Features: 

 

 

13,8VDC/8A uninterrupted supply 

 

wide range of supply voltage 88÷264VAC  

 

high efficiency 80% 

     battery charge and maintenance control 

     deep discharge battery protection (UVP) 

 

battery charging current 0,5A 

     battery output protection against short circuit 

and reverse polarity connection 

     LED indication 

     FAC technical output indicating AC power loss  

       – OC and relay type 

 

 

FPS technical output indicating PSU failure 

      – OC and relay type 

 

FLB technical output indicating battery low 
voltage  

      – OC and relay type 

 

protections: 

 

SCP short-circuit protection 

 

OVP over voltage protection 

 

surge protection  

 

OLP overload protection 

 

warranty – 5 year from the production date 

 

 

 
CONTENTS: 
1. Technical description. 

1.1 General description 
1.2 Block diagram 
1.3 Description of PSU components and connectors 
1.4 Specifications 

2. Installation. 

2.1 Requirements 
2.2 Installation procedure 

3. Operating status indication. 

3.1 LED indication of operating status 
3.2 Technical outputs

 

4. Operation and use. 

4.1 Overload or short circuit of the PSU output  
4.2. Battery-assisted operation 

 

4.3. Maintenance 

 
1. Technical description. 
 

1.1 General description 

A buffer PSU is intended for an uninterrupted supply to devices requiring stabilized voltage of 

12 V DC 

 (+/-15%).

  The  PSU  provides voltage  of 

13,8V  DC 

with  current  capacity

  I=8A  +  0,5A  battery  charge

.  In  case  of 

power decay, a battery back-up is activated immediately.  

 

 

 

 

During normal operation, the total current drawn by the receivers may not exceed I=8A. 
Maximum battery charging current: 0,5 A. Total device c battery: 8,5 A max. 

 

 

 

 

 

 

 

 

 

Содержание ADOC1551280

Страница 1: ...ADOC1551280 v 1 0 ADOC 13 8V 8A OC Enclosed buffer switch mode power supply unit with automatic operation control EN Edition 1 from 07 10 2013 Supercedes edition ...

Страница 2: ... CONTENTS 1 Technical description 1 1 General description 1 2 Block diagram 1 3 Description of PSU components and connectors 1 4 Specifications 2 Installation 2 1 Requirements 2 2 Installation procedure 3 Operating status indication 3 1 LED indication of operating status 3 2 Technical outputs 4 Operation and use 4 1 Overload or short circuit of the PSU output 4 2 Battery assisted operation 4 3 Mai...

Страница 3: ... voltage 4 FAC AC absence technical output relay type 5 FPS output indicating DC absence PSU failure relay type 6 FLB output indicating battery low voltage relay type 7 FAC AC absence technical output OC type 8 FPS output indicating DC absence PSU failure OC type 9 FLB output indicating battery low voltage OC type 10 B B battery connector 11 V COM DC supply output 12 L N 230V AC power connector PE...

Страница 4: ...rt circuit protection SCP electronic automatic recovery Overload protection OLP 105 150 of power supply automatic recovery Battery circuit protection SCP and reverse polarity connection fuse Surge protection varistors Over voltage protection OVP 15 87 18 63V automatic recovery Deep discharge protection UVP U 9 5V 5 disconnection of the battery terminal Technical outputs FAC output indicating AC po...

Страница 5: ...ºC 60ºC Storage temperature 20ºC 85ºC Relative humidity 20 90 without condensation Vibrations during operation unacceptable Impulse waves during operation unacceptable Direct insolation unacceptable Vibrations and impulse waves during transport PN 83 T 42106 2 Installation 2 1 Requirements The buffer PSU is to be mounted by a qualified installer holding relevant permits and licenses applicable and...

Страница 6: ...PTABLE It can cause a device failure or an electric shock 4 Connect load loads to proper output connectors of the power supply positive pole is marked as V negative pole as COM 5 Connect the technical outputs to the central or other device 6 Connect the battery to proper output connectors of the power supply positive pole is marked as B negative pole as B 7 Once the tests and operation control hav...

Страница 7: ...at the output e g short circuit the output is switched into high impedance state hi Z relay output In case of a failure the contacts of the relay change over CAUTION In the Fig 2 the set of contacts shows a potential free status of the relay which corresponds to a state with no DC power PSU failure FLB technical output indicating battery voltage OC type output Under normal status UBAT 11 5V the ou...

Страница 8: ...vide warranty repairs at the earliest convenienve however not later that within 14 days from the delivery to the service centre of the manufacturer 6 The repair period mentioned in item 5 may be prolonged if there are no technical possibilities to carry out the repairs or if the equipment has been conditionally accepted due to the breaking warranty terms by the claimant 7 All the services rendered...

Отзывы: