www.pulsar.pl
EN54-2A17
RED POWER
17
- press
„OK” button
- the number 2, denoting the next number of failure in the memory, will be displayed.
Then, after one second, the next failure code will be displayed automatically
- if the memory has more failures, pressing the "OK" button will result in displaying subsequent
codes
-
The „- - -„ parameter on the display marks the end of the list of failures
6.2.8. List of failure codes and information messages.
The PSU indicates the operation status with the appropriate code. The codes are divided into two
groups,
marked with the initial letters "F" or "
I”.
The codes beginning with the letter "F" indicate a failure. The codes that begin with the letter "I" indicate the
correct operation of the PSU or repaired fault, involving, for example, fuse replacement: "I03 - BAT fuse
replaced”.
Table 8. List of PSU failure codes.
Failure
code
Information
Technical
output
activation
Causes
Additional
information
F01
AC power fail!
EPS FLT
ALARM
- No AC mains supply
- F
MAIN
fuse failure
F02
AUX1 fuse fail!
PSU FLT,
ALARM
- Blown F
AUX1
fuse
AUX2 fuse fail!
- Blown F
AUX2
fuse
F03
BAT fuse fail!
APS FLT,
ALARM
- Blown F
BAT
fuse
- Short circuit in the battery circuit
- Short circuit in the AUX output circuit
F04
Output overload!
PSU FLT,
ALARM
- PSU overload
Section 6.9
F05
Battery
undercharged!
APS FLT,
ALARM
- Spent batteries
- Undercharged batteries
Section 7
F06
High AUX1
voltage!
PSU FLT,
ALARM
- Output voltage over 29.2V
High AUX2
voltage!
F08
Charge circuit fail!
PSU FLT,
ALARM
- The output voltage of the PSU set too low , below
26V
- Battery charging circuit failure
F09
Low AUX1
voltage!
PSU FLT,
ALARM
- Output voltage below 26V
Low AUX2
voltage!
F10
Low battery
voltage!
APS FLT,
ALARM
- The battery voltage has dropped below 23V (during
battery-assisted operation
F11
Low battery volt.
–
off!
APS FLT,
ALARM
- the battery voltage has dropped below 20V (during
battery-assisted operation)
Section 7.4
F12
External input
EXTi!
ALARM
- Activation of the input of collective failure: EXTi
Section 6.5
F14
Temp. sensor
fault!
PSU FLT,
ALARM
- Faulty temperature sensor
- Temperature sensor disconnected
Section 7.7