RED LED: 

 

on – the PSU is supplied with 230V AC  

 

off – no 230V AC supply  

 

GREEN LED: 

 

on – DC voltage in the AUX output of the PSU 

 

off – no DC voltage in the AUX output of the PSU 

 

2. Installation. 

 

2.1 Requirements. 

The buffer PSU shall be mounted by a qualified installer with appropriate permissions and qualifications for 

230V/AC installations and low-voltage installations (required and necessary for a given country). The device shall 
be  mounted  in  confined  spaces,  according  to  the  environment  class  II,  with  normal  air  humidity  (RH=90%  max. 
without  condensation)  and  the  temperature  from  -

10°C  to  +40°C.  The  PSU  shall  work  in  a  vertical  position  that 

guarantees sufficient convectional air-flow through ventilating holes of the enclosure. 

 

                   Before installation, prepare a PSU load balance: 

 
                                      1. Output current 5A + 0,5A battery charge

*

 

                                      2. Output current 3,5A + 2A battery charge

                                        Total device c battery: 5,5A max

*

 
As the PSU is designed for a continuous operation and is not equipped with a power-switch, therefore an 

appropriate  overload  protection  shall  be  guaranteed  in  the  power  supply  circuit.  Moreover,  the  user  shall  be 
informed  about  the  method  of  unplugging  (usually  through  assigning  an  appropriate  fuse  in  the  fuse-box).  The 
electrical system shall follow valid standards and regulations. 

 
 

2.2 Installation procedure. 

 

1. Before installation, cut off the voltage in the 230V power-supply circuit.

 

2. Mount the PSU in a selected location and connect the wires. 
3. Connect the power cables (~230Vac) to L-N clips of the PSU. Connect the ground wire to the clip marked by the 
earth symbol PE (PSU module connector). Use a three-core cable (with a yellow and green PE protection wire) to 
make the connection. Lead the cables to the appropriate clips through the insulating bushing of the connection 
board. 
 

 

 

The shock protection circuit shall be performed with a particular care, i.e. the yellow and 
green wire coat of the power cable shall stick to one side of the terminal - marked with  

 symbol on the PSU enclosure. Operation of the PSU without the properly made and 

fully  operational  shock  protection  circuit  is  UNACCEPTABLE!  It  can  cause  a  device 
failure or an electric shock. 

 
4. Connect the 

receivers’ cables to the terminals V+ (+), V-(-) of the PSU module.  

5. Connect the power (~230V) 
6. Check the PSU output voltage: 
- the PSU voltage without load should amount to U=27,6V DC.   
7. Connect the battery (mind the colours):   
- battery output (+V):  BAT+ cable / red, 
- battery output (0V):  BAT 

– cable / GND / black. 

8. Check the PSU operation indicator: green LED on the power supply module. 
9. After installing and checking proper working, the enclosure can be closed. 
 

 
3. Operating status indication. 

The PSU is equipped with two diodes on the front panel:

 

 

 
 
 

 

                                                 

*

 

Refer to chart 1

 

Содержание HPSB 5524D

Страница 1: ...HPSB 5524D v 1 0 HPSB 27 6V 5A 2x40Ah Buffer switch power supply unit EN Edition 2 from 24 10 2016 Supercedes the edition 1 from 18 03 2016 ...

Страница 2: ...ments 2 2 Installation procedure 3 Operating status indication 4 Operation and use 4 1 Overload or short circuit of the PSU output SCP on 4 2 Disconnection of discharged battery 4 3 Maintenance 1 Technical description 1 1 General description A buffer PSU is intended for an uninterrupted supply to devices requiring stabilised voltage of 24V DC 15 The PSU provides voltage of U 27 6V DC Current effic...

Страница 3: ...dule 2 Connectors PSU L N power supply connector 230V AC Protection connector PE V V DC power output B B battery output 3 green LED indicates AC power 4 P1 potentiometer output voltage adjustment 5 Battery outputs red black 6 TAMPER contact of sabotage protection NC 7 Additional connector for LED indication 8 Selection jumper for charging current Ibat 0 5 A Ibat 2 A Description jumper installed ju...

Страница 4: ... 1 Voltage adjustment range 24 28VDC Ripple 150mV p p max Current consumption by PSU systems 100mA Battery charge current 0 5A or 2A jumper selectable Short circuit protection SCP electronic automatic return Overload protection OLP 105 150 of the PSU power automatic return Battery circuit protection SCP and reverse polarity connection PTC polymer fuse Surge protection varistors Overvoltage protect...

Страница 5: ...50 1 2007 I first Protection grade PN EN 60529 2002 U IP20 Electrical strength of insulation between input and output circuits of the PSU I P O P between input circuit and PE protection circuit I P FG between output circuit and PE protection circuit O P FG 3000 V AC min 1500 V AC min 500 V AC min Insulation resistance between input circuit and output or protection circuit 100 MΩ 500V DC Table 5 Op...

Страница 6: ...stem shall follow valid standards and regulations 2 2 Installation procedure 1 Before installation cut off the voltage in the 230V power supply circuit 2 Mount the PSU in a selected location and connect the wires 3 Connect the power cables 230Vac to L N clips of the PSU Connect the ground wire to the clip marked by the earth symbol PE PSU module connector Use a three core cable with a yellow and g...

Страница 7: ...ped with the discharged battery disconnection system During the battery assisted operation reducing voltage below 19V at the battery terminals will cause battery disconnection 4 3 Maintenance Any and all maintenance operations may be performed following the disconnection of the PSU from the power supply network The PSU does not require performing any specific maintenance measures however in case o...

Страница 8: ...c equipment should be disposed of separately from normal household waste CAUTION The power supply unit is adapted for cooperation with the sealed lead acid batteries SLA After the operation period they must not be thrown but recycled according to the applicable law Pulsar Siedlec 150 32 744 Łapczyca Poland Tel 48 14 610 19 40 Fax 48 14 610 19 50 E mail biuro pulsar pl sales pulsar pl http www puls...

Отзывы: