USER INTERFACE MODULE AND FUNCTIONS 

LCD DISPLAY

   A 2 line, 16 character per line, LCD display is 

used to set up, and indicate the status of, the 

ChromaFlood and 

ChromaBatten

At switch on, the display shows: 

Press the 

ñ

 (Up)  or 

ò

 (Down)  keys  to cycle through the Menu 

Options (see 

LCD Display Sheet

). 

Press the 

 key on the 

UIM 

to change the settings.

 

Note:

 Program Mode self cancels after ~30 seconds if no keys have 

been pressed. 

Note:

 if, at  any time, the display shows 

Receiving: ERROR

, then 

there is a problem with  the  DMX signal.  It could be wiring, 
termination or poorly implemented DMX. 

?  DMX Address –

 

depending on the operating mode, a block 

of 3, 6, 9, 10, 36, 42 or 46 channels is received from the DMX signal 
– see 

Channel Assignments  Tables

. The 

DMX Address 

is the 

number of the first channel in the block. 
To set the required 

DMX Address

, press the 

ñ

 or 

ò

 keys on the 

UIM

 until the display shows 

DMX Address: 

Press the 

X (change)

 key on the 

UIM

, then set the start address 

using the 

ñ

 or 

ò

 keys.  These keys repeat if held down. 

When the  required 

DMX Address

 number shows in the display, 

press the 

ü

 

(Yes)

 key to save changes or 

X (Back)

 key to restore 

the previous settings. 

Note:

 the 

Receiving:

 text (NO SIGNAL / PMX / DMX / ERROR) in 

the display is for information only. 

?  ChromaZone Mode -

 the unit can be run in similar modes 

to the ChromaZone.  The options are 3, 6, 9, 10, 36, 42 and 46 
channel modes – see 

Channel Assignments Tables

To set the required 

Mode

, press the 

ñ

 or 

ò

 keys on the 

UIM

 until 

the display shows 

ChromaZone Mode

:

 

Press the 

X (change)

 key on the 

UIM

, then select the required mode 

using the

ñ

 or 

ò

 keys. 

When the required 

ChromaZone Mode

 shows in the display, press 

the 

ü

 

(Yes)

 key to save changes or 

X (Back)

 key to restore the 

previous settings. 

?  Channels per Fixture –

 the 

CFLD

 and 

CBAT

 can be run 

in 3 channels per fixture or 6

(CFLD)

 / 9

(CBAT)

 channels per fixture 

modes.  The 6/9 channel modes allow a chase to be run across the 
fixture.  This is particularly effective in the 

CBAT

 where the Batten is 

divided into 3 fixtures, each of RGB. 
To set the required number of 

Channels per Fixture

, press the 

ñ

 or 

ò

 keys on the 

UIM

 until the display shows 

Channels per Fixture 

:

 

Press the 

X (change)

 key on the 

UIM

, then select the required 

number using the 

ñ

 or 

ò

 keys. 

When the required number of 

Channels per Fixture

 shows in the 

display, press the 

ü

 

(Yes)

 key to save changes or 

X (Back)

 key to 

restore the previous settings. 

?  Fixture number:

  the 36  RGB outputs from the built in 

ChromaZone are divided into fixture groups.    36 divided by the 
channels per fixture (set above) gives the number of fixtures available 
from the data block. 
For example, if you set the channels per fixture on a 

CBAT

 to 9, the 

maximum number of fixtures available will be 4.  See the 

Channel 

Assignments Table

 for channel and fixture number colour details. 

To set the required 

fixture number

, press the 

ñ

 or 

ò

 keys on the 

UIM

 until the display shows 

Fixture number

:

 

Press the 

X (change)

 key on the 

UIM

, then select the required 

number using the 

ñ

 or 

ò

 keys. 

When the required 

Fixture number

 shows in the display, press the 

ü

 

(Yes)

 key to save changes or 

X (Back)

 key to restore the previous 

settings. 

?  Chase patterns:

 may be 

6 or 12 way

.  E.g. two 

CBAT

s set 

for 9 Channels per Fixture (3 x RGB) will run a 6 way chase. 
To set the required 

chase patterns

, press the 

ñ

 or 

ò

 keys on the 

UIM

 until the display shows 

Chase patterns

:

 

Press the 

X (change)

 key on the 

UIM

, then select 

6 or 12 way

 using 

the 

ñ

 or 

ò

 keys. 

When the required 

chase pattern way number

 shows in the 

display, press the 

ü

 

(Yes)

 key to save changes or 

X (Back)

 key to 

restore the previous settings. 

?  Channel 10:

 

may be set as a Grand Master for the 36 RGB 

channels only, OR as a Global Grand Master for the 36 RGB 
channels, the ALL Red ,Green and Blue, and the Chase Levels 
To set the required 

Ch.10

 mode of operation, press the 

ñ

 or 

ò

 keys 

on the 

UIM

 until the display shows 

Ch.10…

:

 

Press the 

X (change)

 key on the 

UIM

, then select the required 

number using the 

ñ

 or 

ò

 keys. 

When the required 

Ch.10

 operation shows in the display,  press the 

ü

 

(Yes)

 key to save changes or 

X (Back)

 key to restore the previous 

settings. 

?  Input Smoothing

 

ON

 or 

OFF

.   To  disable the input 

smoothing,  e.g.  for fast response to video graphics signals, set to 

OFF

 

To turn the 

Input Smoothing

 ON/OFF, press the 

ñ

 or 

ò

 keys on 

the 

UIM

 until the display shows

 Input Smoothing: 

Press the 

X (change)

 key on the 

UIM

, then select the required state 

using the

ñ

 or 

ò

 keys. 

When the required state shows in the display, press the 

ü

 

(Yes)

 key 

to save changes or 

X (Back)

 key to restore the previous settings. 

?  Low Voltage Supply -

 ON

 or 

OFF

.  To connect the LVS to 

pin 5 of the MALE XLR, set to 

ON

The LVS is used to power some PULSAR controllers, e.g. Outstation 
OS1.  24V at up to 250mA d.c. is available. 
To turn the 

Low Voltage Supply

 ON/OFF, press the 

ñ

 or 

ò

 keys 

on the 

UIM

 until the display shows

 Low Voltage Supply is: 

Press the 

X (change)

 key on the 

UIM

, then select the required state 

using the

ñ

 or 

ò

 keys. 

When the required state shows in the display, press the 

ü

 

(Yes)

 key 

to save changes or 

X (Back)

 key to restore the previous settings. 

?  DMX Line Termination

 

 

ON

 or 

OFF

, set the last unit in 

the DMX cable run to 

ON

, all others to 

OFF

.  Errors can often occur if 

the DMX line is not terminated.  DMX errors are shown in the display 
as:  

To turn the 

DMX Line Termination

 ON/OFF, press the 

ñ

 or 

ò

 keys 

on the 

UIM

 until the display shows

 DMX Line Termination: 

Press the 

X (change)

 key on the 

UIM

, then select the required state 

using the 

ñ

 or 

ò

 keys. 

When the required state shows in the display, press the 

ü

 

(Yes)

 key 

to save changes or 

X (Back)

 key to restore the previous settings. 

?  If NoSignal use:

  In the event the 

CFLD

 or 

CBAT

  is not 

receiving a DMX signal (e.g. controller no longer present), the unit 
may either  use the user-programmable Stand Alone Settings (see 

Stand Alone Settings View/Change

 below) OR continue to use the 

Last DMX Packet received. 
To select the 

If NoSignal use:

 requirement, press the 

ñ

 or 

ò

 keys 

on the 

UIM

 until the display shows

 If NoSignal use 

Press the 

X (change)

 key on the 

UIM

, then select the requirement 

using the 

ñ

 or 

ò

 keys. 

When your requirement is showing in the display, press the 

ü

 

(Yes)

 

key to save changes or 

X (Back)

 key to restore the previous settings. 

?  Stand Alone Settings View/Change 

There are three possibilities depending on: 
a) whether there is an input signal and 
b) whether "If NoSignal use:" is set to "Stand Alone Mode" or set to 
"Last DMX Packet". 

1.  No Use Stand Alone Mode: 
The current Stand Alone Settings may be viewed, changed and 
saved as the new Stand Alone Settings. 
2.  No Use Last DMX Packet: 
The channel levels of the Last DMX Packet (if any) may be viewed, 
changed and saved as the new Stand Alone Settings. 
3.  Signal present: 
The incoming signal overwrites any changes made but these 
incoming channel levels may be set at the controller,  viewed and 
saved as the new Stand Alone Settings. 
 

DMX Address: 

n

 

Receiving: 

ERROR

 

DMX Address: n

 (where n=1 to 512) 

Receiving:

NO SIGNAL or DMX or PMX or ERROR 

Содержание Chromabatten CBAT100

Страница 1: ...ChromaFlood and ChromaBatten have a colour code letter This signifies the finished colour of the fixture B Black S Silver Other colours may become available please check with Pulsar if required The ChromaFlood and ChromaBatten have a thermal management system This progressively reduces the power to the LEDs if the internal temperature exceeds limits set by the software Excess temperature will occu...

Страница 2: ...he UIM then select 6 or 12 way using the ñ or ò keys When the required chase pattern way number shows in the display press the ü Yes key to save changes or X Back key to restore the previous settings Channel 10 may be set as a Grand Master for the 36 RGB channels only OR as a Global Grand Master for the 36 RGB channels the ALL Red Green and Blue and the Chase Levels To set the required Ch 10 mode ...

Страница 3: ...store Factory Default Settings Press the X change key on the UIM then press the ü Yes key to restore defaults or X Back key to exit The factory default settings are DMX Address 1 ChromaZone Mode 46 Channel Channels per Fixture 3 CFLD 9 CBAT Fixture number 1 Chase patterns 12 Way Channel 10 Grand Master for the 36 RGBs only Input Smoothing ON Low Voltage Supply ON DMX Line Termination OFF If NoSign...

Страница 4: ...ChromaFlood100 and ChromaFlood200 Mechanical Details ...

Страница 5: ...xture 12 Blue 42 Fixture 6 Blue 2 42 Fixture 4 Blue 3 46 Channel Mode 3 Channels Fixture 6 Channels Fixture 9 Channels Fixture 1 9 as 9 Channel Mode 1 9 as 9 Channel Mode 1 9 as 9 Channel Mode 10 36xRGBGrand Master 10 36xRGB Grand Master 10 36xRGB Grand Master OR OR OR 10 Global Grand Master 10 Global Grand Master 10 Global Grand Master 11 Fixture 1 Red 11 Fixture 1 Red 1 11 Fixture 1 Red 1 12 Fix...

Страница 6: ...1 14 89 228 Rainbow Strobe 13 86 220 White Any Colour Strobe Channels 1 2 3 set colour 83 212 White Any Colour Crossover Channels 1 2 3 set colour 12 80 204 Blue Yellow Wave Reverse 77 196 Blue Yellow Wave Forward 73 188 Green Magenta Wave Reverse 11 70 180 Green Magenta Wave Forward 67 172 Red Cyan AnyCol Op Col Wave Forward 10 64 164 Red Cyan AnyCol Op Col Wave Reverse Channels 1 2 3 set colour ...

Страница 7: ...hing t Low Voltage Supply is t DMX Line Termination t VIEW Sig SET No Sig Chan Levels DMX Address n Receiving t X Change X Restore If NoSignal use t Stand Alone Sett ings View Change ChromaZone Mode nn Channels 3 6 9 10 36 42 46 3 6 FLOOD 9 BATTEN 1 12 of 12 1 6 of 6 FLD 1 4 of 4 BAT 6 Way 12 Way CH10 36xRGB GM CH10 Global GM ON Gentle Smooth OFF Fast Video ON OFF ON OFF Stand Alone Mode Last DMX ...

Страница 8: ... apparatus before lightning storms or when unused for long periods Refer all servicing to suitably qualified service personnel Servicing is required when the apparatus has been damaged in any way such as power supply cord or plug damaged liquid has been spilled or objects have fallen into the apparatus the apparatus has been exposed to rain or moisture does not operate normally or has been dropped...

Страница 9: ...the internal temperature exceeds predefined limits When mounting the ChromaBatten300 at an angle other than horizontal it is essential that the cable end is at the lowest point and the display at the top as shown in the picture to the left This mounting arrangement locates the internal temperature sensor at the hottest point the top Failure to observe these essential mounting arrangements may resu...

Отзывы: