Page 

26

 

Chapter 4  

Programming Guide 

Level

Level

Level

Level    

Example 1 Level Measurement  

 

 
 

empty distance (P105), 3.5m  

100%, span (P106), 3.2m              
(output = 5 volts) 

 high alarm on (P213), 2.5m 

 high alarm off (P214), 2.4m 

 low alarm off (P224), 0.6m 

 low alarm on (P223), 0.5m 

0% , empty level (output = 0 volts) 

 

In  this  example,  a 

blackbox

  and  dB6  is  being  used  to  monitor  a  moving 

level  within  a  vessel  and  is  required  to  provide  a  0  to  5  volt  output 
proportional  to  the  level,  over  a  range  of  3.2m.  In  addition  when  the  level 
rises to 2.5m, Relay  ‘1’ is required to give a high alarm and rest  when  the 
level falls to 2.4m. In the event that the level should fall to 0.5m then Relay 
‘2’ is to give a low alarm and reset once the level rise to 0.6m. 

Содержание Blackbox

Страница 1: ...blackbox Level 133 INSTRUCTION MANUAL P P P PULSAR ULSAR ULSAR ULSAR Process Measurement Process Measurement Process Measurement Process Measurement ...

Страница 2: ......

Страница 3: ...cess guarantee for the this product and shall have no liability in respect of any loss injury or damage whatsoever arising out of the application or use of any product or circuit described herein Every effort has been made to ensure accuracy of this documentation but Pulsar Process Measurement Limited cannot be held liable for any errors Pulsar Process Measurement Limited operates a policy of cons...

Страница 4: ......

Страница 5: ...nication Port Configuration 16 Handheld Communicator Optional 16 Operating the Controls 17 Display 17 Keypad 18 Run Mode 20 LED s 21 Program Mode 21 How to Access Program Mode 21 Test Mode 23 LED s 24 Using the RS232 Serial Interface 24 Parameter Defaults 25 Factory Defaults 25 Chapter 4 Programming Guide 26 Level 26 Example 1 Level Measurement 26 Example 2 Alternating Control pump down 28 Chapter...

Страница 6: ...ptions 50 Failsafe 50 Output Parameters 51 Range 51 Operation 51 Setpoint 52 Limits 52 Trim 52 Failsafe 53 Compensation Parameters 54 Offset 54 Temperature 54 Stability Parameters 55 Damping 55 Filters 55 Echo Processing Parameters 56 Transducer Status 56 System Parameters 57 Passcode 57 System Information 57 Date Time 58 Daylight Saving Time 58 Test Parameters 62 Simulation 62 Hardware 63 Chapter...

Страница 7: ...t your installation is as simple as possible About this Manual About this Manual About this Manual About this Manual It is important that this manual is referred to for correct installation and operation There are various parts of the manual that offer additional help or information as shown Tips Tip At various parts of this manual you will find tips to help you Additional Information Additional I...

Страница 8: ...ackbox level system is available in a variety of different versions offering a wide choice of output options The blackbox is very easy to use and may be calibrated quickly and simply via a laptop using the software supplied with the unit or alternatively by using the optional hand held calibrator which connects to the unit via the RS232 interface and provides an onboard LCD display All models of t...

Страница 9: ...ue target level in the face of competing echoes from pipes pumps or other obstructions The blackbox can measure from zero to 40m from the transducer to the surface being monitored dependent on the transducer used The blackbox can measure level space or distance and provide a representative output There are two user definable relays with individual setpoints which can be programmed to activate alar...

Страница 10: ...y and to BS EN61010 1 1993 for low voltage directive Performance Accuracy 0 25 of the measured range or 6 mm whichever is greater Resolution 0 1 of the measured range or 2 mm whichever is greater Max range Dependant on transducer maximum 40m dB40 Min range Dependent upon transducer minimum zero dB Mach 3 Rate response fully adjustable Echo Processing Description DATEM Digital Adaptive Tracking of ...

Страница 11: ...wer typically 5W Fuses 50 mA at 200 240 VAC 100 mA at 90 120 VAC Remote Communicator Power Supply Power supplied via blackbox RS232 interface Pulsar Process Measurement Limited operates a policy of constant development and improvement and reserve the right to amend technical details as necessary ...

Страница 12: ... 10 50 60Hz depending on the position of the selector switch The DC is 10 28V In all cases the blackbox will typically consume 5W of power with a maximum of 10W Location Location Location Location All electronic products are susceptible to electrostatic shock so follow proper grounding procedures during installation The blackbox level controller must be mounted in a non hazardous safe Area and the...

Страница 13: ...ount the enclosure bear in mind the following Easy access to the enclosure is maintained The mounting surface is vibration free The ambient temperature is between 20ºC and 50ºC There should be no high voltage cables or inverters close by ...

Страница 14: ...wn below The blackbox should be mounted by drilling four holes suitable for size 8 screws length and type to suit your application And fix all four screws by removing the top cover to access the pre moulded mounting holes which are located in the base of the enclosure under the lid retaining screws ...

Страница 15: ...Page 9 The full dimensions of the enclosure are as shown below Cable Entry There are 3 x M20 cable glands suitable for 6 12mm cables fitted to the base of the blackbox enclosure ...

Страница 16: ...on Details Terminal Connection Details Terminal Connection Details Terminal Connection Details The terminal strip is as detailed below There is also a wiring diagram attached to the board directly underneath the terminal strip ...

Страница 17: ...re the transducer to the blackbox transducer terminals as detailed below Red Power Terminal 19 White Signal Terminal 20 Black 0 volts Terminal 18 Green screen SCR Terminal 17 When using 2 core screened extension cable the Black and Green wires of the transducer should be connected to the screen of the extension cable and connected to the 0 volts terminal Terminal 18 For Zone 1 applications a trans...

Страница 18: ...0 to 5VDC into a minimum load of 10KΩ RS232 Serial Interface The serial interface is used to programme the blackbox either via a PC standard using the software supplied or alternatively using the hand held calibrator optional Voltage Selector and Fuse Location Voltage Selector and Fuse Location Voltage Selector and Fuse Location Voltage Selector and Fuse Location The voltage selector switch and AC...

Страница 19: ... isolating them from the blackbox Interconnecting cables must be adequately insulated for IEC 664 Category II installations Strip back 30 mm of the outer insulation of the cable Strip 5 mm of insulation from the end of each conductor Twist all exposed strands of the conductor together Insert the stripped conductor into the terminal block as far as it will go and tighten the terminal block screw En...

Страница 20: ...nce any problems with the unit then please contact Pulsar Process Measurement for advice To clean the equipment wipe with a damp cloth Do not use any solvents on the enclosure Important Information The unique DATEM software comes into operation as soon as power is applied and is designed to monitor a moving level or target with the transducer in a fixed position If after any period of use it shoul...

Страница 21: ...e computer via its serial port to the blackbox RS232 serial interface RJ11 connector located on the terminal connector strip inside the blackbox enclosure Double click the Handheld Programmer icon installed on your desktop and the PC will automatically connect to the blackbox Once connected you will briefly see the message illustrated on the display below which after connecting successfully will t...

Страница 22: ...tor Op Handheld Communicator Optional tional tional tional The optional Handheld communicator can be used to programme any number of blackbox units and works in a similar way to the PC Software Connect the Handheld Communicator with the cable supplied to the RS232 interface via the RJ11 connector located on the terminal connector inside the blackbox enclosure Once connected you will briefly see a ...

Страница 23: ...display is used to read information on the Menu System Parameter Number and parameter details and values which can be entered During Test Mode the display is used to monitor the simulated level 1234 56 mm 1 Main Display 6 digit numeric display Run Mode current measurement displayed dependent on mode and measurement unit s chosen and value of Hot Key function selected Program Mode displays paramete...

Страница 24: ...e shown below Hot Key Run Mode Program Mode Not used with blackbox 133 Not used with blackbox 133 Echo Confidence echo strength H A L L average peak noise temperature Not used with blackbox 133 Not used with blackbox 133 Reset parameter to default setting Instantaneous mA output Not used with blackbox 133 Gives readings of Distance Level or Space in units of measurement Not used with blackbox 133 ...

Страница 25: ...ate the level moving up and down 1 Used to confirm each action for example select a menu option or when entering a parameter number or value 2 Used to confirm questions asked by your blackbox such as before restoring factory defaults Used to navigate up a level in the menu system and back to run mode Used to cancel a value entered in error Numeric Keys These keys are used for entering numerical in...

Страница 26: ...hen the blackbox is switched on for the first time it will provide an output proportional to the distance from the transducer to the target in metres All relays by default are switched off If either the PC Programming Software standard or the Hand Held Calibrator optional are connected to the blackbox via the RS232 interface whilst the blackbox is in the RUN mode then the current measurement will ...

Страница 27: ...e This mode is used to set up the blackbox or change information already set You must use either the PC Software supplied standard or alternatively the unit can be set up with a Hand Held Calibrator optional both of which must be connected to the blackbox via the RS 232 Serial Interface Entering a value for each of the parameters that are relevant to your application provides all the programming i...

Страница 28: ...rsor keys to scroll left and right between these you can press ENTER at any time to select it and take you to the sub menu Each of these options along with their sub menus are described in Chapter 5 Parameter Guide When you move down into the sub menu you can scroll round using the arrow keys press ENTER to go to the required section of parameters Once you have reached the relevant section scroll ...

Страница 29: ...the last parameter you edited by pressing when you first enter program mode Test Mode Test Mode Test Mode Test Mode Test mode is used to simulate the application and confirm that all parameters and relay setpoints have been entered as expected During simulation there is a choice of whether the relays will physically change state hard simulation or not soft simulation the LED s will always change s...

Страница 30: ...crement P981 or increase the value in rate P982 To make the simulated level move faster increase the value in increment P981 or decrease the value in rate P982 LED s There are two LED s which can be seen through the lid of the blackbox enclosure which will indicate the status of the relays whilst in simulation as follows Green Red Run Mode Off Off Relays are in there OFF state Constant On Off Rela...

Страница 31: ...ate P931 and time P932 in the blackbox were set at the factory but may need checking and amending if for example the application is in a time zone other than GMT see Chapter 5 Parameter Guide for full details TIP In some applications it is simplest to empty the vessel take a reading from the blackbox for distance and then setup the empty level to this figure Once you are satisfied with the install...

Страница 32: ...y level output 0 volts In this example a blackbox and dB6 is being used to monitor a moving level within a vessel and is required to provide a 0 to 5 volt output proportional to the level over a range of 3 2m In addition when the level rises to 2 5m Relay 1 is required to give a high alarm and rest when the level falls to 2 4m In the event that the level should fall to 0 5m then Relay 2 is to give...

Страница 33: ... 3 5 P106 Span 3 2 Relays Relay 1 P210 Relay 1 Type 1 Alarm P211 R1Function 1 Level P212 R1 ID 2 High P213 R1 Set 1 2 5 P214 R1 Set 2 2 4 Relay 2 P220 Relay 1 Type 1 Alarm P221 R1Function 1 Level P222 R1 ID 4 Low P223 R1 Set 1 0 5 P224 R1 Set 2 0 6 Programming is now complete and the unit can be returned to the run mode press CANCEL until Run Mode Is displayed on the display press ENTER and the bl...

Страница 34: ...ut 0VDC pump 2 on P 223 1 4m pump 1 on P 213 1 0m In this example a blackbox with dB6 is being used to control pumps on a pump down application there are two pumps and the duty pump is to be alternated between the pumps This will operate as follows During normal operation pump 1 will come on at 0 8 m and pump down to 0 5 m The setpoints are then shifted to pump 2 which will come on first next time...

Страница 35: ...106 Span 4 7 Relays Relay 1 P210 Relay 1 2 Control P211 R1Function 1 General P212 R1 ID 2 Alternate P213 R1 Set 1 1 0 P214 R1 Set 2 0 5 Relay 2 P220 Relay 1 2 Control P221 R1Function 1 General P222 R1 ID 2 Alternate P223 R1 Set 1 1 4 P224 R1 Set 2 0 5 Programming is now complete and the unit can be returned to the run mode press CANCEL until Run Mode Is displayed on the display press ENTER and the...

Страница 36: ...how all the various parts can be found using the menu system Top Level Menu Application Relays Data Logs Display Output Compensation Stability Echo Process System Test Application Menu Operation Distances Remote Alarm SMS Time P100 Mode P104 Measnt Units P985 Tel No 1 P995 Interval P101 Xducer P105 Empty Level P986 Tel No 2 P996 SMS Start P106 Span P987 Tel No 3 P997 SMS Stop P107 Near Blankin P98...

Страница 37: ...212 R1 ID P222 R2 ID R213 R1 Set 1 R223 R2 Set 1 R214 R1 Set 2 R224 R2 Set 2 P217 R1 Closures P227 R2 Closures P218 R1 Fail Safe P228 R2 Fail Safe Data Logs Menu Temperature P580 Min temp P581 Min Temp Date P582 Min Temp Time P583 Maximum Temp P584 Max Temp Date P855 Max Temp Time P856 Current Temp ...

Страница 38: ... Menu Range Operation Setpoint Limits Trim Failsafe P830 Output Range P831 Output Mode P834 Low Value P836 Low Limit P838 Low Output Trim P840 Fail Mode P835 High Value P837 High Limit P839 High Output Trim Compensation Menu Offset Temperature P851 Measu Offset P852 Temp Source P854 Fixed Temp ...

Страница 39: ...lters P870 Fill Damping P881 Fixed Dist P871 Empty Damping P882 Process Filter Echo Processing Menu Xdr Status P900 Xdr Status P901 Echo Confid P902 Echo Strength P903 Average Noise P904 Peak Noise P905 Sensitivity P906 Side Clearance ...

Страница 40: ...tware Rev P931 Date P970 DST Enable P922 Passcode P927 Hardware Rev P932 Time P971 DST Differen P928 Serial No P933 Date Format P972 DST Start Time P929 Site Ident P973 Start Day P930 Factory Def P974 Start Week P975 Start Month P976 DST End Time P977 End Day P978 End Week P979 End Month ...

Страница 41: ...Page 35 Test Menu Simulation Hardware P980 Simulate P992 Out Test P981 Increment P933 Relay Test P982 Rate P994 Transd Test ...

Страница 42: ...et to one of the following Option Description 1 Distance Default Display and Output relative to the distance from the transducer to the surface 2 Level Display and Output relative to how full the vessel is 3 Space Display and Output relative to how empty a vessel is P101 Transducer This parameter should be set to the transducer being used with the unit and can be set to one of the following Option...

Страница 43: ...should be set before span Important Information When changing the Empty Distance P105 you can also recalculate the values for the Span so that it equals the empty distance P105 minus Near Blanking P107 and the Relay Setpoints so that they remain at the same percentage values of the empty distance as they were before you changed the empty distance P105 You will be asked the question Recalculate Spa...

Страница 44: ...a dB10 Default Blanking Distance 0 3m P101 4 Xducer is a dB15 Default Blanking Distance 0 5m P101 5 Xducer is a dB25 Default Blanking Distance 0 6m P101 6 Xducer is a dB40 Default Blanking Distance 1 2m P101 7 Xducer is a dBS6 Default Blanking Distance 0 2m P108 Far Blanking Distance This is the distance as a percentage of empty level P105 beyond the empty point that the unit will be able to measu...

Страница 45: ... 0 present at the beginning of the telephone number to be dialled 2 Add 00 2 0 s present at the beginning of the telephone number to be dialled P986 Tel No2 This parameter is used to enter to enter the next 6 digits following the 0 s of the telephone number to be dialled If there are less then 8 digits following the 0 s then just enter the digits required if there are more than digits following th...

Страница 46: ...iated SMS Time The following parameters determine when and how often a SMS message is to be sent P995 SMS Interval This parameter determines how often a SMS message will be sent If the time interval is set at 0 00 mins then a SMS message will only be sent when an alarm condition occurs when the time interval is set to anything other that zero then a SMS message will be sent at the relevant interva...

Страница 47: ...is active and is entered as a Boolean value equating to the total of the days that the SMS message is required to be active Mon Tue Wed Thu Fri Sat Sun 1 2 4 8 16 32 64 Add together any combination up to a maximum of 127 every day Examples 21 Mon Wed Fri 31 Mon to Fri 10 Tue and Thu ...

Страница 48: ...ected individually and results in the following parameter numbers for each relay Relay 1 210 to 218 Relay 2 220 to 228 Relay Type P210 P220 Relay Type This parameter defines what type each relay should be see the table below or available options Option Description 0 Not In Use Default Relay not in use or programmed 1 Alarm Relay is programmed as an alarm relay which will de energise ON and energis...

Страница 49: ...s are entered in Display Units or of span as referenced to Empty Level 2 Temperature Alarm is based on the temperature and the type of temperature alarm P212 222 and two setpoints must be set P213 223 P214 224 The temperature used depends on the temperature source selected P852 Setpoints are entered in o C 3 Loss of Echo Alarm is raised if the Failsafe Timer P809 expires No setpoints are required ...

Страница 50: ...es the OFF setpoint P213 223 is ON Setpoint P214 224 is OFF Setpoint 2 High Relay goes ON when the value rises to the ON setpoint and goes OFF when the value lowers to the OFF setpoint ON OFF Relay Setpoints P213 223 and P214 224 Setpoints can be set in any order as the unit knows that you are setting a high level alarm 3 Hi Hi Same as 2 High but different identifier 4 Low Relay goes ON when the v...

Страница 51: ...are setting an out of bounds alarm The fourth parameter and the fifth parameter for each relay set the Alarm ON and OFF points For a high alarm the ON is set higher than OFF For low alarm then ON is set lower than OFF See the appropriate alarm ID table P212 222 for further information When P211 P221 3 Loss of Echo or 4 Loss of Clock This parameter has no function and will not be displayed When P21...

Страница 52: ...P221 Relay Function This function is used where it is required to energise the relay to switch a device such as a pump ON and de energise the relay to switch the device OFF Options Description 0 Off Relay is always de energised 1 General Relay will energise ON as set in Relay Setpoint 1 P213 223 And turns OFF de energises as set in Relay Setpoint 2 P214 224 Important Information A control relay is...

Страница 53: ...F P214 224 3 Alternate All control devices are used to assist each other run at the same time With each device having its own setpoints ON P213 223 OFF P214 224 but each time all devices have stopped then the setpoints are sequentially rotated between the devices to ensure equal usage The fourth parameter and fifth parameter are set to determine the switch points ON and OFF for the relay See contr...

Страница 54: ...ed this parameter displays the number of times the relay has activated since the relay has been in use It can be reset with any value P218 P228 Relay Fail Safe Your blackbox has a general fail safe parameter P808 However this can be overridden so that each individual relay has its own independent fail safe mode This parameter determines what the relay will do in the event of the Fail safe Time P80...

Страница 55: ...displays the minimum temperature recorded P581 Minimum Temperature Date This parameter displays the date when the minimum temperature was recorded P582 Minimum Temperature Time This parameter displays the time when the minimum temperature was recorded P583 Maximum Temperature This parameter displays the maximum temperature recorded P584 Maximum Temperature Date This parameter displays the date whe...

Страница 56: ...n or low empty as follows Option Description 1 Known Default Remain at the last known value 2 High Will fail to the high value 100 of Span 3 Low Will fail to the low value empty See Also P840 Output Fail safe Important Information In the event of a fail safe condition occurring the display when connected to the PC Handheld Communicator or the optional Handheld Communicator and Output can be config...

Страница 57: ...he output mode P831 so if the reading is 0 then the voltage output is 5 VDC If the reading is 100 then the voltage output is 0 VDC 2 0 to 5 VDC Default Voltage output directly proportional to the output mode P831 so if the reading is 0 then the voltage output is 0 VDC If the reading is 100 then the voltage output is 5 VDC Operation P831 Output Mode This parameter determines how the Output relates ...

Страница 58: ...igh voltage output will occur 5 VDC Default 5 700m Limits P836 Output Low Limit This parameter sets the lowest level that the voltage output will drop to the default is 0 VDC but you can override this if required P837 Output High Limit This parameter sets the highest level that the voltage output will rise to the default is 5 VDC but you can override this if required Trim P838 Output Low Trim If t...

Страница 59: ... safe P808 but this can be overridden to force the mA output to an independent fail safe mode as follows Option Description 0 Default output will fail as per P808 1 Hold output will retain its last known value 2 Low output will fail to its low condition 3 High output will fail to its high condition 5 VDC maximum 4 Very high output will fail to its highest or fault condition of greater than 5 VDC ...

Страница 60: ...ource This parameter determines the source of the temperature measurement By default it is set to automatic P852 1 which will automatically detect if a temperature sensor is available from the transducer If for any reason no temperature input is received then the Fixed Temp value is used as set by P854 The temperature source can be specifically set as follows Option Description 1 Automatic Default...

Страница 61: ...imum vessel empty rate Default 10 000 metres minute Filters The following two parameters can be used to filter out unwanted changes of level caused by a rippled or agitated surface P881Fixed Distance This parameter determines the width of gate to be used in tracking an echo and under normal circumstances will not require changing but it can be increased in the cases where the surface is moving ext...

Страница 62: ...ence from the transducer It is useful to help find the best mounting location for the transducer where you should aim to get the highest figure It is a percentage of confidence that the echo reporting the level is the correct one P902 Echo Strength This parameter shows the most recent echo strength figure for the transducer where a higher figure indicates a better returned echo P903 Average Noise ...

Страница 63: ...show the current software revision P927 Hardware Revision This parameter will show details of the current hardware revision P928 Serial Number This parameter will show the serial number of the unit P929 Site Identification This parameter allows you to give each unit an individual reference number for identification purposes You can set any number between 1 and 99999 P930 Factory Defaults This para...

Страница 64: ...mation In order to ensure the correct operation of Daylight Saving Time P932 Time should be checked and adjusted if necessary to ensure that it is set for the current valid time P970 DST Enable When Enabled set to 1 the internal clock will be automatically adjusted to compensate for the difference between standard time and Daylight Saving Time Default 0 Off P971 DST Difference This parameter sets ...

Страница 65: ... Sunday Default DST will start on a Sunday P974 Start Week This parameter will determine the week of the month P975 in which Daylight Saving Time is to start Option Description 1 Week 1 DST will start on day P973 in the first week P974 of the month P975 2 Week 2 DST will start on day P973 in the second week P974 of the month P975 3 Week 3 DST will start on day P973 in the third week P974 of the mo...

Страница 66: ...tart during the month of September 10 October DST will start during the month of October 11 November DST will start during the month of November 12 December DST will start during the month of December P976 DST End Time This parameter is used to set the time of day at which Daylight Saving Time will end the time is entered in the format HH MM 24 hour format Default 02 00 P977 End Day Use this param...

Страница 67: ...9 P979 End Month This parameter is used to select the month in which Daylight Saving Time will end Option Description 1 January DST will end during the month of January 2 February DST will end during the month of February 3 March DST will end during the month of March 4 April DST will end during the month of April 5 May DST will end during the month of May 6 June DST will end during the month of J...

Страница 68: ...responding LED at the switchpoints programmed if you wish to change the direction of the level movement at anytime this can be done by using the arrow keys In manual simulation using the arrow keys will allow you to move the level up and down as required The choices for you to enter are as follows 1 Manual soft simulation 2 Automatic soft simulation 3 Manual hard simulation 4 Automatic hard simula...

Страница 69: ...the output P993 Relay Test Press a numeric key corresponding to the number of the relay you wish to test and the relay will change state each time the key is pressed If you press any other key other than a valid relay number then the test will end P994 Transducer Test Press any key on the keypad other than 0 and the transducer will continually fire for 5 seconds pressing 0 will terminate the test ...

Страница 70: ...surface of material Enter Program Mode and directly access P21 Set Distance type in the measured distance press ENTER when prompted press ENTER again wait until SET displayed Return to Run Mode display should now update to correct reading Material level is consistently incorrect by the same amount Check empty level P105 display offset P802 and measurement offset P851 LED s change colour at relevan...

Страница 71: ...ment Units 1 metres P105 Empty Level 6 000 metres P106 Span 5 700 metres P107 Near Blanking 0 300 metres P108 Far Blanking 20 0 Remote Alarm Parameter Details Entered Values No Description Default 1 2 3 4 5 P985 Tel No 1 1 Add 0 P986 Tel No 2 0 P987 Tel No 2 0 P988 Call Type 0 Off SMS Time Parameter Details Entered Values No Description Default 1 2 3 4 5 P995 Interval 0 00 mins P996 SMS Start 00 0...

Страница 72: ...ult 1 2 3 4 5 P220 R2 Type 0 Off P221 R2 Function 0 Off P222 R2 Alarm ID Pump Group 1 Off P223 R2 Set 1 0 000 metres P224 R2 Set 2 0 000 metres P227 R2 Closures 0 P228 R2 Fail Safe 0 DATA LOGS Temperature Parameter Details Entered Values No Description Default 1 2 3 4 5 P580 Minimum Temperature Read Only P581 Min Temperature Date Read Only P582 Min Temperature Time Read Only P583 Maximum Temperatu...

Страница 73: ...rameter Details Entered Values No Description Default 1 2 3 4 5 P830 Output Range 2 0 5VDC Operation Parameter Details Entered Values No Description Default 1 2 3 4 5 P831 Output Mode 0 Default Set Point Parameter Details Entered Values No Description Default 1 2 3 4 5 P834 Low Level 0 000 metres P835 High Level 6 000 metres Limits Parameter Details Entered Values No Description Default 1 2 3 4 5 ...

Страница 74: ...ription Default 1 2 3 4 5 P851 Measurement Offset 0 000 metres Temperature Parameter Details Entered Values No Description Default 1 2 3 4 5 P852 Temperature Source 1 Automatic P854 Fixed Temperature 20 00 Deg C STABILITY Damping Parameter Details Entered Values No Description Default 1 2 3 4 5 P870 Fill Damping 10 000 m min P871 Empty Damping 10 000 m min Filters Parameter Details Entered Values ...

Страница 75: ...de Parameter Details Entered Values No Description Default 1 2 3 4 5 P921 Enable Code 1 Yes P922 Passcode 1997 System Information Parameter Details Entered Values No Description Default 1 2 3 4 5 P926 Software Revision Read Only P927 Hardware Revision Read Only P928 Serial Number Read Only P929 Site Ident 1 Date Time Parameter Details Entered Values No Description Default 1 2 3 4 5 P931 Date Curre...

Страница 76: ...Entered Values No Description Default 1 2 3 4 5 P970 DST Enable 0 P971 DST Differen 01 00 P972 DST Start Time 02 00 P973 Start Day 8 P974 Start Week 1 P975 Start Month 3 P976 DST End Time 02 00 P977 End Day 8 P978 End Week 5 P979 End Month 10 ...

Отзывы: