Service and Maintenance

Spark Plug

 Remove access cover and spark plug boot.

 Use the (included) thin-wall T-socket wrench to remove the

     spark plug by turning it counter-clockwise.

 Inspect spark plug for discoloration and remove carbon

     deposits; replace if necessary.

 Adjust the gap 0.7~0.8mm.

Spark Plug # A5RTC
Gap: 0.7-0.8mm

 Install new or serviced spark plug in reverse order.

Spark Plug torque: 12.5 Nm; 110 in lbs.

Tip:

 If no torque wrench is available turn the spark plug ¼ - ½ turn

       after the gasket contacts the cylinder head.

Adjustment of the Carburetor

This carburetor is not adjustable, only maintenance and cleaning
are possible. We strongly recommend leaving this work to an
authorized Pulsar Service Center.

Oil Change

 Raise the generator up on support blocks on a flat, stable

      surface

② 

Unscrew the knob 

, to remove oil access cover

 Unscrew oil dipstick 

 Place an oil pan under the engine, tilt the generator toward

      the oil pan until all oil has drained; wipe up any spills.

 Refill crankcase with 12 ounces (0.35l) 10w-30 engine oil; check

      with dipstick.

 Tighten oil dipstick, replace oil access cover, and tighten the

      knob.

Air Filter

A dirty air filter can cause poor performance and engine damage.
Perform inspection and cleaning per the maintenance schedule
on page 11.

If the generator is used in high temperature or under high
load, change the oil every 25 hours.

If the generator is used in a dusty or abrasive environment,
service the air filter element every 10 hours; replace it
every 25 hours.

If you miss a maintenance cycle, perform the maintenance
as soon as possible per the table above.

Do not drain the oil immediately after turning off the generator;
allow it to cool completely before servicing it.

Shut down the engine and allow it to cool before performing
any service. Place the generator on a flat, stable surface.
Remove the spark plug boot to prevent accidental engine
start.

NEVER USE ANY GENERATOR INDOORS or in any poorly
ventilated area. Engine exhaust contains carbon monoxide
which can KILL you and others in the area.

NOTICE

DANGER

WARNING

 

 

 

 

 

Содержание GD400BN

Страница 1: ...tate of California to cause cancer birth defects or other reproductive harm support pulsar products com 866 591 8921 STOP DO NOT RETURN TO STORE HAVE QUESTIONS OR NEED SERVICE FUEL SOURCE CIRCUIT BREA...

Страница 2: ...e or more of the notices below Safety Warnings alert you to potential hazards that could cause death injury or damage to property The decals show one of four words DANGER WARNING CAUTION and NOTICE De...

Страница 3: ...bon Monoxide can KILL YOU in minutes Avoid running the generator in the rain or very high condensing humidity Never smoke or allow any heat source near the generator while refueling it Always shut dow...

Страница 4: ...tion practices Lifting Handle Left Enclosure Control Panel Recoil Start Spark Plug Access Rear Panel Muffler Fuel Tank Cap FUEL SOURCE CIRCUIT BREAKER INDICATOR LIGHT LOW IDLE PARALLEL CONNECTION TO A...

Страница 5: ...4 Control Panel FUEL SOURCE CIRCUIT BREAKER INDICATOR LIGHT LOW IDLE PARALLEL CONNECTION TO AVOID DAMAGE DO NOT CONNECT OR DISCONNECT PARALLEL CABLES WHILE THE UNIT IS RUNNING MULTI SWITCH...

Страница 6: ...OR LIGHT Overload Indicator Red When the overload indicator illuminates the generator has detected excess electrical load and the circuit breaker may open trip If the overload indicator illuminates an...

Страница 7: ...surface 2 Unscrew the knob to remove oil access cover 3 Unscrew oil dipstick CIRCUIT BREAKER Gasoline is highly flammable and toxic You must read and understand ALL safety instructions before fueling...

Страница 8: ...ting propane to your generator Never bring a propane tank inside the home or any enclosed structure After connection check for leaks Open the tank supply valve apply soapy water to the gas fittings an...

Страница 9: ...engine start FUEL SOURCE CIRCUIT BREAKER INDICATOR LIGHT LOW IDLE PARALLEL CONNECTION TO AVOID DAMAGE DO NOT CONNECT OR DISCONNECT PARALLEL CABLES WHILE THE UNIT IS RUNNING SELECTOR SWITCH STEP 2 Let...

Страница 10: ...PG valve completely Fuel source switch to LPG FUEL SOURCE CIRCUIT BREAKER INDICATOR LIGHT LOW IDLE PARALLEL CONNECTION TO AVOID DAMAGE DO NOT CONNECT OR DISCONNECT PARALLEL CABLES WHILE THE UNIT IS RU...

Страница 11: ...IRCUIT BREAKER INDICATOR LIGHT LOW IDLE PARALLEL CONNECTION TO AVOID DAMAGE DO NOT CONNECT OR DISCONNECT PARALLEL CABLES WHILE THE UNIT IS RUNNING SELECTOR SWITCH Using the Generator Operating Range o...

Страница 12: ...ust Clean Check Adjust Clean Fuel Hose Inspection Every Two Years Remove Carbon Deposit Check Fill These tasks should be completed by an authorized Pulsar service center Every 125 hours Cylinder Head...

Страница 13: ...til all oil has drained wipe up any spills Refill crankcase with 12 ounces 0 35l 10w 30 engine oil check with dipstick Tighten oil dipstick replace oil access cover and tighten the knob Air Filter A d...

Страница 14: ...lter element and squeeze gently to distribute the oil film evenly 5 Reinstall the air filter element in reverse order 1 Remove fuel tank cap and fuel tank filter screen 2 Clean fuel tank filter screen...

Страница 15: ...tank leave some expansion space Do not run the generator while transporting Protect from direct sunlight Do not transport the generator across rough terrain Engine No Start Fuel System 1 There is no...

Страница 16: ...plash Lubrication Splash Lubrication Noise dB at 7m 62 63 Generator Rated Power kW 1 8 2 8 Rated Voltage V 120 120 Rated Frequency Hz 60 60 Rated Power Factor 1 1 Phase Number Single Phase Single Phas...

Страница 17: ...16 Electrical Schematic 120V 60Hz Electrical Schematic...

Отзывы: