8. Reserve power supply circuit. 

 

The  PSU  is  fitted  with  intelligent  circuits:  battery  charging  circuit  with  the  function  of  the  accelerated 

charging and battery control, which main task is to monitor the condition of the batteries and the connections in the 
circuit. 
If the controller detects a power failure in the battery circuit, appropriate indication and activation of the APS FLT 
and ALARM technical outputs takes place. 
 

       8.1. Battery detection. 

The  control  unit  of  the  PSU  checks  the voltage  at  the  battery  terminal  and,  depending  on  the  measured 

values, determines the appropriate reaction: 

U

BAT

 below 4V  - batteries not connected to the PSU circuits  

U

BAT

 = 4 to 20V - faulty batteries 

U

BAT

 over 20V  - batteries connected to the PSU circuits 

 

       8.2. Protection against short -circuit of the battery terminals. 

 

The  PSU  is  fitted  with  the  circuit  protecting  against  short-circuit  of  the  battery  terminals.  In  case  of  short 

circuit, control circuit immediately disconnects the batteries from the rest of the power supply circuit, so the loss of 
output  voltage  on  power  supply  outputs  is  not  observed.  Automatic  reconnection  of  the  batteries  to  the  PSU's 
circuits is only possible after the removal of the short-circuit and correct connection of the circuits. 
 

       8.3. Protection against reverse battery connection. 

The PSU is protected against reverse connection of the battery terminals. In case of incorrect connection, 

the  F

BAT

  fuse  in  the  battery  circuit  becomes  damaged.    The  return  to  normal  operation  is  possible  only  after 

replacing the fuse and correct connection of the batteries. 

 

     8.4. Deep discharge battery protection UVP. 

The  PSU  is  fitted  with  the  disconnection  system  and  the  battery  discharge  indication.  If the voltage  at  the 

battery terminals drops below 20V±0.2V during battery-assisted operation, acoustic indication will be activated and 
the batteries will be disconnected within 15s.  

The batteries are reconnected to the power supply unit automatically once the AC mains supply is restored. 

 

      8.5. Battery test. 

The  PSU  runs  dynamic  battery  test  every  5  minutes,  temporarily  switching  the  receivers  to  the  battery 

operation  mode.  During  testing, the  control  unit  of  the  PSU  measures  the  electrical  parameters  according  to  the 
implemented measuring method.  
A negative result occurs when: 
- the battery circuit continuity is interrupted,  
- resistance in the battery circuit increases above 300 m

  

- the battery terminal voltage drops below 24V. 

The battery test can be activated manually from the main menu (see section 7.2.1), for example to test the 

replaced batteries. 

The  PSU  is  protected  against  too  frequent  performing  of  the  battery  test,  which  could  result  in 

undercharging. The protection involves blocking the ability to perform test for 30 seconds from the last activation.  

 Ι

n this case, the LCD will display the "WAIT” message in the PSU Settings -> PSU -> Battery test menu. 

 

 

Fig. 27. Temporary lock of the battery test. 

 

This function can be disabled by putting the Z2 jumper on the power supply board (Fig.2 [8]). 
 
 
 
 
 

Содержание EN54-5A17LCD

Страница 1: ...EN54 5A17LCD v 1 0 EN54 27 6V 5A 2x17Ah LCD power supply for fire alarm systems EN Edition 1 from 28 11 2013 Supersedes the edition LCD Version...

Страница 2: ...OSURE OPENING TAMPER 23 6 8 INCREASING THE NUMBER OF OUTPUTS WITH OPTIONAL EN54 LB4 OR EN54 LB8 FUSE MODULES 23 6 9 OVERVOLTAGE PROTECTION OF THE PSU OUTPUT OVP 24 6 10 PSU OVERLOAD 24 6 11 INDICATION...

Страница 3: ...TURE MEASUREMENT 39 8 8 STANDBY TIME 39 9 REMOTE MONITORING OPTIONS WI FI ETHERNET RS485 USB 40 9 1 COMMUNICATION VIA THE USB TTL INTERFACE 40 9 2 ETHERNET NETWORK COMMUNICATION 40 9 3 THE WI FI WIREL...

Страница 4: ...m PowerSecurity to monitor the performance of the PSU remote control options WiFi Ethernet RS485 USB remote battery test required additional modules cooperation with optional EN54 LB4 or EN54 LB8 fuse...

Страница 5: ...al CD Red mounting spacers 4 pieces Red metal mounting brackets for hanging the power supply 4 pieces M8x16 mounting screws 4 pieces PG9 cable glands 4 pieces PG11 cable glands 4 pieces Battery serial...

Страница 6: ...circuit YES YES Low battery indication YES YES Deep discharge battery protection YES YES Protection against short circuit of the battery terminals YES YES Blown battery fuse indication YES YES Chargin...

Страница 7: ...tput current Imax b 5A In case of power loss the PSU switches to battery power providing uninterruptible power supply The PSU is enclosed in a metal casing color RAL 3001 red with battery housing for...

Страница 8: ...oltage AUX2 AUX2 output voltage OVL PSU overload APS battery failure PSU PSU failure ALARM collective failure EXTi EXTi input status EXTo EXTo relay output status LB battery charging 11 Terminals AC A...

Страница 9: ...omponents of the PCB of the EMC filter Fig 3 Element No Description FMAINS fuse in the power supply circuit 230V T6 3A 250V L N power supply connector 230V AC PE protective connector Connector for con...

Страница 10: ...nal module INTR INTE INTW 5 Place to install the EN54 LB4 or EN54 LB8 fuse module 6 TAMPER microswitch contacts of antisabotage protection NC 7 EMC filter module see Table 2 Fig 3 8 2x17Ah batteries 9...

Страница 11: ...cables Installation cables should be firmly connected to the battery side terminals and to the power supply connector The side walls of the housing include the embossings which should be used to carry...

Страница 12: ...g 4 Connect the batteries with the PSU paying special attention to the correct polarity Batteries must be connected in series using the special cable included 6 Switch on the 230V AC supply The corres...

Страница 13: ...e parameters which should be displayed Fig 7 Control panel Table 6 The description of the buttons and LEDs of the LCD panel moves the pointer on the screen next screen selection selection approval qui...

Страница 14: ...he LCD Main screen of the LCD displays the basic electrical parameters and indicates the current status of the power supply Fig 9 Main screen of the LCD The resolution of voltage and current measureme...

Страница 15: ...starts the preview menu allowing to choose one of the four available PSU screens Use the or buttons to choose a proper screen and press the SET button to confirm current parameters of the PSU see sec...

Страница 16: ...current flashing Imax a exceeded See section 6 10 6 11 PSU failure indication highlighted PSU failure See sections 6 4 6 6 5 Battery failure indication highlighted battery failure See sections 6 4 6 6...

Страница 17: ...re of the highest priority If there are more than five failures at the same time use the or buttons to display the next failure 6 4 4 LCD screen history of the parameters To set the screen press the E...

Страница 18: ...nimum the lowest value measured during 5 minutes maximum the highest value measured during 5 minutes of the following parameters UAC mains supply voltage 230V AC UAC MIN mains supply voltage minimum U...

Страница 19: ...ying information about the fault type time of occurrence and the values of other electrical parameters In addition the diagnostic system assigns the failure code for a particular event on the basis of...

Страница 20: ...ing circuit failure Low AUX1 voltage F09 Low AUX2 voltage PSU FLT ALARM Output voltage below 26V F10 Low battery voltage APS FLT ALARM The battery voltage has dropped below 23V during battery assisted...

Страница 21: ...re The output indicates a failure in the battery circuit Under normal status during correct operation the output is closed In case of failure the PSU will switch the output into the open position Fail...

Страница 22: ...n between the PSU s systems and the attached devices Fig 18 Electrical diagram of the EXT IN input The connection of external devices to the EXT IN input is shown in the electrical diagram below OC ou...

Страница 23: ...circuit on the line could cause damage to other receivers connected to the same output The solution is provided by the optional fuse module EN54 LB4 4 channel or EN54 LB8 8 channel while its mounting...

Страница 24: ...croprocessor may disconnect the AUX1 and AUX2 outputs and switch into the battery assisted operation Restart will occur after 1 minute PSU overload is indicated by the PSU FLT and ALARM technical outp...

Страница 25: ...password full access to the PSU s settings User s password locked access to the PSU settings menu Table11 Access ranges Access range PASSWORD Control panel settings PSU settings SERVICE USER Preset p...

Страница 26: ...hange it To do this choose a password that will be changed user s password or service password and enter the new one 7 1 3 Disabling the password If the password is not required it can be turned off T...

Страница 27: ...by pressing the SET button When on the keyboard will be locked automatically if no buttons are pressed within 5 minutes After this time pressing any button on the control panel will display a window w...

Страница 28: ...4 6 NO acoustic indication OFF Section 7 2 2 EXTo output ON output ON see section 4 9 OFF output OFF Section 7 2 3 Delay time for EPS output Setting the delay time for AC power failure indication 10s...

Страница 29: ...1 1 signal every 10s battery mode AC power failure 2 1 signal every 10s mains operation Battery failure undercharged batteries 3 2 signals every 10s battery mode Low battery level 4 Fast signals batt...

Страница 30: ...mation about the changes in the EXTo output is written in the event log of the PSU use the or buttons to display the EXTo output menu press the SET button the prompt will appear at the end of the line...

Страница 31: ...ers responsible for communication between the PSU and the computer namely the address parity and speed should have the same settings for both the PSU and the PowerSecurity program Communication addres...

Страница 32: ...e the same settings for both the PSU and the PowerSecurity program The PSU has preset transmission parameters of 115200 baud 8E1 if these values were changed they should be restored to original settin...

Страница 33: ...isplayed messages Intensity of the LCD backlight can be set in the range from 0 to100 in 10 intervals The display features a function of constant or temporary backlight mode In temporary mode the scre...

Страница 34: ...t date according to which error messages and operation history will be saved Built in real time clock does not take into account leap years and the changes resulting from the switch between summer and...

Страница 35: ...the SET button the prompt will appear next to the hour digits use the or buttons to set the hour press the SET button the prompt will appear next to the minute position use the or buttons to set the m...

Страница 36: ...st of the display text use the or buttons to display the Contrast menu press the SET button the prompt will appear at the end of the line use the or buttons to set the contrast confirm by pressing the...

Страница 37: ...RED POWER 37 press the SET button the prompt will appear at the end of the line use the or buttons to select YES blinking light indicating failure ON NO blinking light indicating failure OFF confirm...

Страница 38: ...ase of incorrect connection the FBAT fuse in the battery circuit becomes damaged The return to normal operation is possible only after replacing the fuse and correct connection of the batteries 8 4 De...

Страница 39: ...tteries hence temperature readings should not be confused with the ambient temperature Temperature measurement and compensation of the battery charging voltage can extend the life of the batteries 8 8...

Страница 40: ...power supply unit power supply current consumption used for the calculation of standby time should be taken into account see section 8 8 9 1 Communication via the USB TTL interface The easiest way of...

Страница 41: ...mounted in a hermetic enclosure protecting against adverse environmental conditions Fig 31 Ethernet communication using the RS485 Ethernet INTRE interface 9 3 The Wi Fi wireless communication The Wi F...

Страница 42: ...adverse environmental conditions Fig 33 The The Wi Fi communication using the RS485 WIFI INTRW interface 9 4 RS485 network communication Another type of network communication is the RS485 communicati...

Страница 43: ...of the program into smaller areas depending on the number of monitored power supplies The program is equipped with manager mode which allows the grouping of power supplies for easier analysis and orie...

Страница 44: ...attery voltage indication Ubat 23V during battery mode Overvoltage protection OVP U 30 5V 0 5V disconnection of the output voltage AUX disconnection automatic return Short circuit protection SCP F6 3A...

Страница 45: ...EP 17 12 or 2 x GP12170 Net gross weight 9 7 10 8 kg Enclosure Steel plate DC01 1 2mm color RAL 3001 red Closing Key lock Terminals Mains supply 0 51 2 AWG 24 12 Outputs 0 51 2 AWG 24 12 Battery outp...

Страница 46: ...ear During the inspection check the batteries and run the battery test 4 weeks after installation re tighten all threaded connections see Fig 2 11 and Fig 3 2 11 1 Battery replacement of the LCD panel...

Страница 47: ...thin 14 days from the delivery to the service centre of the manufacturer 6 The repair period mentioned in point 5 may be prolonged if there are no technical possibilities to carry out the repairs or i...

Страница 48: ...ulsar pl EN54 5A17LCD RED POWER 48 Pulsar K Bogusz Sp j Siedlec 150 32 744 apczyca Polska Tel 48 14 610 19 40 Fax 48 14 610 19 50 e mail biuro pulsar pl sales pulsar pl http www pulsar pl www zasilacz...

Отзывы: