ML60.241
MiniLine-2
24V,
2.5A,
S
INGLE
P
HASE
I
NPUT
Fig. 3-5
De-rating requirements for
low input voltages
0
85Vac
10
20
30
40
50
60W
Input Voltage
A... < +45°C
B... < +60°C
A
B
90Vac
Allowable
Output Power
4.
I
NPUT
I
NRUSH
C
URRENT
A NTC limits the input inrush current after turn-on of the input voltage. The inrush current is input voltage and
ambient temperature dependent.
The charging current into EMI suppression capacitors is disregarded in the first microseconds after switch-on.
AC 100V
AC 120V
AC 230V
Inrush current
max.
17A
peak
21A
peak
40A
peak
40°C ambient, cold start
typ.
14A
peak
16A
peak
32A
peak
40°C ambient, cold start
Inrush energy
typ.
0.15A
2
s 0.2A
2
s 1.0A
2
s
40°C ambient, cold start
Fig. 4-1
Input inrush current, typical behavior
Fig. 4-2
Input inrush current, zoom into first peak
Input Current
Input Voltage
Input Current
Output Voltage
Input:
230Vac
Output:
24V, 2.5A
Ambient: 25°C
Input current 2A/DIV
Time basis:
0.5ms / DIV
Input:
230Vac
Output:
24V, 2.5A
Ambient: 25°C
Upper curve:
Input current 5A/DIV
Middle curve:
Input voltage 100V/DIV
Lower curve:
Output voltage 5V/DIV
Time basis:
20ms / DIV
Nov. 2015 / Rev. 1.4 DS-ML60.241-EN
All parameters are specified at 24V, 2.5A, 230Vac 50Hz input, 25°C ambient and after a 5 minutes run-in time unless otherwise noted.
www.pulspower.com Phone +49 89 9278 0 Germany
5/23