UZK24.262/-E1, UZO24.262/-E1 Installation Manual 

 

 

 

 

Product Description 

The UZK24.262 battery module utilizes 2 non-spillable maintenance-free VRLA lead-acid batteries. 
The battery module includes the connector module UZW24.100 which provides an auto-resettable 
fuse, temperature sensor and terminals for paralleling of a battery extension module. 
The auto-resettable fuse is suitable for balancer currents up to 2.5A. It protects the center-tap wire 
between the battery module and the DC-UPS control unit. 
The use of the sensor board enables to monitor and charge the two batteries individually and 
precisely, which extends the service life of the batteries and makes the use of matched replacement 
batteries unnecessary. The use of the sensor board signal connections is optional, the DC-UPS will 
also function without the sensor board installed. 
The UZK24.262 is compatible with most of the PULS DC-UPS control units and enables all the 
benefits of the PULS 1-Battery-Concept. It can be ordered as UZK24.262 (including batteries) or as 
UZO24.262 (comes without batteries; to be procured by customers).  
For increase of battery capacity, UZK24.262-E1 (with batteries) and UZO24.262-E1 (comes without 
batteries) are the perfect match. 
 

Intended Use

 

This device is designed for installation in an enclosure and is intended for commercial use, such as in 
industrial control, process control, monitoring and measurement equipment or the like. Do not use this 
device in equipment where malfunction may cause severe personal injury or threaten human life. 
 

Installation Instructions 

This device does not contain serviceable parts, except the fuse or replacement battery. If malfunction 
should occur during installation or operation, first check the fuse and battery for proper functionality. If 
the unit is damaged or if the malfunction continues, immediately turn power off and send device to the 
factory for inspection. 
Do not install the battery fuse until the installation work is complete. 
Replacement fuses must be of the same type or an UL listed fuse with the same nominal value and 
characteristics. 
Do not store batteries or battery modules at temperatures higher than 25°C or performance and 
lifetime may change. 
Before initial use, check the last charging which is marked on the battery. If it is older than 9 month, 
replace the battery. 
Do not store batteries longer than 9 months without charging or performance and lifetime may change. 
Every 9 months or whenever the open circuit voltage (OCV) falls below 25.2V, the battery module 
should be charged. Apply a charging voltage of 27.6V (at 

25°C) for 72 hours. Batteries with an OCV 

below 24V should be disposed. 
Do not short-circuit the battery poles or power wires and always check correct battery polarity. 
Mount the device onto a flat surface. Do not install the battery module upside down. 
Install the device in a cool area inside an enclosure providing protection against electrical, mechanical 
and fire hazards. Ensure sufficient ventilation by following the requirements of the EN 50272-2. 
The device is designed for pollution degree 2 areas in controlled environments.

 

No condensation or 

frost allowed. 
The enclosure of the device provides a degree of protection of IP00. 
Do not use batteries other than the original batteries supplied by the manufacturer to avoid conflicts 
with agency approvals. 
The maximum surrounding air temperature is +5

0°C (+122°F). The operational temperature is the 

same as the ambient or surrounding air temperature and is defined 2cm below the device. Charging is 
allowed up to +5

0°C. 

Frequ

ently charging below +5°C reduces the lifetime of the battery. 

The device is designed to operate in areas between 5% and 95% relative humidity. 
Do not use wires smaller than 6mm

2

 (AWG 10) or longer than 2m (7ft) to avoid voltage drops on the 

connection between the battery module and the DC-UPS. 
Connect the sensor board signals to the DC-UPS by using control wires with a minimum wire size of 
0.5mm

2

 (AWG 20) and the center tap with a minimum wire size of 1mm

(AWG 17). 

Instructions for replacement and disposal of batteries: 

Batteries need to be replaced periodically. The time interval depends on the ambient temperature in 
which the battery is used and on the number and depth of discharge cycles. In a typical application it 
is recommended to replace the batteries at least every 2 years. Disconnect battery fuse before 
replacing the batteries. 
Always dispose batteries through a recycling organization. Optionally, batteries can be returned to the 
supplier or the battery manufacturer. Batteries must be completely discharged before recycling. 
CAUTION: The unit contains wet cell batteries. Ventilation of the installation room in accordance with 
the rules of Canadian Electrical Code, part 1 is required if used in Canada. 

Instructions for replacing and installing batteries: 
ATTENTION! Disconnect battery fuse before replacing the battery 

1) 

Loosen screw of battery holder with only one turn. 

2) 

Remove Insulating caps from the battery terminals. 

3) 

Unscrew the battery terminals. 

4) 

Slide the mounting bracket sideways and take the mounting bracket off. 

5) 

Remove the battery (if applicable). 

6) 

Insert the new battery. 

7) 

Fix it again with the mounting bracket and make sure that the lock washer lies between the 

screw head and mounting bracket. 

8) 

Screw the mounting bracket with tightening torque: 2Nm (18 lb.inch). 

9) 

Do not over-tighten screws of the terminal bolts of the battery. Recommended tightening 

torque: 2,5Nm (22 lb.inch). 

10)  Insert battery fuse. 

 

 

Technical Data

 

All values are typical figures unless otherwise noted. 

Voltage 

DC 24V 

 

Nominal battery capacity 

26Ah 

 

Battery current 

Max. 50A 

Discharge current 

 

Max. 7.5A 

Charging current 

 

Max. 2.5A 

Balancer current 

Recommended charging 
voltage 

27.8V 
27.5V 
27.15V 
26.8V 

At +

10°C 

At +

20°C 

At +3

0°C 

At +

40°C 

Self-discharge rate 

3% / month 

At +20°C 

Battery fuse 

2*40A 

ATOF

®

 287 040 from 

Littelfuse. 

Temperature sensor 

PT1000 

 

Temperature range 

-

10°C to +50°C  

For charging 

 

-

15°C to +50°C 

For discharging 

Storage temperature range 

-

20°C to +50°C 

 

Max. wire size (litz wire) 

10mm

² 

For power terminals 

Wire size AWG 

AWG 22-8 

For power terminals 

Maximum wire diameter 

5.2mm 

For power terminals 

Wire stripping length 

12mm / 0.5inch 

For power terminals 

Tightening torque 

2.3Nm / 20lb.inch  For power terminals 

Max. wire size (litz wire) 

1.5mm² 

Sensor board terminals 

Wire size AWG 

AWG 26-14 

Sensor board terminals 

Maximum wire diameter 

1.5mm 

Sensor board terminals 

Wire stripping length 

5mm / 0.25inch 

Sensor board terminals 

Tightening torque 

0.45Nm / 4lb.inch  Sensor board terminals 

Cable length 

0.2m 
1m 

UZK(O)24.262  
UZK(O)24.262

–E1  

Size 

(wxhxd)

 

359x214x167mm  UZK24.262 incl. 

UZW24.100 

 

359x214x128mm  UZK24.262

–E1 

Weight 

per module

 

10kg / 22lb 

UZK24.262/-E1 

 

0.7kg / 1.54lb 

UZO24.262/-E1 

 
 
 

 

 

Mechanical Dimensions 

 

All dimensions in mm 

Hole Pattern for Wall Mounting 

 

 

All dimensions in mm 