3.2 Technical outputs 

The PSU has indication outputs: 
 

 

EPS - absence of AC supply output

 -  OC  type  output  that  indicates  AC  power  loss.  Under  normal  status,  with  230V  AC  supply,  the  output  is 

connected  to  ground  (L  level 

–  0V).  In  case  of  power  loss,  the  PSU  will  switch  the  output  into  high 

impedance state hi-Z after approx. 10s. 
 

- relay output indicating the absence of AC supply. In case of power loss, the PSU module will switch the relay 

contacts after approx. 10 seconds. 
 

 

CAUTION!

 In Fig.2. the contact set in the potential-free status corresponds to a state with no AC 

power (AC power failure). 
 
 

 

 

PSU 

– technical output indicating absence of DC voltage at the PSU

-  OC type output indicating the PSU failure. In normal state (during correct operation) the output is connected 

to ground  (L  level 

– 0V). In case of absence of DC voltage at the output (e.g. short circuit), the output is 

switched into high impedance state 

– hi-Z. 

     - relay output. In case of a failure, the contacts of the relay change over. 

 
 

CAUTION!

  In  the  Fig.2.  the  set  of  contacts  shows  a  potential-free  status  of  the  relay  which 

corresponds to a state with no DC power (PSU failure). 

 

 

 

LoB 

– technical output indicating battery voltage

-  OC type output. Under normal status (U

BAT

 > 11,5V) the output is connected to ground (L level 

– 0V). In case 

of decrease of battery voltage (U

BAT

 < 11,5V) the output is switched into high impedance state 

– hi-Z. 

      -  relay output. In case of a battery voltage drop U

BAT

 < 11,5V, the contacts of the relay change over. 

        The power supply unit does not feature a battery detection function. In the  case of no battery or non battery 

connected, the output is in the normal mode. 

 
 

CAUTION!

 In the Fig.2. the set of contacts shows a potential-free status of the relay which 

corresponds to a state with low battery level (U

BAT

 <11,5V). 

 

 

Fig. 4. Electrical diagram of OC outputs. 

 
 
 
 
 
 
 
 
 
 
 
 
 
 
 
 
 

 

Содержание GREEN POWER plus HPSBOC 2512B

Страница 1: ...HPSBOC 2512B v 1 1 HPSBOC 13 8V 2A 7Ah OC Buffer switch mode power supply unit with technical outputs EN Edition 9 from 01 03 2018 Supercedes edition 8 from 01 06 2016 GREEN POWER plus...

Страница 2: ...Technical description 1 1 General description A buffer PSU intended for uninterrupted supply to devices that require stabilized voltage of 12V DC 15 The PSU provides voltage of U 13 8V DC with output...

Страница 3: ...orrect battery voltage 4 EPS AC absence technical output relay type 5 PSU output indicating DC absence PSU failure relay type 6 LoB output indicating battery low voltage relay type 7 EPS AC absence te...

Страница 4: ...WER plus 4 Fig 2 The view of the PSU Description of PSU components and connectors tab 2 fig 3 Element no Fig 3 Description 1 PSU module 2 TAMPER contact sabotage protection NC Tab 2 The components of...

Страница 5: ...Overvoltage protection OVP 16V automatic recovery Excessive discharge protection UVP U 9 5V 5 disconnection of battery terminal Tampering protection system TAMPER indicating unwanted opening of the P...

Страница 6: ...1500 V AC min 500 V AC min Insulation resistance between input circuit and output or protection circuit 100 M 500V DC Operating parameters tab 6 Operating temperature 10 C 40 C see chart 1 Storage tem...

Страница 7: ...The shock protection circuit shall be performed with a particular care i e the yellow and green wire coat of the power cable shall stick to one side of the terminal marked with symbol on the PSU enclo...

Страница 8: ...V In case of absence of DC voltage at the output e g short circuit the output is switched into high impedance state hi Z relay output In case of a failure the contacts of the relay change over CAUTION...

Страница 9: ...o a battery assisted operation The PSU is equipped with the discharged battery disconnection system During the battery assisted operation reducing voltage below 9 5V at the battery terminals will caus...

Страница 10: ...l waste and to collect such WEEE separately The power supply unit is adapted for a sealed lead acid battery SLA After the operation period it must not be disposed of but recycled according to the appl...

Отзывы: