background image

EN 

FPT500.245-018-103

 

Installation Manual 

 

 

 

 

Product Description 

The FPT500.245-018-103 is a stand-alone power supply for three-phase mains systems, which 
provides a stabilized and galvanically separated PELV output voltage at 4 outputs via two output 
connectors. The negative potential of the outputs is permanently connected to PE within the unit. 
The device is incorporated in a housing rated for IP65 and IP67, which provides protection against 
electrical, mechanical and fire hazards. 
The device is equipped with an IO-Link Interface V1.1 to parameterize and access data. 

Intended Use

 

This indoor use device is intended for commercial use, such as in industrial control, process control, 
monitoring, measurement or the like. 
Do not use this device in equipment, where malfunctioning may cause severe personal injury or 
threaten human life without additional appropriate safety devices, that are suited for the end-
application. 
If this device is used in a manner outside of its specification, the protection provided by the device may 
be impaired.  
Do not connect the negative potential of the output to PE . 

Installation Instructions 

Install the device onto a flat surface with the terminals on the bottom of the device. Other mounting 
orientations require a reduction in output current. 
The device is designed for pollution degree 3 areas

 

in controlled environments. 

Install the device on a large enough flat surface so that any sharp edges on the back cannot cause 
injury. 
Use screws for wall mounting, 2 on top and 2 on bottom mounting holes. Use M4 screws or similar. 
The enclosure of the device provides a degree of ingress protection of IP65 and IP67 when installed 
with all mating connectors firmly connected. 
The 

device is designed as “Class of Protection I” equipment according to IEC 61140. Do not use 

without a proper PE (Protective Earth) connection. 
For TN,TT mains systems with earthed neutral and IT star mains systems with insulation monitoring 
the device is designed for overvoltage category III zones up to 2000m (6560ft) and for overvoltage 
category II zones up to 5000m (16400ft). For TN, TT, IT delta mains systems or IT star mains systems 
without insulation monitoring the device is intended for overvoltage category II zones up to 2000m 
(6560ft). 
The device is designed to be safe in case of a single phase loss and no external protection is required. 
A disconnecting means shall be provided for the input of the device. 
The device is designed for convection cooling and does not require an external fan. Do not obstruct 
airflow and do not cover ventilation fins! 
The device is designed for altitudes up to 5000m (16400ft). Above 2000m (6560ft) a reduction in 
output current is required and the operation is limited according mains systems description above. 
Keep the following minimum installation clearances: 50mm on top and bottom, 10mm on the front and 
10mm left and right side. 
The device is designed, tested and approved for branch circuits up to 20A (UL) and 32A (IEC) without 
additional protection device. If an external fuse is utilized, do not use circuit breakers smaller than 6A 
B- or C-Characteristic to avoid a nuisance tripping of the circuit breaker. 
The maximum surrounding air temperature is +70°C (+158°F). The operational temperature is the 
same as the ambient or surrounding air temperature and is defined 2cm below the device. 
The device is designed to operate in areas between 5% and 95% relative humidity. 
Cleaning only with a damp cloth. 
Do not connect any output to PE outside of the unit. 

Functional Description 

The output is electronically protected against no-load, overload and short circuit and can supply any 
kind of loads, including unlimited inductive and capacitive loads.

 

If capacitors with a capacitance 

>20mF are connected to one output, this output might switch off after turning the unit or the output on 
or connecting the load. 
Do not apply return voltages from the load to the output terminals higher than 35V. 
The green Status LED reports an output above 90% of the adjusted voltage of a running device. 
The device is equipped with an over-temperature protection. In case of a high temperature, the output 
shuts down and starts automatically again after cooling off. 
Do not parallel outputs or devices for higher output currents. 
In case of an internal defect, a redundant circuit limits the maximum output voltage to 32.5V. The 
output shuts down and automatically attempts to restart. 
IO-Link gives access to internally measured parameters and can be used to change settings. For 
additional IODD files and descriptions please visit 

www.pulspower.com

.

 

LED bargraph and push-buttons: 

Normal operation of the LED bar is the monitoring mode showing the actual output power as 
percentage of 500W (100% is 500W). Percentages above 100% is shown in orange. Pressing the up / 
down buttons shows the percentage of each output. The orange LED indicates the selected output.  
Pressing 

the “Set Mode” button for 3s lets flash all LED ‘s for a short time and changes the LED bar 

into the configuration mode. Configuration mode starts in 

“set voltage” mode. With the up / down 

buttons the voltage can be changed to the values indicated by the single lit green LED, while all 
orange LED are dark. The voltage is set immediately and the value stored until the next change. 
Pressing 

the “Set Mode” button again changes into the “set output current” mode. The orange LED 

indicates the selected output. With the up / down buttons the current limit can be changed to the 
values indicated by the single lit green LED. The value stored until the next change. Select other 
outputs with the 

“Set Mode” button. Without further pressing of push-buttons, the LED bar will return 

from any other mode to normal mode after 15s. 
With the buttons at each channel the channel can turned on/off manually by pressing for at least 1s. 

Mating connectors: 

For the mating input voltage connector (X1) use a standard M12 S-coded male connector. The Pin 
assignment is Pin 1 for L1, Pin 2 for L2, Pin 3 for L3 and The Pin with the PE symbol for PE. 
For the mating IO Link (X2) use a standards M12 A-coded 5 pin female connector.  
For mating the output voltage connectors (X3, X4) use 7/8

” male connectors.

 

 

Pin assignment X3 (X4): Pin 1: 24VDC Out2(4); Pin 4:0V DC Out2(4) 
Pin 2:24V DC Out1(3); Pin 3: 0V DC Out1(3);  

 

Technical Data

 

All values are typical figures specified at 3x 400Vac 50Hz input voltage, 
symmetrical phase voltages, 24V, 500W output load, 25°C ambient 
temperature and after a 5 minutes run-in time unless otherwise noted. 

Output voltage 

DC 24V 

Nominal 

Adjustment range 

24 

– 28Vdc 

Factory setting 24.5V 

Output power 

Continuous: 

 

600W 

At +45°C ambient 

 

500W 

At +55°C ambient 

 

350W 

At +70°C ambient 

 

Short-term, up to 5s: 

 

1000W 

Below +55°C ambient 

 

700W 

At +70°C ambient 

 

Derate linearly b45°C and +70°C 

Output currents 

Settable per output; up to 10A  

Input voltage AC 

3AC 380 - 480V 

±15% 

Mains frequency 

50 

– 60Hz 

±6% 

Input current AC 

1.1 / 0.9A 

At 3x400 / 480Vac 

Power factor 

0.94 / 0.95 

At 3x400 / 480Vac 

Input inrush current 

1.5 / 1.5A peak 

At 3x400 / 480Vac, 
temp. independent 

Efficiency 

95.8 / 95.6% 

At 3x400 / 480Vac 

Losses 

20.8 / 23.0W 

At 3x400 / 480Vac 

Hold-up time 

24 / 24ms 

At 3x400 / 480Vac 

Temperature range 

-25 to +70°C 

 

Size 

(LxWxH)

 

183x182x59mm 

Without connectors 

Weight 

1200g / 2.7lb 

 

 

Functional Diagram 

 

 

Output Characteristic per output 

 

 

Temperature Range 

Allowed output power

Ambient temperature

0

-25

0

+70°C

600W

700W

+45

1000W

350W

B

 A: continuous
 B: short term (max. 5s)

A

+55

500W

 

 

Hole Pattern for Mounting 

 

All dimensions in mm connectors X1 to.X4 from left to right 

 

Отзывы: