MLY10.241 Installation Manual 

 

 

 

Product Description 

The MLY10.241 is a redundancy module for building redundant power supply systems. It is 
equipped with two input channels and one output. The two inputs are decoupled by diodes. 

Intended Use 

This device is designed for installation in an enclosure and is intended for commercial use, such as 
in industrial control, process control, monitoring and measurement equipment or the like. Do not use 
this device in equipment where malfunction may cause severe personal injury or threaten human 
life.  
The redundancy module can be used with any type of power supply as long as the maximum output 
current ratings are not exceeded. It is suitable for power supplies with continuous overload current 
as well as any kind of intermittent (Hiccup) overload behavior. 
If this device is used in a manner outside of its specification, the protection provided by the device 
may be impaired. 

Installation Instructions 

Install the device in an enclosure providing protection against electrical, mechanical and fire 
hazards. 
Do not ground or earth the positive output pole which could prevent redundancy in case of a ground 
failure. Ground the negative output pole, when needed. 
Use only power supplies with a negligible output ripple voltage in the low frequency range between 
50Hz and 10kHz when used in marine applications according to the GL regulations. 
Install the device onto a DIN-rail according to EN 60715 with the input terminals on the top of the 
device. Other mounting orientations require a reduction in output current. 
Make sure that the wiring is correct by following all local and national codes. Use appropriate copper 
cables that are designed for a minimum operating temperature of 60°C for ambient temperatures up 
to +45°C, 75°C for ambient temperatures up to +60°C and 90°C for ambient temperatures up to 
+70°C. Ensure that all strands of a stranded wire enter the terminal connection. Unused screw 
terminals should be securely tightened. 
The device is designed for pollution degree 2 areas in controlled environments. No condensation or 
frost is allowed. 
The enclosure of the device provides a degree of protection of IP20. The enclosure does not provide 
protection against spilled liquids. 
The input must be powered from a PELV or SELV source or an “Isolated Secondary Circuit” in order 
to maintain a SELV or PELV output. 
Check correct input polarity. The device will not operate when input voltage is reversed. 
The device is designed as “Class of Protection III” equipment according to IEC 61140. 
The device is designed for convection cooling and does not require an external fan. Do not obstruct 
airflow and do not cover ventilation grid! 
The device is designed for altitudes up to 5000m (16400ft). Above 2000m (6560ft) a reduction in 
output current is required. 
Keep the following minimum installation clearances: 40mm on top, 20mm on the bottom, 5mm left 
and right side. Increase the 5mm to 15mm in case the adjacent device is a heat source. When the 
device is permanently loaded with less than 50%, the 5mm can be reduced to zero. 
The maximum surrounding air temperature is +70°C (+158°F). The operational temperature is the 
same as the ambient or surrounding air temperature and is defined 2cm below the device. 
The device is designed to operate in areas between 5% and 95% relative humidity. 

Installation Instructions for Hazardous Location Areas 

The device is suitable for use in Class I Division 2 Groups A, B, C, D locations and for use in Group 
II Category 3 (Zone 2) environments. 
Hazardous Location classification: ATEX: EPS 11 ATEX 1 312 X, II 3G EX ec IIC T4 Gc 
WARNING EXPLOSION HAZARDS! 
Substitution of components may impair suitability for this environment.  
Do not disconnect the device unless power has been switched off or the area is known to be non-
hazardous. 
A suitable enclosure must be provided for the end product which has a minimum protection of IP54 
and fulfils the requirements of the EN 60079-0. 

Functional Description 

The device can supply any kind of loads, including unlimited capacitive and inductive loads. 
Do not apply return voltages from the load to the output higher than 200Vdc. 

 

Technical Data

 

All values are typical figures specified at 24Vdc input voltage, 10A 
output current, 25°C ambient temperature and after a 5 minutes 
run-in time unless otherwise noted. 

Input voltage 

DC 12-48V 

±25% 

Input voltage range 

9–60Vdc  

Input current 

2x 5A 

Below +60°C ambient 

 

2x 3.75A 

At +70°C ambient 

 

2x 8A 

Up to 5 seconds 

 

Derate linearly b60°C and +70°C

Output current 

10A 

Below +60°C ambient 

 

7.5A 

At +70°C ambient 

 

16A 

Up to 5 seconds 

Maximum overload current  16A R.M.S. 

In any overload or 
short circuit condition 

Input to output voltage loss 800mV 

At 2x 2.5A input 

 

900mV 

At 2x 5A input 

Power losses 

0W 

At no load 

 

4.0W 

At 2x 2.5A input 

 

9.0W 

At 2x 5A input 

Temperature range 

-40 to +70°C 

 

Max. wire size (litz wire) 

4mm²  

Wire size AWG 

AWG 20-10 

 

Max. wire diameter 

2.8mm  

Wire stripping length 

7mm / 0.28inch 

 

Tightening torque 

1Nm / 9lb.inch 

 

Size (wxhxd) 

45x75x91mm Without 

DIN-rail 

Weight 

140g / 0.31lb 

 

 

Functional Diagram 

+

-

+

-

+

-

Input 1

Input 2

Output

-

 

 

Wiring Scheme - 1+1 Redundancy 

L1
L2

PE

L3

Load

Failure

Monitor

I

I

I

I

I

I

Power

Supply

Output

DC-
OK

L1 L2 L3

Input

+

-

+

-

o o

Redundancy

Module

Output

Input

 1

Input

2

+

-

+

-

+

-

-

Power

Supply

Output

DC-
OK

L1 L2 L3

Input

+

-

+

-

o o

 

 

Wiring Scheme - N+1 Redundancy 

L1
L2

PE

L3

Load

Failure

Monitor

I

I

I

I

I

I

I

I

I

I

I

I

Power

Supply

Output

DC-
OK

L1 L2 L3

Input

+

-

+

-

o o

Power

Supply

Output

DC-
OK

L1 L2 L3

Input

+

-

+

-

o o

Power

Supply

Output

DC-
OK

L1 L2 L3

Input

+

-

+

-

o o

Power

Supply

Output

DC-
OK

L1 L2 L3

Input

+

-

+

-

o o

Redundancy

Module

Output

Input

 1

Input

2

+

-

+

-

+

-

-

Redundancy

Module

Output

Input

 1

Input

2

+

-

+

-

+

-

-

 