Mar. 2007 / Rev. 1.0  DS-ML50.100-EN 
All parameters are specified at 24V, 2.1A, 230Vac, 25°C ambient and after a 5 minutes run-in time unless otherwise noted. 

www.pulspower.com   Phone +49 89 9278 0    Germany 

8/20 

 

12. F

UNCTIONAL 

D

IAGRAM

 

 

 

Fig. 12-1

   Functional diagram 

 

Input Fuse
&
Input Filter

L

N

Output Over-

Voltage

Protection

DC-OK

Transistor

Signal

Input
Rectifier
&
Inrush
Limiter

Power

Converter

Output

Voltage

Regulator

+

+

-

-

Output

Filter

V

OUT

DC

ok

DC-ok

Signal

 

 

 

13. R

ELIABILITY

 

 

These units are extremely reliable and use only the highest quality materials. The number of critical components such 
as electrolytic capacitors has been reduced. 

   

AC 100V 

AC 120V 

AC 230V 

 

  Lifetime expectancy 

min. 

34 000h 

44 000h 

54 000h 

40°C, 24V, 2.1A 

   

min. 

112 000h 

117 000h 

111 000h 

40°C, 24V, 1.05A 

   

min. 

96 000h 

125 000h 

152 000h 

25°C, 24V, 2.1A 

  MTBF SN 29500, IEC 61709 

2 383 000h 

2 456 000h 

2 613 000h 

40°C, 24V, 2.1A 

   

3 977 000h 

4 100 000h 

4 362 000h 

25°C, 24V, 2.1A 

  MTBF MIL HDBK 217F 

1 021 000h 

1 053 000h 

1 120 000h 

40°C, 24V, 2.1A, Ground Benign GB40 

   

1 370 000h 

1 413 000h 

1 503 000h 

25°C, 24V, 2.1A, Ground Benign GB25 

 

The 

Lifetime expectancy

 shown in the table indicates the operating hours (service life) and is determined by the 

lifetime expectancy of the built-in electrolytic capacitors.  

Lifetime expectancy is specified in operational hours. Lifetime expectancy is calculated according to the capacitor’s 
manufacturer specification. The prediction model allows a calculation of up to 15 years from date of shipment. 

MTBF

 stands for 

M

ean 

T

ime 

B

etween 

F

ailure, which is calculated according to statistical device failures, and indicates 

reliability of a device. It is the statistical representation of the likelihood of a unit to fail and does not necessarily 
represent the life of a product. 

 

Содержание FAML50-100

Страница 1: ...3W C 60 to 70 C Hold up time typ 35 190ms at 120 230Vac Dimensions 45x75x91mm WxHxD A compact size light weight simple mounting on the DIN rail and the quick connect spring clamp terminals are what ma...

Страница 2: ...ENDED USE The power supply shall only be installed and put into operation by qualified personnel This power supply is designed for installation in an enclosure and is intended for the general use such...

Страница 3: ...yp 3 05 3 26 3 91 at 24V 2 1A Start up delay typ 32ms 32ms 32ms See Fig 5 2 Rise time typ 33ms 33ms 48ms 0mF 24V 2 1A see Fig 5 2 typ 45ms 45ms 60ms 2mF 24V 2 1A see Fig 5 2 Turn on overshoot max 400m...

Страница 4: ...ut Current Input 230Vac Output 24V 2 1A Ambient 40 C Upper curve Input current 20A DIV Middle curve Input voltage 1000V DIV Lower curve Output voltage 20V DIV Time scale 20ms DIV Input 230Vac Output 2...

Страница 5: ...is also on during this time 9 DC OK OUTPUT This feature monitors the output voltage which is present on the output terminals The signal is a source output which can feed loads up to 30mA Loads can be...

Страница 6: ...0W Short circuit current min 3 1A Load impedance 400mOhm see Fig 10 1 max 5A Load impedance 400mOhm see Fig 10 1 Fig 10 1 Output voltage vs output current 230Vac typ Output Voltage 0 0 1 2 4 8 12 28V...

Страница 7: ...W 4 1W 4 4W 1 05A 24V typ 7 2W 6 6W 6 2W 2 1A 24V Fig 11 1 Efficiency vs output current at 24V Fig 11 2 Losses vs output current at 24V Efficiency 0 3 76 78 80 82 84 86 88 74 90 2 1A 0 9 1 2 1 8 Outpu...

Страница 8: ...C 24V 1 05A min 96 000h 125 000h 152 000h 25 C 24V 2 1A MTBF SN 29500 IEC 61709 2 383 000h 2 456 000h 2 613 000h 40 C 24V 2 1A 3 977 000h 4 100 000h 4 362 000h 25 C 24V 2 1A MTBF MIL HDBK 217F 1 021...

Страница 9: ...itive output Negative return output Dual pins per pole DC OK Open collector output Indicates an output voltage higher than 20Vdc 15 TERMINALS AND WIRING All terminals are easy to access when mounted o...

Страница 10: ...70 of 200Vac 0Vac 20ms 40Vac 200ms 70Vac 500ms 0Vac 20ms 80Vac 200ms 140Vac 500ms Criterion A Criterion C Criterion A Criterion A Criterion A Criterion A Voltage interruptions EN 61000 4 11 0Vac 5000m...

Страница 11: ...ltitudes from 2000m to 6000m Degree of pollution 2 EN 50178 IEC 62103 non conductive Fig 17 1 Output current vs ambient temp Fig 17 2 Output current vs altitude 24V 0 10 0 20 40 70 C 0 4 0 8 1 2 1 6 2...

Страница 12: ...mains 0 40mA 264Vac 50Hz TN mains 20 DIELECTRIC STRENGTH Fig 20 1 Dielectric strength A B C Type test 60s 2500Vac 3000Vac 500Vac Factory test 5s 2500Vac 2500Vac 500Vac Field test 5s 2000Vac 2000Vac 5...

Страница 13: ...n switched off Wiring must be in accordance with Class I Division 2 wiring methods of the National Electrical Code NFPA 70 and in accordance with other local or national codes Marine GL ABS GL Germani...

Страница 14: ...te electrical and fire end product enclosure should be considered in the end use application Cooling Convection cooled no forced cooling required Do not cover ventilation grill e g cable conduits by m...

Страница 15: ...Germany 15 20 26 ACCESSORY DIN Rail bracket for wall or panel mount A DIN rail bracket is included in each shipping box Fig 26 1 DIN Rail Bracket Fig 26 2 DIN Rail Bracket Dimensions Hole diameter 4...

Страница 16: ...age is turned on before such an event the built in large sized output capacitors inside the power supply can deliver extra current Discharging this capacitor causes a voltage dip on the output The fol...

Страница 17: ...adjusted output voltage draws current until it goes into current limitation This means no harm to this power supply as long as the ambient temperature stays below 50 C If a current sharing feature is...

Страница 18: ...ower supply to different phases of the mains network 27 6 DAISY CHAINING OF OUTPUTS Daisy chaining jumping from one power supply output to the next is allowed as long as the maximum current through on...

Страница 19: ...or two phase operation a A phase to phase connection is allowed as long as the supplying voltage is below 240V 10 b Use a fuse or a circuit breaker to protect the N input The N input is internally not...

Страница 20: ...A1 Recommended output power Curve A2 Max allowed output power results approx in half the lifetime expectancy of A1 Fig 27 8 Mounting Orientation A Standard Orientation Power Supply OUTPUT INPUT Output...

Отзывы: