Pulsar HPSB 5512C Скачать руководство пользователя страница 6

www.pulsar.pl                                                               HPSB5512C                                               

GREEN POWER

 

 

 

6

 

RED LED: 

 

on – the PSU is supplied with 230V AC  

 

off – no 230V AC supply  

 

GREEN LED: 

 

on – DC voltage in the AUX output of the PSU 

 

off – no DC voltage in the AUX output of the PSU 

 

2. Installation. 

 

2.1 Requirements. 
The buffer PSU shall be mounted by a qualified installer with appropriate  permissions and qualifications for 

230V/AC installations and low-voltage installations (required and necessary for a given country). The device shall 
be  mounted  in  confined  spaces,  according  to  the  environment  class  II,  with  normal  air  humidity  (RH=90%  max. 
without  condensation)  and  the  temperature  from  -10°C  to  +40°C.  The  PSU  shall  work  in  a  vertical  positi on  that 
guarantees sufficient convectional air-flow through ventilating holes of the enclosure. 

 

           Before installation, prepare a PSU load balance. During normal operation, the total current drawn by 
the  device    may  not  exceed  I  =  5A

*

.    Maximum  battery  charge  current:  0,5A

*

.  Total  device    current  + 

battery: 5,5A max

*

 
As the PSU is designed for a continuous operation and is not equipped with a power-switch, therefore an 

appropriate  overload  protection  shall  be  guaranteed  in  the  power  supply  circuit.  Moreover,  the  user  shall  be 
informed  about  the  method  of  unplugging  (usually  through  assigning  an  appropriate  fuse  in  the  fuse-box).  The 
electrical system shall follow valid standards and regulations. 
 
 

2.2 Installation procedure. 
 

1. Before installation, cut off the voltage in the 230V power-supply circuit. 
2. Mount the PSU in a selected location and connect the wires. 
3. Connect the power cables (~230Vac) to L-N clips of the PSU. Connect the ground wire to the clip marked by the 
earth symbol PE. Use a three-core cable (with a yellow and green PE protection wire) to make the connection. 
Lead the cables to the appropriate clips through the insulating bushing of the connection board. 
 

 

The shock protection circuit shall be performed with a particular care, i.e. the yellow and 
green wire coat of the power cable shall stick to one side of the terminal - marked with  

 symbol on the PSU enclosure. Operation of the PSU without the properly made and 

fully  operational  shock  protection  circuit  is  UNACCEPTABLE!  It  can  cause  a  device 
failure or an electric shock. 

 
4. Connect the receivers’ cables to the terminals 

V+ (+), V-(-) 

 of the PSU module.  

5. Connect the power (~230V) 
6. Connect the battery (mind the colours):   
- battery output (+V):  BAT+ cable / red, 
- battery output (0V):  BAT – cable / GND / black. 
7. Check the PSU operation indicator: green LED. 
8. Check the PSU output voltage: 
- the PSU voltage without load should amount to U=13.8V DC.   
9. After installing and checking proper working, the enclosure can be closed. 
 
 
3. Operating status indication. 

 
3.1 LED indication of operating status. 
The  is equipped with two diodes on the front panel: 
 
 
 
 
 
 

 
 
 
 

                                                 

*

 

Refer to chart 1 

 

Содержание HPSB 5512C

Страница 1: ...HPSB 5512C v 1 0 HPSB 13 8V 5A 17Ah Buffer switch mode power supply unit EN Edition 1 from 01 07 2014 Supersedes edition...

Страница 2: ...chnical description 1 1 General description A buffer PSU intended for uninterrupted supply to devices that require stabilised voltage of 12V DC 15 The PSU provides voltage of U 13 8V DC with output cu...

Страница 3: ...A AWZ574 or AWZ576 7Ah 1 2 Block diagram Fig 1 Fig 1 The block diagram of the PSU 1 3 Description of PSU components and connectors tab 1 tab 2 fig 2 Part no Fig 2 Description 1 PSU module 2 connectors...

Страница 4: ...e refer to chart 1 Voltage adjustment range 12 14VDC Ripple 120mV p p max Battery charge current 0 5A max 17Ah 5 Short circuit protection SCP electronic automatic return Overload protection OLP 105 15...

Страница 5: ...60950 1 2007 I first Protection grade PN EN 60529 2002 U IP20 Electrical strength of insulation between input input and output circuits of the PSU I P O P between input circuit and PE protection circ...

Страница 6: ...use box The electrical system shall follow valid standards and regulations 2 2 Installation procedure 1 Before installation cut off the voltage in the 230V power supply circuit 2 Mount the PSU in a se...

Страница 7: ...d with the discharged battery disconnection system During the battery assisted operation reducing voltage below 9 5 V at the battery terminals will cause battery disconnection 4 3 Maintenance Any and...

Страница 8: ...later that within 14 days from the delivery to the service centre of the manufacturer 6 The repair period mentioned in item 5 may be prolonged if there are no technical possibilities to carry out the...