![Puls CP10.241-60 Скачать руководство пользователя страница 6](http://html1.mh-extra.com/html/puls/cp10-241-60/cp10-241-60_manual_1624220006.webp)
CP10.241-60
CP-Series
24V,
200W,
DC/DC
C
ONVERTER
P R E L I M I N A R Y
6.
O
UTPUT
Output voltage
Nom.
24V
Adjustment range
Min.
24-28V
Guaranteed
Max.
30V
*)
At clockwise end position of potentiometer
Factory setting
Typ.
24.1V
±0.2%, at full load, cold unit
Line regulation
Max.
10mV
67-154Vdc
Load regulation
Max.
100mV
Static value, 0A
Æ
8.3A
Ripple and noise voltage
Max.
50mVpp
20Hz to 20MHz, 50Ohm
Output current
Nom.
8.3A
At 24V, ambient temperature <70°C, see Fig. 6-1
Nom.
7.1A
At 28V, ambient temperature <70°C, see Fig. 6-1
Typ.
30A
Up to 12ms, output voltage stays above 20V, see Fig.
6-2 and Fig. 24-3, This peak current is available once
every five seconds (firmware controlled).
Output power
Nom.
200W
Continuously available
Overload behaviour
Cont. current
Output voltage > 13Vdc, see Fig. 6-1
Hiccup
PLUS
mode
**)
Output voltage < 13Vdc, see Fig. 6-1
Short-circuit current Min.
9.5A
***)
Load impedance 50mOhm, see Fig. 6-1
Max.
13.5A
***)
Load impedance 50mOhm, see Fig. 6-1
Max.
4.3A
Average (R.M.S.) current, load impedance 50mOhm,
see Fig. 6-3
Min.
28A
Up to 12ms, load impedance 50mOhm, see Fig. 6-2
Typ.
30.5A
Up to 15ms, load impedance 50mOhm, see Fig. 6-2
Output capacitance
Typ.
4 400μF
Included inside the power supply
*)
This is the maximum output voltage which can occur at the clockwise end position of the potentiometer due to tolerances. It is not a
guaranteed value, which can be achieved. The typical value is 28.6V.
**) Hiccup
PLUS
Mode
At heavy overloads (when output voltage falls below 13V), the power supply delivers continuous output current for 2s. After this, the
output is switched off for approx. 18s before a new start attempt is automatically performed. This cycle is repeated as long as the
overload exists. If the overload has been cleared, the device will operate normally. See Fig. 6-3
***) Discharge current of output capacitors is not included.
Fig. 6-1
Output voltage vs. output current,
typ.
Fig. 6-2
Dynamic output current capability,
typ.
Output Voltage
0
0
1
4
8
12
28V
16
20
24
0
12A
6
2
4
8
Adjustment
Range
Output Current
Continuous
current
Factory
setting
Hiccup
PLUS
mode
Output Voltage
(dynamic behavior, < 12ms)
0
0
4
8
12
28V
16
20
24
50A
20
10
30
40
5
15
25
35
45
Adjustment
Range
Output Current
May 2017 / Rev. 0.1 DS-QS10.241-60-EN preliminary
All parameters are typical values specified at 24V, 8.3A output, 110Vdc input, 25°C ambient and after a 5 minutes run-in time
unless otherwise noted.
www.pulspower.com Phone +49 89 9278 0 Germany
6/27