www.pulsar.pl                                                               HPSB5512C                                               

GREEN POWER

 

 

 

7

 

4. Operation and use. 

 
4.1 Overload or short circuit of the PSU output (SCP on) 
In case of overload, the output voltage is automatically shut off, and so is the LED indicator. The restoration 

of the voltage takes place immediately after the failure (overload) is over. 

 
4.2 Disconnection of discharged battery. 

The PSU is equipped with the discharged battery disconnection system. During the battery-assisted operation, 

reducing voltage below 9.5 V at the battery terminals will cause battery disconnection. 

 

4.3 Maintenance. 

Any and all maintenance operations may be performed following the disconnection of the PSU from the 

power supply network. The PSU   does not require performing any specific maintenance measures, however, in 
case of significant dust rate, its interior is recommended to be cleaned with compressed air. In case of fuse 
replacement, use a replacement of the same parameters. 
 

 

 
 
 
 
 
 
 
 

Содержание HPSB 5512C

Страница 1: ...HPSB 5512C v 1 0 HPSB 13 8V 5A 17Ah Buffer switch mode power supply unit EN Edition 1 from 01 07 2014 Supersedes edition...

Страница 2: ...chnical description 1 1 General description A buffer PSU intended for uninterrupted supply to devices that require stabilised voltage of 12V DC 15 The PSU provides voltage of U 13 8V DC with output cu...

Страница 3: ...A AWZ574 or AWZ576 7Ah 1 2 Block diagram Fig 1 Fig 1 The block diagram of the PSU 1 3 Description of PSU components and connectors tab 1 tab 2 fig 2 Part no Fig 2 Description 1 PSU module 2 connectors...

Страница 4: ...e refer to chart 1 Voltage adjustment range 12 14VDC Ripple 120mV p p max Battery charge current 0 5A max 17Ah 5 Short circuit protection SCP electronic automatic return Overload protection OLP 105 15...

Страница 5: ...60950 1 2007 I first Protection grade PN EN 60529 2002 U IP20 Electrical strength of insulation between input input and output circuits of the PSU I P O P between input circuit and PE protection circ...

Страница 6: ...use box The electrical system shall follow valid standards and regulations 2 2 Installation procedure 1 Before installation cut off the voltage in the 230V power supply circuit 2 Mount the PSU in a se...