![Pulsar HPSB 3512B Скачать руководство пользователя страница 5](http://html1.mh-extra.com/html/pulsar/hpsb-3512b/hpsb-3512b_quick-start-manual_1624885005.webp)
www.pulsar.pl HPSB3512B
GREEN POWER
5
W
H
D
Mechanical parameters (tab. 4)
Enclosure dimensions
250 x 250 x 80+8 [mm] (WxHxD)
Fixation
See figure 2
Fitting battery
7Ah/12V (SLA) max.
160x90x75mm (WxHxD) max
Net/gross weight
1,8 kg / 2kg
Enclosure
Steel plate DC01, thickness: 0,7mm, colour: RAL 9003
Closing
Cheese head screw (at the front), (lock assembly possible)
Connectors
Power-supply:
Φ0,63-2,50 (AWG 22-10)
Outputs: Φ0,63-2,50 (AWG 22-10)
Battery output BAT: 6,3F-2,5
TAMPER output: wires
Notes
The enclosure does not touch the assembly surface so that cables can be led.
Convectional cooling.
Operation safety (tab.5)
Protection class PN-EN 60950-1:2007
I (first)
Protection grade PN-EN 60529: 2002 (U)
IP20
Electrical strength of insulation:
- between input and output circuits of the PSU (I/P-O/P)
- between input circuit and PE protection circuit (I/P-FG)
- between output circuit and PE protection circuit (O/P-FG)
3000 V/AC min.
1500 V/AC min.
500 V/AC min.
Insulation resistance:
- between input circuit and output or protection circuit
100 MΩ, 500V/DC
Operating parameters (tab.6)
Operating temperature
-
10ºC...+40ºC (see: chart 1)
Storage temperature
-
20ºC...+60ºC
Relative humidity
20%...90%, without condensation
Vibrations during operation
unacceptable
Impulse waves during operation
unacceptable
Direct insulation
unacceptable
Vibrations and impulse waves during transport
According to PN-83/T-42106
Chart 1. Acceptable output current from the PSU depending on ambient temperature.
2. Installation.
2.1 Requirements.
The buffer PSU shall be mounted by a qualified installer with appropriate permissions and qualifications for
230V/AC installations and low-voltage installations (required and necessary for a given country). The device shall be
mounted in confined spaces, according to the environment class II, with normal air humidity (RH=90% max. without
condensation) and the temperature from -
10°C to +40°C. The PSU shall work in a vertical position that guarantees
sufficient convectional air-flow through ventilating holes of the enclosure.