background image

 

 

UF40.241

 

 

UF-Series 

24V,

 

40A,

 

160

MS

,

 

B

UFFER 

M

ODULE

 

 

 

4.

 

E

LECTRICAL 

R

ATINGS

 

 

Supply voltage 

Nom. 

DC 24V 

-20%/+25%

 

 

Supply voltage range

1)

 

Nom. 

19.2 - 30Vdc 

 

Normal operating voltage range

2)

 

Typ. 

23 – 30Vdc 

 

Transfer voltage for switching 
into buffer mode 

Typ. 
Typ. 

22.5Vdc 
V

IN

 – 1V 

Back-up threshold jumper set to “22.5V fixed” 
Back-up threshold jumper set to “V

IN

 – 1V” 

See also chapter 5

Transfer voltage for switching 
from buffer mode into power 
supply mode 

Typ. 
Typ. 

22.5Vdc 
V

BUFFER

 + 1V 

Back-up threshold jumper set to “22.5V fixed” 
Back-up threshold jumper set to “V

IN

 – 1V” 

See also chapter 5

Buffer voltage 

Typ. 

Same as the transfer voltage for switching into buffer mode. 

Ripple and noise voltage 
   - in buffer mode 

Max. 

200mVpp 

Generated by the buffer module. 
Defined at 20Hz to 20MHz, 50Ohm 

   - in power supply mode 

 

The ripple and noise voltage is defined by the power supply. 

Current consumption 

Typ. 
Min. 
Max. 

80mA 
400mA 
600mA 

When capacitor is fully charged 
During charging of the capacitors 
During charging of the capacitors 

Power dissipation 

Typ. 

1.9W 

When capacitor is fully charged 

Buffer current 

Min. 

40A 

 

Buffer current overload behavior 

 

Electronically limited, buffering stops and capacitor gets discharged 
below 17V. See Fig. 4-2

Allowed voltage between supply 
voltage and chassis ground 

Max. 60Vdc 

or 

42.4Vac 

Continuous, IEC 62477-1 

Capacitive and inductive loads  

No 

limitation  

1) Supply Voltage Range: 

At voltages within the input voltage range, control functions such as LEDs, monitoring features, relay contacts, etc. are functioning 
normally. Within the input voltage range the unit can either be in power supply mode or in buffer mode. 

2) Normal Operating Voltage Range: 

The normal operating voltage range describes the supply voltage, which supports the full functionality of the buffer module (including 
charging) but without entering the buffer mode. 

 

 

Fig. 4-1

   Selection of an appropriate power supply 

 

Fig. 4-2

   Output characteristic in buffer mode, 

22.5V fixed mode, typ. 

Buffer Voltage

0

0

40

4

8

12

28V

16

20

64A

24

8

16

32

48

56

Output Current

24

22.5V

Buffering stops

below 17V

 

 

Internal

current

consumption

Current

consumption

for charging

Load
Current

Power

Supply

Current

 

 

 

Oct. 2016 / Rev. 1.0 DS-UF40.241-EN 
All parameters are specified at 24V, 40A, 25°C ambient and after a 5 minutes run-in time unless otherwise noted. 

www.pulspower.com   Phone +49 89 9278 0    Germany 

5/18

Содержание DIMENSION UF Series

Страница 1: ...g It can be added in parallel to the load circuit at any given point Buffer modules can be connected in parallel to increase the output ampacity or the hold up time SHORT FORM DATA Supply voltage DC 24V 20 25 19 2 30Vdc Required voltage to charge capacitors 23Vdc Threshold voltage for buffer mode 22 5V VIN 1V Selectable Buffer voltage 22 5V VIN 1V Selectable Buffer current 40A Charging time Typ 34...

Страница 2: ...rmission in writing Some parts of this unit are patent by PULS US patent No 091662 063 Des 424 529 TERMINOLOGY AND ABREVIATIONS Power supply mode Describes a condition where the supply voltage is in the rated supply voltage range and the supplying power supply can deliver a sufficient amount of current for the buffer module and the load The mode can also be called Normal mode Buffer mode Describes...

Страница 3: ... any obstructions Signal lines ready active and inhibit must be shorter than 30m Use an appropriately sized power supply which can deliver the additional required internal current consumption including the charging current specified as input current in the table of chapter 4 and Fig 4 1 The following installation clearances must be maintained Left right 0mm On top of the unit 40mm On bottom of the...

Страница 4: ...urrent for a defined period of time Process data can be saved and processes can be terminated before the DC power switches off Controlled restarts are subsequently possible AC DC Buffer Module Easy to handle expandable and maintenance free The buffer module does not require any control wiring It can be added parallel to the load circuit at any given point Buffer modules can be connected in paralle...

Страница 5: ...n 40A Buffer current overload behavior Electronically limited buffering stops and capacitor gets discharged below 17V See Fig 4 2 Allowed voltage between supply voltage and chassis ground Max 60Vdc or 42 4Vac Continuous IEC 62477 1 Capacitive and inductive loads No limitation 1 Supply Voltage Range At voltages within the input voltage range control functions such as LEDs monitoring features relay ...

Страница 6: ...mmended for any application where 22 5V is too low for the application or when the buffer module is placed close to the power supply The factory setting is fixed mode A missing jumper means also fixed mode 6 BUFFER TIME The buffer time sometimes also called autonomy time is the maximum period of time for which the capacitor can maintain the required output current The buffer time mainly depends on...

Страница 7: ...than 2minutes Fig 7 1 Charging time re charging Charge 20 0 5 10 45s Charging Time 40 80 60 100 15 20 25 30 35 40 max min typ 8 OPERATING DIAGRAMS Fig 8 1 Operating diagram Fig 8 2 Signal schematic Ready t Active t Optocoupler high ohmic Optocoupler high ohmic Optocoupler low ohmic Optocoupler low ohmic V Mains t V Buffer Capacitor t Vout t Charging Mode LED t Buffer Mode Hold up Time Power Supply...

Страница 8: ...age current Max 50μA While opto coupler is high ohmic Isolation voltage See chapter 21 11 INHIBIT INPUT Buffering can be disabled or interrupted with the inhibit input pin 9 Therefore pin 6 should be connected to the positive pole of the terminal voltage or to the external control voltage and pin 9 must be connected to the corresponding negative pole Inhibiting the unit also discharges the interna...

Страница 9: ...tional hours and is calculated according to the capacitor s manufacturer specification The manufacturer of the electrolytic capacitors only guarantees a maximum life of up to 15 years 131 400h Any number exceeding this value is a calculated theoretical lifetime which can be used to compare devices MTBF stands for Mean Time Between Failure which is calculated according to statistical device failure...

Страница 10: ... American Wire Gauge Max AWG 22 8 AWG 22 14 Max wire diameter Max 5 2mm including ferrules 2 25mm including ferrules Wire stripping length Typ 12mm 0 5inch 6mm 0 25inch Tightening torque 2 3Nm 20 5lb inch 0 4Nm 3 5lb inch Screwdriver 3 5mm or 5mm slotted or cross head No 2 3mm slotted Instructions a Use appropriate copper cables that are designed for minimum operating temperatures of 60 C for ambi...

Страница 11: ...ls see chapter 11 D Status LED This green LED indicates that the following information OFF Capacitors are discharged or supply voltage is below 22V ON Capacitors are fully charged Slow flashing 1 25Hz Capacitors are getting charged Fast flashing 10Hz Capacitors are getting discharged E Back up Threshold Jumper Option 1 Fixed mode Jumper in position 2 3 The unit switches to buffer mode as soon as t...

Страница 12: ...erions A Buffer module shows normal operation behavior within the defined limits EMC Emission for standby and charging mode According to generic standards EN 61000 6 3 and EN 61000 6 4 Conducted emission supply voltage IEC CISPR 16 1 2 IEC CISPR 16 2 1 Limits for DC power ports acc EN 61000 6 3 fulfilled Radiated emission EN 55011 EN 55022 Class B This device complies with FCC Part 15 rules Operat...

Страница 13: ...sation is present 19 PROTECTION FEATURES Electrical protection Electronically protected against overload no load and short circuits Over voltage protection in buffer mode Typ 32Vdc Max 35Vdc In case of an internal buffer module defect a redundant circuit limits the maximum output voltage Buffering stops and automatically attempts to restart Degree of protection IP 20 EN IEC 60529 Penetration prote...

Страница 14: ...trength A B C Type test 60s 500Vac 500Vac 500Vac 14 18 Factory test 5s 500Vac 500Vac 500Vac Field test 5s 500Vac 500Vac 500Vac Cut off current setting 1mA 1mA 1mA Supply Voltage Chassis Active and Ready Signal Inhibit Input A C B 22 APPROVALS EU Declaration of Conformity The CE mark indicates conformance with the EMC directive CB Scheme Information Technology Equipment IEC 60950 1 2nd Edition Reco...

Страница 15: ...ight 1040g 2 3lb DIN rail Use 35mm DIN rails according to EN 60715 or EN 50022 with a height of 7 5 or 15mm Housing material Body Aluminium alloy Cover Zinc plated steel Installation clearances See chapter 2 Fig 23 1 Front view Fig 23 2 Side view Oct 2016 Rev 1 0 DS UF40 241 EN All parameters are specified at 24V 40A 25 C ambient and after a 5 minutes run in time unless otherwise noted www pulspow...

Страница 16: ...l To mount a unit on a wall or a panel the two zinc plated steel brackets have to be installed on the side of the unit Fig 24 1 Wall mounting Fig 24 2 Mounting Dimensions Wall mounting bracket Oct 2016 Rev 1 0 DS UF40 241 EN All parameters are specified at 24V 40A 25 C ambient and after a 5 minutes run in time unless otherwise noted www pulspower com Phone 49 89 9278 0 Germany 16 18 ...

Страница 17: ...el brackets can be mounted For sideway DIN rail mounting the removed aluminum brackets and the black plastic slider need to be mounted on the steel bracket Fig 24 3 Side mounting without DIN rail brackets Fig 24 4 Side mounting with DIN rail brackets Fig 24 5 Mounting Dimensions Side mounting bracket Oct 2016 Rev 1 0 DS UF40 241 EN All parameters are specified at 24V 40A 25 C ambient and after a 5...

Страница 18: ...N PE Output Input L N PE Inhibit Active Relay lamp or signal Ready Relay lamp or signal External Voltage Source Load UF40 Buffer Module Back up Threshold Status Active Ready Inhibit 9 8 7 6 Power Supply DC 24V L N PE Output Input Fig 25 3 Paralleling of buffer modules Fig 25 4 Decoupling of buffered branches 18 18 L N PE UF40 Buffer Module Back up Threshold Status Active Ready Inhibit 9 8 7 6 UF40...

Отзывы: