Page 33
P871 Empty Damping
This parameter determines the maximum rate at which the unit will respond
to a decrease in level. It should be set slightly higher than the maximum
vessel empty rate.
Default = 10.000 metres/minute (32.81 feet/minute)
System (SyS1) Menu
The following three parameters do not affect how the unit performs, but
details, contained in them, may be required, by Pulsar, when making
technical enquiries.
P921 Enable Code
Enables
the passcode (
P922
), which means the passcode must be entered
to go into program mode. If
disabled
(set to
0
), then no passcode is
required, and pressing ESC and ENTER button simultaneously will allow
entry into the program mode.
P922 Passcode
This is the passcode that must be used to enter program mode. The
default
is
1997
, but this can be changed to another value.
P926 Software Revision
This parameter will display the current software revision.
P928 Serial Number
This parameter will display the serial number of the unit.
P930 Factory Defaults
This parameter resets all parameter values to the original Factory Set values
that were installed when the unit was tested, before despatch to you.
To
reset
parameters, enter
1
and press
ENTER
, all parameters, except for the
mA trims, will be restored to the factory settings (including the DATEM
trace) and on completion Stor (Store) will be displayed after which you can
ESC out of this parameter and continue programming the
IMP+ i.s.
for the
required application.