Puls MiniLine-2 ML60.241 Скачать руководство пользователя страница 3

 

 

ML60.241

 

 

MiniLine-2 

 

24V,

 

2.5A,

 

S

INGLE 

P

HASE 

I

NPUT

 

 

 

1.

 

I

NTENDED 

U

SE

 

This device is designed for installation in an enclosure and is intended for the general use such as in industrial control, 
office, communication, and instrumentation equipment. 

Do not use this power supply in equipment, where malfunction may cause severe personal injury or threaten human 
life. 

 

 

 

2.

 

I

NSTALLATION 

R

EQUIREMENTS

 

This device may only be installed and put into operation by qualified personnel. 

This device does not contain serviceable parts. The tripping of an internal fuse is caused by an internal defect. 

If damage or malfunction should occur during installation or operation, immediately turn power off and send unit to 
the factory for inspection.  

Mount the unit on a DIN-rail so that the output terminals are located on top and input terminal on the bottom. For 
other mounting orientations see de-rating requirements in this document. 

This device is designed for convection cooling and does not require an external fan. Do not obstruct airflow and do 
not cover ventilation grid (e.g. cable conduits) by more than 30%! 

Keep the following installation clearances:  
40mm on top, 20mm on the bottom 
Left / right: 0mm (or 15mm in case the adjacent device is a heat source; in example another power supply….). 

 

WARNING

  Risk of electrical shock, fire, personal injury or death. 

-  Do not use the power supply without proper grounding (Protective Earth). Use the terminal on the input block for 

earth connection. 

-  Turn power off before working on the device. Protect against inadvertent re-powering. 
-  Make sure that the wiring is correct by following all local and national codes. 
-  Do not modify or repair the unit. 
-  Do not open the unit as high voltages are present inside. 
-  Use caution to prevent any foreign objects from entering into the housing. 
-  Do not use in wet locations or in areas where moisture or condensation can be expected. 
-  Do not touch during power-on, and immediately after power-off. Hot surface may cause burns. 

 

Notes for use in hazardous location areas: 

The power supply is suitable for use in Class I Division 2 Groups A, B, C, D locations. 

WARNING EXPLOSION HAZARDS!  

Substitution of components may impair suitability for this environment. Do not disconnect the unit or operate the 
voltage adjustment unless power has been switched off or the area is known to be non-hazardous.  

A suitable enclosure must be provided for the end product which has a minimum protection of IP54 and fulfils the 
requirements of the EN 60079-15:2010. 

 

Nov. 2015 / Rev. 1.4  DS-ML60.241-EN 
All parameters are specified at 24V, 2.5A, 230Vac 50Hz input, 25°C ambient and after a 5 minutes run-in time unless otherwise noted. 

www.pulspower.com   Phone +49 89 9278 0    Germany 

3/23

Содержание MiniLine-2 ML60.241

Страница 1: ...diode module MLY10 241 allows building of redundant systems or to protect against back feeding voltages SHORT FORM DATA Output voltage DC 24V Adjustment range 24 28V Output current 2 5A at 24V 2 1A a...

Страница 2: ...e and reliable and may change without notice The housing is patent by PULS US patent No US D442 923S No part of this document may be reproduced or utilized in any form without permission in writing fr...

Страница 3: ...other power supply WARNING Risk of electrical shock fire personal injury or death Do not use the power supply without proper grounding Protective Earth Use the terminal on the input block for earth co...

Страница 4: ...he power factor is the ratio of the true or real power to the apparent power in an AC circuit The crest factor is the mathematical ratio of the peak value to RMS value of the input current waveform At...

Страница 5: ...t cold start typ 14Apeak 16Apeak 32Apeak 40 C ambient cold start Inrush energy typ 0 15A2 s 0 2A2 s 1 0A2 s 40 C ambient cold start Fig 4 1 Input inrush current typical behavior Fig 4 2 Input inrush c...

Страница 6: ...tput voltage vs output current typ Output Voltage 0 0 4 8 12 28V 16 20 24 3 2 1 5 6A 4 Adjustment Range Output Current a 100Vac b 120Vac c 230Vac b c a Peak current capability up to several millisecon...

Страница 7: ...ect the pole to L and the pole to N Connect the PE terminal to an earth wire or to the machine ground DC input nom DC 110 300V 20 25 DC input range min 88 375Vdc continuous operation reduce output pow...

Страница 8: ...2 0 Output Current 1 0 84 88 a 230Vac b 120Vac c 100Vac b c a Power Losses 0 1 4 8 0 9W 0 5 1 5 2 0 Output Current 2 5A 1 0 2 6 b c a 3 7 a 230Vac b 120Vac c 100Vac 5 Fig 8 3 Efficiency vs input volta...

Страница 9: ...tive and positive pole Both poles are equal Positive output Negative return output B Input Terminals Screw terminals L Phase Line input N Neutral conductor input PE Protective Earth input C DC on LED...

Страница 10: ...61709 1 391 000h 1 667 000h 1 916 000h at 24V 2 5A and 40 C 2 541 000h 2 964 000h 3 345 000h at 24V 2 5A and 25 C MTBF MIL HDBK 217F 1 038 000h 1 112 000h 1 060 000h at 24V 2 5A 40 C Ground Benign GB...

Страница 11: ...ower supply shows normal operation behavior within the defined limits B The power supply operates continuously during and after the test During the test minor temporary impairments may occur which wil...

Страница 12: ...oltage category III IEC 62103 EN 50178 altitudes up to 2000m II altitudes from 2000m to 6000m Degree of pollution 2 IEC 62103 EN 50178 not conductive LABS compatibility The unit does not release any s...

Страница 13: ...eable In case of a protection event audible noise may occur 16 SAFETY FEATURES Input output separation SELV IEC EN 60950 1 PELV IEC EN 60204 1 EN 50178 IEC 62103 IEC 60364 4 41 Class of protection I P...

Страница 14: ...B C Type test 60s 2500Vac 4000Vac 2000Vac Factory test 5s 2500Vac 2500Vac 500Vac Field test 5s 2000Vac 2000Vac 500Vac Cut off current setting 4mA 4mA 1mA at 500V 4mA at 2000V A C N L Input Earth PE Ou...

Страница 15: ...on Class I Div 2 T4 Groups A B C D systems U S A ANSI ISA 12 12 01 2007 and Canada C22 2 No 213 M1987 GL Germanischer Lloyd classified Environmental category C EMC1 Marine and offshore applications Ma...

Страница 16: ...e DIN rail height must be added to the unit depth 91mm to calculate the total required installation depth Installation Clearances See chapter 2 Fig 20 1 Front view Fig 20 2 Side view Nov 2015 Rev 1 4...

Страница 17: ...ailures ODULE 21 3 UF20 241 BUFFER M This buffer unit is a supplementary device for DC 24V power supplies It delivers power to bridge typical mains failures or extends the hold up time after turn off...

Страница 18: ...e dips Fig 22 1 Peak loading with 2x the nominal current for 50ms typ Fig 22 2 Peak loading with 5x the nominal current for 5ms typ Output Voltage 18 23 10ms DIV Output Current 24 5V 0A 5A 16V 24 5V O...

Страница 19: ...A B or 6A C Characteristic breaker should be used 22 5 PARALLEL USE TO INCREASE OUTPUT POWER Unit A AC DC Unit B AC DC Load ML60 241 power supplies can be paralleled to increase the output power This...

Страница 20: ...put Input Output Load IN 2 Voltage Monitor Recommendations for building redundant power systems a Use separate input fuses for each power supply b Use separate mains systems for each power supply when...

Страница 21: ...Supply AC DC internal fuse The power supply can also be used on two phases of a three phase system A phase to phase connection is allowed as long as the supplying voltage is below 240V 10 Use a fuse o...

Страница 22: ...Enclosure Rittal Type IP66 Box PK 9510 100 plastic 130x130x75mm Input 230Vac Case A Load 24V 2 5A load is placed outside the box Temperature inside the box 40 1 C in the middle of the right side of th...

Страница 23: ...ended output current Curve A2 Max allowed output current results in approximately half the lifetime expectancy of A1 Fig 22 7 Mounting Orientation A Standard orientation Power Supply OUTPUT Output Pow...

Отзывы: