PIC480.241C, PIC480.241C-C1
PIANO-Series
24V,
20A,
480W,
S
INGLE
P
HASE
I
NPUT
Mar. 2021 / Rev. 1.2 DS-PIC480.241C-EN
All parameters are typical values specified at 24V, 20A output, 230Vac input , 25°C ambient and after a 5 minutes run-in time
unless otherwise noted.
www.pulspower.com Phone +49 89 9278 0 Germany
3/19
1.
I
NTENDED
U
SE
This device is designed for installation in an enclosure and is intended for commercial use, such as in industrial control,
process control, monitoring, measurement, Audio/Video, information or communication equipment or the like. Do not use
this device in equipment where malfunction may cause severe personal injury or threaten human life.
If this device is used in a manner outside of its specification, the protection provided by the device may be impaired.
Without additional measures to reduce the conducted emissions on the output (e.g. by using a filter), the device is not suited
to supply a local DC power network in industrial, residential, commercial and light-industrial environments
2.
I
NSTALLATION
I
NSTRUCTIONS
WARNING
Risk of electrical shock, fire, personal injury or death
.
- Turn power off before working on the device and protect against inadvertent re-powering.
- Do not open, modify or repair the device.
- Use caution to prevent any foreign objects from entering into the housing.
- Do not use in wet locations or in areas where moisture or condensation can be expected.
- Do not touch during power-on, and immediately after power-off. Hot surface may cause burns.
Obey the following installation instructions:
This device may only be installed and put into operation by qualified personnel.
This device does not contain serviceable parts. The tripping of an internal fuse is caused by an internal defect.
If damage or malfunction should occur during installation or operation, immediately turn power off and send unit to the
factory for inspection.
Install device in an enclosure providing protection against electrical, mechanical and fire hazards.
Install the device onto a DIN-rail according to EN 60715 with the input terminals on the bottom of the device.
Make sure that the wiring is correct by following all local and national codes. Use appropriate copper cables that are
designed for a minimum operating temperature of 60°C for ambient temperatures up to +45°C, 75°C for ambient
temperatures up to +55°C and 90°C for ambient temperatures up to +70°C. Ensure that all strands of a stranded wire enter
the terminal connection. Unused screw terminals should be securely tightened.
The device is designed for pollution degree 2 areas in controlled environments. No condensation or frost is allowed.
The enclosure of the device provides a degree of protection of IP20. The enclosure does not provide protection against spilled
liquids.
The isolation of the device is designed to withstand impulse voltages of overvoltage category III according to IEC 60664-1.
The device is designed as “Class of Protection” I equipment according to IEC 61140. Do not use without a proper PE
(Protective Earth) connection.
The device is suitable to be supplied from TN, TT or IT mains networks. The continuous voltage between the input terminals
and the PE potential must not exceed 300Vac.
A disconnecting means shall be provided for the input of the device.
The device is designed for convection cooling and does not require an external fan. Do not obstruct airflow and do not cover
ventilation grid!
The device is designed for altitudes up to 5000m (16400ft). Above 2000m (6560ft) the overvoltage category is reduced to level
II and a reduction in output current is required.
Keep the following minimum installation clearances: 40mm on top, 20mm on the bottom, 5mm left and right side. Increase
the 5mm to 15mm in case the adjacent device is a heat source. When the device is permanently loaded with less than 50%,
the 5mm can be reduced to zero.
The device is designed, tested and approved for branch circuits up to 20A without additional protection device. For higher
branch circuits use an additional protection device. If an external input protection device is utilized, do not use one smaller
than a 10A B- or 6A C-characteristic to avoid a nuisance tripping of the circuit breaker.
The maximum surrounding air temperature is +70°C (+158°F). The operational temperature is the same as the ambient or
surrounding air temperature and is defined 2cm below the device.
The device is designed to operate in areas between 5% and 95% relative humidity.