Pulsar HPSB 5524D Скачать руководство пользователя страница 2

www.pulsar.pl

                                                                 

HPSB5524D                                                    

GREEN POWER

 

 

 

2

 

Features: 

 

 

DC 27,6V/5A uninterruptible power supply*  

 

fitting battery: 2x40Ah/12V  

 

wide range 

of mains supply: 176÷264V  

 

high efficiency 83% 

 

battery charging and maintenance control 

 

excessive discharging (UVP) protection 

 

jumper selectable battery charge current  
0,5A/2A 

 

 

battery output full protection against short-circuit 
and reverse polarity connection  

 

LED indication  

 

protections: 

 

SCP short-circuit protection 

 

OVP overvoltage protection 

 

overvoltage protection (AC input)  

 

against sabotage 

 

overload protection (OLP) 

  warranty 

– 2 year from the production date   

 

CONTENTS: 
1. Technical description. 

1.1 General description 
1.2 Block diagram 
1.3 Description of PSU components and connectors. 
1.4 Specifications 

2. Installation. 

2.1 Requirements 
2.2 Installation procedure 

3. Operating status indication. 
4. Operation and use. 

4.1 Overload or short circuit of the PSU output (SCP on) 
4.2 Disconnection of discharged battery 
4.3 Maintenance

 

 

 
1. Technical description. 
 

1.1 General description. 

A buffer PSU is intended for an uninterrupted supply to devices requiring stabilised voltage of 

24V DC (+/-15%).

 

The PSU provides voltage of 

U=27,6V DC.

 Current efficiency: 

 

                                     1. Output current 5A + 0,5A battery charge

*

 

                                     2. Output current 3,5A + 2A battery charge

                                     Total device c battery: 5,5A max

*

 

In case of power decay 230V, a battery back-up is activated immediately. The PSU is constructed based on the 

switch mode PSU, with high energy efficiency. The PSU is housed in a metal enclosure (colour RAL 9003) which can 
accommodate a 2x40Ah/12V battery. A micro switch indicates door opening (front cover). 

 

The power supply housing has space for additional modules (fuse blocks, voltage regulators and DC/DC 
converters).  

 

 
 
 
 
 
 
 
 
 
 
 
 
 
 

                                                 

*

 

Refer to chart 1

 

Содержание HPSB 5524D

Страница 1: ...HPSB 5524D v 1 0 HPSB 27 6V 5A 2x40Ah Buffer switch power supply unit EN Edition 2 from 24 10 2016 Supercedes the edition 1 from 18 03 2016 ...

Страница 2: ...ments 2 2 Installation procedure 3 Operating status indication 4 Operation and use 4 1 Overload or short circuit of the PSU output SCP on 4 2 Disconnection of discharged battery 4 3 Maintenance 1 Technical description 1 1 General description A buffer PSU is intended for an uninterrupted supply to devices requiring stabilised voltage of 24V DC 15 The PSU provides voltage of U 27 6V DC Current effic...

Страница 3: ...dule 2 Connectors PSU L N power supply connector 230V AC Protection connector PE V V DC power output B B battery output 3 green LED indicates AC power 4 P1 potentiometer output voltage adjustment 5 Battery outputs red black 6 TAMPER contact of sabotage protection NC 7 Additional connector for LED indication 8 Selection jumper for charging current Ibat 0 5 A Ibat 2 A Description jumper installed ju...

Страница 4: ... 1 Voltage adjustment range 24 28VDC Ripple 150mV p p max Current consumption by PSU systems 100mA Battery charge current 0 5A or 2A jumper selectable Short circuit protection SCP electronic automatic return Overload protection OLP 105 150 of the PSU power automatic return Battery circuit protection SCP and reverse polarity connection PTC polymer fuse Surge protection varistors Overvoltage protect...

Страница 5: ...50 1 2007 I first Protection grade PN EN 60529 2002 U IP20 Electrical strength of insulation between input and output circuits of the PSU I P O P between input circuit and PE protection circuit I P FG between output circuit and PE protection circuit O P FG 3000 V AC min 1500 V AC min 500 V AC min Insulation resistance between input circuit and output or protection circuit 100 MΩ 500V DC Table 5 Op...

Страница 6: ...stem shall follow valid standards and regulations 2 2 Installation procedure 1 Before installation cut off the voltage in the 230V power supply circuit 2 Mount the PSU in a selected location and connect the wires 3 Connect the power cables 230Vac to L N clips of the PSU Connect the ground wire to the clip marked by the earth symbol PE PSU module connector Use a three core cable with a yellow and g...

Страница 7: ...ped with the discharged battery disconnection system During the battery assisted operation reducing voltage below 19V at the battery terminals will cause battery disconnection 4 3 Maintenance Any and all maintenance operations may be performed following the disconnection of the PSU from the power supply network The PSU does not require performing any specific maintenance measures however in case o...

Страница 8: ...c equipment should be disposed of separately from normal household waste CAUTION The power supply unit is adapted for cooperation with the sealed lead acid batteries SLA After the operation period they must not be thrown but recycled according to the applicable law Pulsar Siedlec 150 32 744 Łapczyca Poland Tel 48 14 610 19 40 Fax 48 14 610 19 50 E mail biuro pulsar pl sales pulsar pl http www puls...