PIC480.241C, PIC480.241C-C1 

 

 

 

 PIANO-Series

 

 

24V,

 

20A,

 

480W,

 

S

INGLE 

P

HASE 

I

NPUT

 

 

 

Mar. 2021 / Rev. 1.2 DS-PIC480.241C-EN 
All parameters are typical values specified at 24V, 20A output, 230Vac input , 25°C ambient and after a 5 minutes run-in time 

unless otherwise noted. 

www.pulspower.com   Phone +49 89 9278 0    Germany 

2/19 

 

I

NDEX

 

 
 

Page 

Page 

1.

 

Intended Use ....................................................... 3

 

2.

 

Installation Instructions ...................................... 3

 

3.

 

AC-Input............................................................... 4

 

4.

 

DC-Input............................................................... 5

 

5.

 

Input Inrush Current ........................................... 5

 

6.

 

Output ................................................................. 6

 

7.

 

Hold-up Time ....................................................... 7

 

8.

 

DC-OK Relay Contact .......................................... 7

 

9.

 

Efficiency and Power Losses ................................ 8

 

10.

 

Lifetime Expectancy and MTBF ........................... 8

 

11.

 

Functional Diagram ............................................. 9

 

12.

 

Terminals and Wiring .......................................... 9

 

13.

 

Front Side and User Elements ........................... 10

 

14.

 

EMC .................................................................... 11

 

15.

 

Environment ...................................................... 12

 

16.

 

Safety and Protection Features ........................ 13

 

17.

 

Dielectric Strength ............................................ 14

 

18.

 

Approvals and Fulfilled Standards ................... 15

 

19.

 

Regulatory Compliance .................................... 15

 

20.

 

Physical Dimensions and Weight ..................... 16

 

21.

 

Accessory ........................................................... 17

 

21.1.

 

YR40.242 Redundancy Module ................ 17

 

21.2.

 

PIRD20.241 Redundancy Module ............. 17

 

22.

 

Application Notes ............................................. 18

 

22.1.

 

Back-feeding Loads .................................. 18

 

22.2.

 

External Input Protection ......................... 18

 

22.3.

 

Parallel Use to Increase Output Power .... 18

 

22.4.

 

Parallel Use for 1+1 Redundancy ............. 18

 

22.5.

 

Series Operation ....................................... 19

 

22.6.

 

Inductive and Capacitive Loads................ 19

 

22.7.

 

Charging of Batteries ............................... 19

 

22.8.

 

Operation on Two Phases ........................ 19

 

22.9.

 

Use in a Tightly Sealed Enclosure ............ 19

 

 

 
The information given in this document is correct to the best of our knowledge and experience at the time of 
publication. If not expressly agreed otherwise, this information does not represent a warranty in the legal sense of the 
word. As the state of our knowledge and experience is constantly changing, the information in this data sheet is 
subject to revision. We therefore kindly ask you to always use the latest issue of this document (available under 

www.pulspower.com). No part of this document may be reproduced or utilized in any form without our prior 
permission in writing. 
 
 

T

ERMINOLOGY AND 

A

BREVIATIONS

 

PE and 

 symbol

 

PE is the abbreviation for 

P

rotective 

E

arth and has the same meaning as the symbol 

Earth, Ground 

This document uses the term “earth” which is the same as the U.S. term “ground”. 

T.b.d.

 

To be defined, value or description will follow later. 

AC 230V 

A figure displayed with the AC or DC before the value represents a nominal voltage with 
standard tolerances (usually ±15%) included.  
E.g.: DC 12V describes a 12V battery disregarding whether it is full (13.7V) or flat (10V) 

230Vac 

A figure with the unit (Vac) at the end is a momentary figure without any additional 
tolerances included.  

50Hz vs. 60Hz

 

As long as not otherwise stated, AC 230V parameters are valid at 50Hz mains frequency. 

may

 

A key word indicating flexibility of choice with no implied preference. 

shall

 

A key word indicating a mandatory requirement. 

should

 

A key word indicating flexibility of choice with a strongly preferred implementation. 

 

Содержание PIANO Series

Страница 1: ...tiple mains inputs the reduction to a regional input voltage range AC 200 240V simplifies the circuitry and has significant advantages for reliability efficiency and cost The addition of a DC OK signa...

Страница 2: ...is document is correct to the best of our knowledge and experience at the time of publication If not expressly agreed otherwise this information does not represent a warranty in the legal sense of the...

Страница 3: ...t by following all local and national codes Use appropriate copper cables that are designed for a minimum operating temperature of 60 C for ambient temperatures up to 45 C 75 C for ambient temperature...

Страница 4: ...99 at 24V 20A 230Vac see Fig 3 4 Crest factor typ 1 6 at 24V 20A 230Vac Start up delay typ 400ms see Fig 3 2 Rise time typ 60ms at 24V 20A const current load 0mF load capacitance see Fig 3 2 typ 240m...

Страница 5: ...INPUT INRUSH CURRENT A NTC inrush limiter which is bypassed by a relay contact during normal operation limits the input inrush current after turn on of the input voltage Inrush current max 32Apeak 40...

Страница 6: ...tage 13 5Vdc see Fig 6 1 Short circuit current min 21A load impedance 50mOhm see Fig 6 1 max 25A load impedance 50mOhm see Fig 6 1 typ 8 1A average R M S current load impedance 50mOhm see Fig 6 1 Outp...

Страница 7: ...90 230Vac Input Voltage 50 60 Hold up Time 70 a b c d a 24V 10A typ b 24V 10A min c 24V 20A typ d 24V 20A min 5 Hold up Time Zero Transition Output Voltage Input Voltage 8 DC OK RELAY CONTACT This fea...

Страница 8: ...and 25 C 230Vac MTBF SN 29500 IEC 61709 482 000h at 24V 20A and 40 C 230Vac 894 000h at 24V 20A and 25 C 230Vac MTBF MIL HDBK 217F 207 000h at 24V 20A and 40 C 230Vac Ground Benign GB40 279 000h at 24...

Страница 9: ...ructed and suitable for field and factory wiring Input and output DC OK Signal Type Screw terminals Push in terminals Solid wire max 6mm2 max 1 5mm2 Stranded wire max 4mm2 max 1 5mm2 American Wire Gau...

Страница 10: ...wer com Phone 49 89 9278 0 Germany 10 19 13 FRONT SIDE AND USER ELEMENTS Fig 13 1 Front side A Input Terminals screw terminals N L Line input PE Protective Earth input B Output Terminals screw termina...

Страница 11: ...200Vac 140Vac 50 of 200Vac 100Vac 1000ms 500ms 200ms Criterion A Criterion C Criterion C Powerful transients VDE 0160 over entire load range 750V 0 3ms Criterion A Criterions A Power supply shows norm...

Страница 12: ...to 6000m 6 560 to 20 000ft reduce output power or ambient temperature see Fig 15 2 IEC 62103 EN 50178 overvoltage category II Altitude de rating 30W 1000m or 5 C 1000m 2000m 6500ft see Fig 15 2 Over...

Страница 13: ...s down and automatically attempts to restart Class of protection I According to IEC 61140 A PE Protective Earth connection is required Ingress protection IP 20 According to EN IEC 60529 Over temperatu...

Страница 14: ...ucting the test When testing set the cut off current settings to the value in the table below Fig 17 1 Dielectric strength A B C D A D C B B N L Input DC ok Earth PE Output Type test 60s 2500Vac 3000V...

Страница 15: ...eclaration Online Document Airborne Contaminants Corrosion Test Severity Level G3 Harsh H2S 100ppb NOx 1250ppb Cl2 20ppb SO2 300ppb Test Duration 3 weeks which simulates a service life of at least 10...

Страница 16: ...ICAL DIMENSIONS AND WEIGHT Width 49mm 1 93 Height 124mm 4 88 Depth 124mm 4 88 The DIN rail height must be added to the unit depth to calculate the total required installation depth Weight 620g 1 37lb...

Страница 17: ...dancy module which can be used to build 1 1 and N 1 redundant systems It is equipped with two input channels which can be connected to power supplies with up to 10A output current and one output which...

Страница 18: ...breaker should be used 22 3 PARALLEL USE TO INCREASE OUTPUT POWER Do not use the power supply in parallel to increase the output power 22 4 PARALLEL USE FOR 1 1 REDUNDANCY Power supplies can be parall...

Страница 19: ...ng capacitive and inductive loads If extreme large capacitors such as EDLCs electric double layer capacitors or UltraCaps with a capacitance larger than 1 5F are connected to the output the unit might...