Pulsar GREEN POWER plus HPSBOC 2512B Скачать руководство пользователя страница 9

www.pulsar.pl                                                      HPSBOC2512B                                                              

GREEN POWER plus

 

 

 

9

 

4. Operation and use. 

 
4.1 Overload or short circuit of the PSU output (SCP on). 

In case of overload, the output voltage is automatically shut off, and so is the LED indicator. The restoration 

of the voltage takes place immediately after the failure (overload) is over. 

 

4.2 Battery-assisted operation.  

In case of a main power outage, the device is immediately switched into a battery-assisted operation. 

 
 
The  PSU  is  equipped  with  the  discharged  battery  disconnection  system.  During  the 

battery-assisted operation, reducing voltage below 9,5V at the battery terminals will cause 
battery disconnection. 

 

4.3 Maintenance. 

Any and all maintenance operations may be performed following the disconnection of the PSU from the 

power supply network. The PSU   does not require performing any specific maintenance measures, however, in 
case of significant dust rate, its interior is recommended to be cleaned with compressed air. In case of fuse 
replacement, use a replacement of the same parameters. 

 
 

 
 
 
 
 
 
 
 
 
 
 
 
 
 
 
 
 
 
 
 
 
 
 
 
 
 
 
 
 
 
 
 
 
 
 
 
 
 
 
 
 
 
 
 
 

Содержание GREEN POWER plus HPSBOC 2512B

Страница 1: ...HPSBOC 2512B v 1 1 HPSBOC 13 8V 2A 7Ah OC Buffer switch mode power supply unit with technical outputs EN Edition 9 from 01 03 2018 Supercedes edition 8 from 01 06 2016 GREEN POWER plus...

Страница 2: ...Technical description 1 1 General description A buffer PSU intended for uninterrupted supply to devices that require stabilized voltage of 12V DC 15 The PSU provides voltage of U 13 8V DC with output...

Страница 3: ...orrect battery voltage 4 EPS AC absence technical output relay type 5 PSU output indicating DC absence PSU failure relay type 6 LoB output indicating battery low voltage relay type 7 EPS AC absence te...

Страница 4: ...WER plus 4 Fig 2 The view of the PSU Description of PSU components and connectors tab 2 fig 3 Element no Fig 3 Description 1 PSU module 2 TAMPER contact sabotage protection NC Tab 2 The components of...

Страница 5: ...Overvoltage protection OVP 16V automatic recovery Excessive discharge protection UVP U 9 5V 5 disconnection of battery terminal Tampering protection system TAMPER indicating unwanted opening of the P...

Страница 6: ...1500 V AC min 500 V AC min Insulation resistance between input circuit and output or protection circuit 100 M 500V DC Operating parameters tab 6 Operating temperature 10 C 40 C see chart 1 Storage tem...

Страница 7: ...The shock protection circuit shall be performed with a particular care i e the yellow and green wire coat of the power cable shall stick to one side of the terminal marked with symbol on the PSU enclo...

Страница 8: ...V In case of absence of DC voltage at the output e g short circuit the output is switched into high impedance state hi Z relay output In case of a failure the contacts of the relay change over CAUTION...

Страница 9: ...o a battery assisted operation The PSU is equipped with the discharged battery disconnection system During the battery assisted operation reducing voltage below 9 5V at the battery terminals will caus...

Страница 10: ...l waste and to collect such WEEE separately The power supply unit is adapted for a sealed lead acid battery SLA After the operation period it must not be disposed of but recycled according to the appl...

Отзывы: