UF40.241
UF-Series
24V,
40A,
160
MS
,
B
UFFER
M
ODULE
B
UFFER
M
ODULE
Buffering with electrolytic capacitors instead of lead
acid batteries
Buffering of 24V loads
Minimum hold-up time 0.16s at 40A, longer hold-up
time at lower loads
Clear status indication by status LED and signaling
terminals
Extra large screw terminals
3 Years warranty
1/18
G
ENERAL
D
ESCRIPTION
The UF40 buffer module is a supplementary device for
regulated DC 24V power supplies, which can be used for
various purposes:
- Deliver DC-power to bridge failures of the DC
voltage supply system.
- Extend the hold-up time after loss of the AC power.
- Deliver extra short-term peak current above the
current rating of the power supply.
It utilizes service-free electrolytic capacitors for storing
the energy which allows usage even at ambient
temperatures up to +70°C.
The buffer module does not require any control wiring.
It can be added in parallel to the load circuit at any
given point.
Buffer modules can be connected in parallel to increase
the output ampacity or the hold-up time.
S
HORT
-
FORM
D
ATA
Supply voltage
DC 24V
-20%/+25%
19.2-30Vdc
Required voltage to
charge capacitors
23Vdc
Threshold voltage
for buffer mode
22.5V / V
IN
-1V Selectable
Buffer voltage
22.5V / V
IN
-1V Selectable
Buffer current
40A
Charging time
Typ. 34s
Current consumption Typ. 80mA
Max. 600mA
Stand-by mode
During charging
Power dissipation
1.9W
Stand-by mode
Buffer time
Min. 160ms
Min. 320ms
Typ. 250ms
Typ. 500ms
Typ. 62s
At 22.5V, 40A
At 22.5V, 20A
At 22.5V, 40A
At 22.5V, 20A
At 22.5V, 0.1A
Temperature range
-25°C to +70°C operational
Dimensions 64x124x142mm
WxHxD
Weight
1040g / 2.3lb
O
RDER
N
UMBERS
Buffer Module
UF40.241
Accessory ZM2.WALL
Panel/ wall-mount bracket
ZM14.SIDE
Side-mount
bracket
M
ARKINGS
IND. CONT. EQ.
UL 508
UL 60950-1
EMC
Oct. 2016 / Rev. 1.0 DS-UF40.241-EN
All parameters are specified at 24V, 40A, 25°C ambient and after a 5 minutes run-in time unless otherwise noted.