background image

EN 

CT5.241 Installation Manual 

 

 

 

 

Product Description 

The CT5.241 is a DIN-rail mountable power supply for three-phase mains systems, which provides a 
floating, stabilized and galvanically separated SELV/PELV output voltage. 
The device utilizes only two legs of a three-phase system, which saves wiring and installation costs. 

Intended Use

 

This device is designed for installation in an enclosure and is intended for commercial use, such as in 
industrial control, process control, monitoring and measurement equipment or the like.  
Do not use this device in equipment, where malfunctioning may cause severe personal injury or 
threaten human life without additional appropriate safety devices, that are suited for the end-
application. 
If this device is used in a manner outside of its specification, the protection provided by the device may 
be impaired. 

Installation Instructions 

Install device in an enclosure providing protection against electrical, mechanical and fire hazards. 
Install the device onto a DIN-rail according to EN 60715 with the input terminals on the bottom of the 
device. Other mounting orientations require a reduction in output current. 
Make sure that the wiring is correct by following all local and national codes. Use appropriate copper 
cables that are designed for a minimu

m operating temperature of 60°C for ambient temperatures up to 

+

45°C, 75°C for ambient temperatures up to +60°C and 90°C for ambient temperatures up to +70°C. 

Ensure that all strands of a stranded wire enter the terminal connection. Use ferrules for wires on the 
input terminals. Unused screw terminals should be securely tightened. 
The device is designed for pollution degree 2 areas in controlled environments. No condensation or 
frost is allowed. 
The enclosure of the device provides a degree of protection of IP20. The housing does not provide 
protection against spilled liquids. 
The device is designed for overvoltage category II zones. Below 2000m altitude the device is tested 
for impulse withstand voltages up to 4kV, which corresponds to OVC III according to IEC 60664-1. 
The device is designed as “Class of Protection I” equipment according to IEC 61140. Do not use 
without a proper PE (Protective Earth) connection. 
The device is suitable to be supplied from TN, TT or IT mains networks. The continuous voltage 
between the input terminals and the PE potential must not exceed 500Vac. Corner grounded delta 
systems are allowed. 
A disconnecting means shall be provided for the input of the device. 
The device is designed for convection cooling and does not require an external fan. Do not obstruct 
airflow and do not cover ventilation grid! 
The device is designed for altitudes up to 5000m (16400ft). Above 2000m (6560ft) a reduction in 
output current is required. 
Keep the following minimum installation clearances: 40mm on top, 20mm on the bottom, 5mm left and 
right side. Increase the 5mm to 15mm in case the adjacent device is a heat source. When the device 
is permanently loaded with less than 50%, the 5mm can be reduced to zero. 
The device is designed, tested and approved for branch circuits up to 32A (IEC) and 30A (UL) without 
additional protection device. If an external fuse is utilized, do not use circuit breakers smaller than 6A 
B- or 3A C-Characteristic to avoid a nuisance tripping of the circuit breaker. 
The maximum surr

ounding air temperature is +70°C (+158°F). The operational temperature is the 

same as the ambient or surrounding air temperature and is defined 2cm below the device. 
The device is designed to operate in areas between 5% and 95% relative humidity. 

Installation Instructions for Hazardous Location Areas 

The device is suitable for use in Class I Division 2 Groups A, B, C, D locations. 

WARNING EXPLOSION HAZARDS! 

Substitution of components may impair suitability for this environment. 
Do not disconnect the device or operate the voltage adjustment unless power has been switched off or 
the area is known to be non-hazardous. 

Functional Description 

The output is electronically protected against no-load, overload and short circuit and can supply any 
kind of loads, including unlimited inductive or capacitive loads. 
Do not apply return voltages from the load to the output terminals higher than 35Vdc. 
The output voltage can be adjusted with a small flat-blade screwdriver on the front of the unit. 
The green DC OK LED reports an output voltage above 21V of a running device. 
The device is equipped with an over-temperature protection. In case of a high temperature, the output 
shuts down and starts automatically again after cooling off. 
Devices can be paralleled to increase the output power. The ambient temperature is not allowed to 
45

°C. If more than three devices are connected in parallel, a diode, fuse or circuit breaker 

with a rating of 10A is required on each output. 
Same devices can be connected in series for higher output voltages. It is allowed to connect as many 
devices in series as needed, providing the sum of the output voltage does not exceed 150Vdc. 
In case of an internal defect, a redundant circuit limits the maximum output voltage to 32V. The output 
shuts down and automatically attempts to restart. 

 

Technical Data

 

All values are typical figures specified at 400Vac 50Hz input voltage, 24V 
5A output load

, 25°C ambient temperature and after a 5 minutes run-in 

time unless otherwise noted. 

Output voltage 

DC 24V 

Nominal 

Adjustment range 

24 

– 28Vdc 

Factory setting 24.1V 

Output current 

6.0 

– 5.1A 

Below +45

°C ambient  

 

5.0 

– 4.3A 

At +60°C ambient 

 

3.8 

– 3.2A 

At +70°C ambient 

 

Derate linearly 

b45°C and +70°C 

Input voltage AC 

AC 380 - 480V 

-15% / +20% 

Mains frequency 

50 

– 60Hz 

±6% 

Input current AC 

0.75 / 0.68A 

At 400 / 480Vac 

Power factor 

0.45 / 0.43 

At 400 / 480Vac 

Input inrush current 

4 / 4A peak 

At 400 / 480Vac 

Efficiency 

90.4 / 90.0% 

At 400 / 480Vac 

Losses 

12.7 / 13.3W 

At 400 / 480Vac 

Hold-up time 

40 / 60ms 

At 400 / 480Vac 

Temperature range 

-25 

to +70°C 

 

Max. wire size (litz wire) 

4mm² 

 

Wire size AWG 

AWG 20-10 

 

Max. wire diameter 

2.8mm 

 

Wire stripping length 

7mm / 0.28inch 

 

Tightening torque 

1Nm / 9lb.inch 

 

Size 

(wxhxd)

 

40x124x117mm 

Without DIN-rail 

Weight 

500g / 1.1lb 

 

 
 

Functional Diagram 

+

+

-
-

Output

Over-

Voltage

Protection

PFC

Inductor

Voltage

Regulator

Power

Converter

Output

Filter

Output

Power

Manager

Temper-

ature

Shut-

down

Input Fuse
Input Filter
Input Rectifier
Inrush Current
Limiter

V

OUT

L1

L2

DC-OK

LED

 

 
 

Output Characteristic 

Output voltage

8A

24V

Output current

12V

0V

1A

3A

4A

6A

0A

Adjustment range

28V

2A

5A

7A

9A 10A 11A

 

 
 

Temperature Range 

Allowed output current at 24V

Ambient temperature

0A

-25

A: continuous
B: short term (max. 60s)

6.0A

+25

0

+45

+70°C

3.75A

5.0A

+60

A

B

 

 

Отзывы: