www.pulsar.pl                                                      POE044816   

GREEN POWER CCTV PoE

 

 

 

 

- TAMPER output indicating enclosure opening 

- microswitch, NC contacts (enclosure closed), 
0,5A@50V DC (max.) 

Optical indication of operation: 

YES – LED lights  

Technical outputs: 
- FPS technical output indicating output fuse 
activation 
 
 

 
- OC type, 50mA max.  
Normal operation:  L state (0V),  
failure: H state (hi-Z), (automatic return once the normal 
operation is restored) 
- relay type: 1A@ 30VDC/50VAC, delay time: 
approximately 10 seconds 

F1 ÷ F4 fuses 

F 0,5A or PTC 0,5A 

      Mechanical parameters (Table 4). 

Enclosure dimensions 

230 x 281 x 116  mm (WxHxD) 

Mounting 

See Fig. 3 

Net weight 

2,76kg / 2,95kg 

Enclosure 

DC01 steel plate, 1,0mm, RAL 9003 

Closing 

Cylindrical screw x 1 (at the front) lock assembly possible 

Terminals 

Switch mode power supply: 

Φ

0,4-2,5 (AWG 26-10) 

PoE module: 

Φ

0,5-2,1 (AWG 24-12) 

IN1 ÷ IN4 inputs: RJ45 8P8C, shielded 
AUX1 ÷ 4 outputs: RJ45 8P8C, shielded 
TAMPER output: 

Φ

0,8 

Notes 

The enclosure has a 15mm distance from the mounting surface so the cables 
can be led.  

       Safety of use (Table 5). 

Protection class PN-EN 60950-1:2007 

I (first) 

Protection grade PN-EN 60529: 2002 (U) 

IP20 

Insulation electrical strength: 
- between input (network) circuit and the output circuits of the PSU  
(I/P-O/P) 
- between input circuit and PE protection circuit  (I/P-FG) 
- between output circuit and PE protection circuit (O/P-FG) 

 
 
3000 V/AC min. 
1500 V/AC min. 
  500 V/AC min. 

Insulation resistance: 
- between input circuit and output or protection circuit 

 
100 M

, 500V/DC  

Operation parameters (Table 6). 

Operating temperature 

-10ºC...+40ºC (see Figure1) 

Storing temperature 

-20ºC...+60ºC 

Relative humidity  

20%...90%, no condensation 

Vibrations during operation  

unacceptable 

Surges during operation 

unacceptable 

Direct insolation 

unacceptable 

Vibrations and surges during transport 

According 

to 

the 

PN-83/T-42106 

standard 

 
 
2.  Installation. 

 

2.1. Requirements. 

 

The  buffer  PSU  should  be  mounted  by  a  qualified  installer,  holding  relevant  permits  and  licenses 

(applicable and  required  for  a  given  country)  for  230V/AC  and  low-voltage  installations. The  unit  should  be 
mounted  in  confined  spaces,  in  accordance  with  the  2nd environmental  class,  with  normal  relative  humidity 
(RH=90% maximum, no condensation) and temperature range from -10°C up to +40°C. The  power  supply  sh ould  
operate  in  a  vertical position in order to provide free and  convectional  air  flow  through ventilating holes of the 
enclosure.  

 

     During normal operation, the total current drawn by the device should not exceed  

I = 4x0,4A.  

Содержание GREEN POWER CCTV PoE POE044816

Страница 1: ...POE044816 v 1 0 PoE 48V 4x0 4A Switch mode power supply unit for CCTV EN Edition 1 from 28 10 2013 Supersedes the edition GREEN POWER CCTV PoE...

Страница 2: ...ice and operation 4 1 Overload or short circuit of the power supply output 4 2 Maintenance 1 Technical description 1 1 General description The PSU is designed for supply of up to 4 webcams requiring s...

Страница 3: ...e AUX1 AUX4 F500mA circuits 4 Jumper to select melting fuse or PTC polymer fuse 5 Green LED L1 L4 voltage indication at the AUX outputs during normal operation these LEDs are on 6 Network outputs Ethe...

Страница 4: ...chnical parameters electrical parameters Table 3 mechanical parameters Table 4 safety of use Table 5 operation parameters Table 6 Electrical parameters Table 3 Mains supply 88 264V AC Current consumpt...

Страница 5: ...ngth between input network circuit and the output circuits of the PSU I P O P between input circuit and PE protection circuit I P FG between output circuit and PE protection circuit O P FG 3000 V AC m...

Страница 6: ...with a yellow and green PE protection wire to make the connection The power cables should be connected to the appropriate terminals on the connection board through the bushing The shock protection ci...

Страница 7: ...ED is permanently illuminated L1 L4 green LEDs Fig 2 component 5 indicate voltage at the individual outputs of the module L1 for AUX 1 etc Activation of the short circuit overload protection of a give...

Страница 8: ...nufacturer 4 The warranty applies to complete equipment accompanied by a properly filled warranty claim with a description of the defect 5 Should the claim be accepted the manufacturer is obliged to p...

Отзывы: