Pulsar EN54-5A17LCD Скачать руководство пользователя страница 18

www.pulsar.pl   

 

 

 

EN54-5A17LCD 

 

 

 

    

RED POWER

 

 
 

18 

 

       

Fig. 14. Screen of the history of PSU’s parameters. 

 

In order to change the displayed parameter, highlight its name by pressing the „SET” button and use the 

„<” or „>” buttons to choose the requested parameter.  Pressing  the  „SET” button  again  will  highlight  the  time 
range of the chart,  which  also can be changed  with the „<” or „>” buttons. Pressing the „SET” button again will 
enable  moving  the  cursor  (vertical  dotted  line  on  the  chart)  along  the  time  line  with  the  „<”  or  „>”  buttons.  The 
values of current parameter and the recording time pointed by the cursor will also be highlighted 

Among the available positions on the chart, it is possible to view the following values: 
- current - the value measured at the end of the measuring cycle 
- minimum - the lowest value measured during 5 minutes 
- maximum - the highest value measured during 5 minutes 
of the following parameters: 
 

U

AC

    

- mains supply voltage (230V AC) 

U

AC MIN

 

- mains supply voltage - minimum 

U

AC MAX

 

- mains supply voltage - maximum 

 
U

AUX1

   

- AUX1 output voltage 

U

AUX1 MIN

 

- AUX1 output voltage, minimum 

U

AUX1 MAX

 

- AUX1 output voltage, maximum 

 
U

AUX2

   

- AUX2 output voltage  

U

AUX2 MIN

 

- AUX2 output voltage, minimum 

U

AUX2 MAX

 

- AUX2 output voltage, maximum  

 
I

AUX

 

 

- output current  

I

AUX MIN

 

- output current, minimum 

I

AUX MAX

 

- output current, maximum  

 
U

BAT

    

- battery voltage 

U

BAT MIN

 

- battery voltage, minimum 

U

BAT MAX

 

- battery voltage, maximum  

 
T

BAT

    

- battery temperature 

T

BAT MIN

 

- battery temperature, minimum 

T

BAT MAX

 

- battery temperature, maximum 

 
- R

BAT

    

- resistance in the battery circuit 

 
 

To optimally read and analyze the values shown in the chart, it is possible to change the time range on the 

bottom axis of the chart. The following ranges are available: 
<8h>  
<24h> 
<2days> 
<week>
 (weekly) 
 
 
 
 
 
 
 
   
 

Содержание EN54-5A17LCD

Страница 1: ...EN54 5A17LCD v 1 0 EN54 27 6V 5A 2x17Ah LCD power supply for fire alarm systems EN Edition 1 from 28 11 2013 Supersedes the edition LCD Version...

Страница 2: ...OSURE OPENING TAMPER 23 6 8 INCREASING THE NUMBER OF OUTPUTS WITH OPTIONAL EN54 LB4 OR EN54 LB8 FUSE MODULES 23 6 9 OVERVOLTAGE PROTECTION OF THE PSU OUTPUT OVP 24 6 10 PSU OVERLOAD 24 6 11 INDICATION...

Страница 3: ...TURE MEASUREMENT 39 8 8 STANDBY TIME 39 9 REMOTE MONITORING OPTIONS WI FI ETHERNET RS485 USB 40 9 1 COMMUNICATION VIA THE USB TTL INTERFACE 40 9 2 ETHERNET NETWORK COMMUNICATION 40 9 3 THE WI FI WIREL...

Страница 4: ...m PowerSecurity to monitor the performance of the PSU remote control options WiFi Ethernet RS485 USB remote battery test required additional modules cooperation with optional EN54 LB4 or EN54 LB8 fuse...

Страница 5: ...al CD Red mounting spacers 4 pieces Red metal mounting brackets for hanging the power supply 4 pieces M8x16 mounting screws 4 pieces PG9 cable glands 4 pieces PG11 cable glands 4 pieces Battery serial...

Страница 6: ...circuit YES YES Low battery indication YES YES Deep discharge battery protection YES YES Protection against short circuit of the battery terminals YES YES Blown battery fuse indication YES YES Chargin...

Страница 7: ...tput current Imax b 5A In case of power loss the PSU switches to battery power providing uninterruptible power supply The PSU is enclosed in a metal casing color RAL 3001 red with battery housing for...

Страница 8: ...oltage AUX2 AUX2 output voltage OVL PSU overload APS battery failure PSU PSU failure ALARM collective failure EXTi EXTi input status EXTo EXTo relay output status LB battery charging 11 Terminals AC A...

Страница 9: ...omponents of the PCB of the EMC filter Fig 3 Element No Description FMAINS fuse in the power supply circuit 230V T6 3A 250V L N power supply connector 230V AC PE protective connector Connector for con...

Страница 10: ...nal module INTR INTE INTW 5 Place to install the EN54 LB4 or EN54 LB8 fuse module 6 TAMPER microswitch contacts of antisabotage protection NC 7 EMC filter module see Table 2 Fig 3 8 2x17Ah batteries 9...

Страница 11: ...cables Installation cables should be firmly connected to the battery side terminals and to the power supply connector The side walls of the housing include the embossings which should be used to carry...

Страница 12: ...g 4 Connect the batteries with the PSU paying special attention to the correct polarity Batteries must be connected in series using the special cable included 6 Switch on the 230V AC supply The corres...

Страница 13: ...e parameters which should be displayed Fig 7 Control panel Table 6 The description of the buttons and LEDs of the LCD panel moves the pointer on the screen next screen selection selection approval qui...

Страница 14: ...he LCD Main screen of the LCD displays the basic electrical parameters and indicates the current status of the power supply Fig 9 Main screen of the LCD The resolution of voltage and current measureme...

Страница 15: ...starts the preview menu allowing to choose one of the four available PSU screens Use the or buttons to choose a proper screen and press the SET button to confirm current parameters of the PSU see sec...

Страница 16: ...current flashing Imax a exceeded See section 6 10 6 11 PSU failure indication highlighted PSU failure See sections 6 4 6 6 5 Battery failure indication highlighted battery failure See sections 6 4 6 6...

Страница 17: ...re of the highest priority If there are more than five failures at the same time use the or buttons to display the next failure 6 4 4 LCD screen history of the parameters To set the screen press the E...

Страница 18: ...nimum the lowest value measured during 5 minutes maximum the highest value measured during 5 minutes of the following parameters UAC mains supply voltage 230V AC UAC MIN mains supply voltage minimum U...

Страница 19: ...ying information about the fault type time of occurrence and the values of other electrical parameters In addition the diagnostic system assigns the failure code for a particular event on the basis of...

Страница 20: ...ing circuit failure Low AUX1 voltage F09 Low AUX2 voltage PSU FLT ALARM Output voltage below 26V F10 Low battery voltage APS FLT ALARM The battery voltage has dropped below 23V during battery assisted...

Страница 21: ...re The output indicates a failure in the battery circuit Under normal status during correct operation the output is closed In case of failure the PSU will switch the output into the open position Fail...

Страница 22: ...n between the PSU s systems and the attached devices Fig 18 Electrical diagram of the EXT IN input The connection of external devices to the EXT IN input is shown in the electrical diagram below OC ou...

Страница 23: ...circuit on the line could cause damage to other receivers connected to the same output The solution is provided by the optional fuse module EN54 LB4 4 channel or EN54 LB8 8 channel while its mounting...

Страница 24: ...croprocessor may disconnect the AUX1 and AUX2 outputs and switch into the battery assisted operation Restart will occur after 1 minute PSU overload is indicated by the PSU FLT and ALARM technical outp...

Страница 25: ...password full access to the PSU s settings User s password locked access to the PSU settings menu Table11 Access ranges Access range PASSWORD Control panel settings PSU settings SERVICE USER Preset p...

Страница 26: ...hange it To do this choose a password that will be changed user s password or service password and enter the new one 7 1 3 Disabling the password If the password is not required it can be turned off T...

Страница 27: ...by pressing the SET button When on the keyboard will be locked automatically if no buttons are pressed within 5 minutes After this time pressing any button on the control panel will display a window w...

Страница 28: ...4 6 NO acoustic indication OFF Section 7 2 2 EXTo output ON output ON see section 4 9 OFF output OFF Section 7 2 3 Delay time for EPS output Setting the delay time for AC power failure indication 10s...

Страница 29: ...1 1 signal every 10s battery mode AC power failure 2 1 signal every 10s mains operation Battery failure undercharged batteries 3 2 signals every 10s battery mode Low battery level 4 Fast signals batt...

Страница 30: ...mation about the changes in the EXTo output is written in the event log of the PSU use the or buttons to display the EXTo output menu press the SET button the prompt will appear at the end of the line...

Страница 31: ...ers responsible for communication between the PSU and the computer namely the address parity and speed should have the same settings for both the PSU and the PowerSecurity program Communication addres...

Страница 32: ...e the same settings for both the PSU and the PowerSecurity program The PSU has preset transmission parameters of 115200 baud 8E1 if these values were changed they should be restored to original settin...

Страница 33: ...isplayed messages Intensity of the LCD backlight can be set in the range from 0 to100 in 10 intervals The display features a function of constant or temporary backlight mode In temporary mode the scre...

Страница 34: ...t date according to which error messages and operation history will be saved Built in real time clock does not take into account leap years and the changes resulting from the switch between summer and...

Страница 35: ...the SET button the prompt will appear next to the hour digits use the or buttons to set the hour press the SET button the prompt will appear next to the minute position use the or buttons to set the m...

Страница 36: ...st of the display text use the or buttons to display the Contrast menu press the SET button the prompt will appear at the end of the line use the or buttons to set the contrast confirm by pressing the...

Страница 37: ...RED POWER 37 press the SET button the prompt will appear at the end of the line use the or buttons to select YES blinking light indicating failure ON NO blinking light indicating failure OFF confirm...

Страница 38: ...ase of incorrect connection the FBAT fuse in the battery circuit becomes damaged The return to normal operation is possible only after replacing the fuse and correct connection of the batteries 8 4 De...

Страница 39: ...tteries hence temperature readings should not be confused with the ambient temperature Temperature measurement and compensation of the battery charging voltage can extend the life of the batteries 8 8...

Страница 40: ...power supply unit power supply current consumption used for the calculation of standby time should be taken into account see section 8 8 9 1 Communication via the USB TTL interface The easiest way of...

Страница 41: ...mounted in a hermetic enclosure protecting against adverse environmental conditions Fig 31 Ethernet communication using the RS485 Ethernet INTRE interface 9 3 The Wi Fi wireless communication The Wi F...

Страница 42: ...adverse environmental conditions Fig 33 The The Wi Fi communication using the RS485 WIFI INTRW interface 9 4 RS485 network communication Another type of network communication is the RS485 communicati...

Страница 43: ...of the program into smaller areas depending on the number of monitored power supplies The program is equipped with manager mode which allows the grouping of power supplies for easier analysis and orie...

Страница 44: ...attery voltage indication Ubat 23V during battery mode Overvoltage protection OVP U 30 5V 0 5V disconnection of the output voltage AUX disconnection automatic return Short circuit protection SCP F6 3A...

Страница 45: ...EP 17 12 or 2 x GP12170 Net gross weight 9 7 10 8 kg Enclosure Steel plate DC01 1 2mm color RAL 3001 red Closing Key lock Terminals Mains supply 0 51 2 AWG 24 12 Outputs 0 51 2 AWG 24 12 Battery outp...

Страница 46: ...ear During the inspection check the batteries and run the battery test 4 weeks after installation re tighten all threaded connections see Fig 2 11 and Fig 3 2 11 1 Battery replacement of the LCD panel...

Страница 47: ...thin 14 days from the delivery to the service centre of the manufacturer 6 The repair period mentioned in point 5 may be prolonged if there are no technical possibilities to carry out the repairs or i...

Страница 48: ...ulsar pl EN54 5A17LCD RED POWER 48 Pulsar K Bogusz Sp j Siedlec 150 32 744 apczyca Polska Tel 48 14 610 19 40 Fax 48 14 610 19 50 e mail biuro pulsar pl sales pulsar pl http www pulsar pl www zasilacz...

Отзывы: