ML15.121
MiniLine
12V, 1.3A, S
INGLE
P
HASE
I
NPUT
Dec. 2007 / Rev. 1.1 DS-ML15.121-EN
All parameters are specified at 12V, 1.3A, 230Vac, 25°C ambient and after a 5 minutes run-in time unless otherwise noted.
www.pulspower.com Phone +49 89 9278 0 Germany
9/20
13. F
RONT
S
IDE AND
U
SER
E
LEMENTS
Fig. 13-1
Front side
A Output
Terminals
Screw terminals
Dual terminals for the negative pole allows an easy earthing of the output
voltage
+
Positive output
-
Negative (return) output
B Input
Terminals
Screw terminals
L
Neutral
input
N
Line
(hot)
input
EMI
ground
Ground this terminal to minimize high-frequency emissions.
For safety reasons, connecting to ground is not required.
C DC-ON
LED
(green)
On when the voltage is > 10.5V
D Output voltage potentiometer
Turn to set the output voltage. Factory setting is 12.0V.
14. T
ERMINALS AND
W
IRING
All terminals are easy to access when mounted on the panel. Input and output terminals are separated from each
other (input below, output above) to help in error-free wiring.
Type
Screw
terminals
Solid
wire
0.5-6mm
2
Stranded
wire
0.5-4mm
2
American wire gauge
20-10 AWG
Ferrules
Allowed, but not required
Recommended tightening torque
1Nm, 9lb.in
Screwdriver
3.5mm
slotted or Pozidrive No 2
Wire stripping length
7mm / 0.275inch
Instructions:
a)
Use appropriate copper cables that are designed for an operating temperatures of 60°C (for ambient up to 45°C)
and 75°C (for ambient up to 60°C), minimum.
b)
Ferrules are allowed, but not required.
c)
Follow local and national installation codes and regulations!
d)
Ensure that all strands of a stranded wire enter the terminal connection!
e)
In order to fulfill GL requirements, unused terminal spaces must be closed.