www.pulsar.pl
EN54-2A17
RED POWER
24
6.3.6. Setting the communication address
Adr”
applies to cooperation with
PowerSecurity.
All power supplies are factory-set to address 1.
All the parameters responsible for communication between the PSU and the computer, namely the
address, parity and speed should have the same settings for both the PSU and the PowerSecurity program.
Communication address allows to identify power supply units in the same communication network.
- simultaneously press
the „<,>” rightmost and leftmost buttons
-
The „tSt” parameter will be displayed
-
use the „<” or „>” buttons to display the „Adr” parameter
-
press „OK”
- The current address of the PSU will be displayed
-
use the „<” or „>” buttons in order to set the address
1÷ 247
– address of the PSU during the communication with the computer
-
confirm by pressing „OK”
-
in order to return to the main menu, simultaneously press the „<,>” rightmost and leftmost
buttons
6.3.7. Setting the transmission speed
„trS”
applies to cooperation with
PowerSecurity.
All the parameters responsible for communication between the PSU and the computer, namely the
address, parity and speed should have the same settings for both the PSU and the PowerSecurity program.
The PSU has preset transmission parameters of 115200 baud 8E1; if these values were changed, they
should be restored to original settings.
-
simultaneously press the „<,>” rightmost and leftmost buttons
-
The „tSt” parameter will be displayed