ML15.121
MiniLine
12V, 1.3A, S
INGLE
P
HASE
I
NPUT
Dec. 2007 / Rev. 1.1 DS-ML15.121-EN
All parameters are specified at 12V, 1.3A, 230Vac, 25°C ambient and after a 5 minutes run-in time unless otherwise noted.
www.pulspower.com Phone +49 89 9278 0 Germany
8/20
11. F
UNCTIONAL
D
IAGRAM
Fig. 11-1
Functional diagram
Input Fuse
&
Input Filter
L
N
Output Over-
Voltage
Protection
Input
Rectifier
&
Inrush
Limiter
Power
Converter
Output
Voltage
Regulator
+
-
-
Output
Filter
V
OUT
DC
on
12. R
ELIABILITY
These units are extremely reliable and use only the highest quality materials. The number of critical components such
as electrolytic capacitors has been reduced.
AC 100V
AC 120V
AC 230V
Lifetime expectancy
min.
123 000h
126 000h
125 000h
40°C, 12V, 1.3A
min.
> 15 years
> 15 years
> 15 years
40°C, 12V, 0.65A
min.
> 15 years
> 15 years
> 15 years
25°C, 12V, 1.3A
MTBF SN 29500, IEC 61709
3 435 000h
3 723 000h
3 811 000h
40°C, 12V, 1.3A
5 633 000h
6 106 000h
6 205 000h
25°C, 12V, 1.3A
MTBF MIL HDBK 217F
1 482 000h
1 534 000h
1 451 000h
40°C, 12V, 1.3A, Ground Benign GB40
1 986 000h
2 056 000h
1 944 000h
25°C, 12V, 1.3A, Ground Benign GB25
The
Lifetime expectancy
shown in the table indicates the operating hours (service life) and is determined by the
lifetime expectancy of the built-in electrolytic capacitors.
Lifetime expectancy is specified in operational hours. Lifetime expectancy is calculated according to the capacitor’s
manufacturer specification. The prediction model allows a calculation of up to 15 years from date of shipment.
MTBF
stands for
M
ean
T
ime
B
etween
F
ailure, which is calculated according to statistical device failures, and indicates
reliability of a device. It is the statistical representation of the likelihood of a unit to fail and does not necessarily
represent the life of a product.