are carried out at the service centre of the manufacturer exclusively 8 The warranty does not cover the defects of the equipment resulting from reasons beyond the manufacturer s control mechanical damage improper ...

Отзывы: