www.pulsar.pl HPSBOC7012C
GREEN POWER plus
6
Mechanical parameters (tab. 4)
Dimensions
W=280, H=292, D+D
1
=82+8 [+/- 2mm]
W
1
=285, H
1
=296 [+/- 2mm]
The dimensions of the
battery compartment
190x170x75mm (WxHxD) max
Fixation
See figure 2
Net/gross weight
2,3kg / 2,5kg
Enclosure
Steel plate, DC01 0,7mm colour: RAL 9003
Closing
Cheese head screw x 2 (at the front), (lock assembly possible)
Connectors
Power supply:
Φ0,63-2,50 (AWG 22-10)
Outputs: Φ0,63-2,50 (AWG 22-10), battery output BAT: 6,3F-2,5
TAMPER output: wires
Notes
The enclosure does not adjoin the assembly surface so that cables can be led.
Operation safety (tab.5)
Protection class PN-EN 60950-1:2007
I (first)
Protection grade PN-EN 60529: 2002 (U)
IP20
Electrical strength of insulation:
- between input and output circuits of the PSU (I/P-O/P)
- between input circuit and PE protection circuit (I/P-FG)
- between output circuit and PE protection circuit (O/P-FG)
3000 V/AC min.
1500 V/AC min.
500 V/AC min.
Insulation resistance:
- between input circuit and output or protection circuit
100 MΩ, 500V/DC
Operating parameters (tab.6)
Operating temperature
-
10ºC...+40ºC (see: chart 1)
Storage temperature
-
20ºC...+60ºC
Relative humidity
20%...90%, without condensation
Vibrations during operation
unacceptable
Impulse waves during operation
unacceptable
Direct insulation
unacceptable
Vibrations and impulse waves during transport
According to PN-83/T-42106
Chart 1. Acceptable output current from the PSU depending on ambient temperature.
2. Installation.
2.1 Requirements.
The buffer PSU shall be mounted by a qualified installer with appropriate permissions and qualifications for
230V/AC installations and low-voltage installations (required and necessary for a given country). The device shall be
mounted in confined spaces, according to the environment class II, with normal air humidity (RH=90% max. without
condensation) and the temperature from -
10°C to +40°C. The PSU shall work in a vertical position that guarantees
sufficient convectional air-flow through ventilating holes of the enclosure.
Before installation, prepare a PSU load balance.
1. Output current 6A + 1A battery charge
*
2. Output current 5A + 2A battery charge
*
Total device c battery: 7A max
*
.
*
See chart 1