P R E L I M I N A R Y
24.5.
S
ERIES
O
PERATION
DC/DC converters of the same type can be connected in series for higher output voltages. It is possible to connect as
many units in series as needed, providing the sum of the output voltage does not exceed 150Vdc. Voltages with a
potential above 60Vdc are not SELV any more and can be dangerous. Such voltages must be installed with a protection
against touching.
Avoid return voltage (e.g. from a decelerating motor or battery) which is applied to the output terminals.
Fig. 24-4
Parallel use to increase the output power
Instructions for series use:
Unit A
Input
Output
Unit B
-
+
-
+
Load
+
-
Input
Output
- Keep an installation clearance of 15mm (left / right)
between two DC/DC converters and avoid installing the
DC/DC converters on top of each other.
- Do not use DC/DC converters in series in mounting
orientations other than the standard mounting orientation
(input terminals on bottom of the unit).
- Pay attention that EMI and inrush current will increase
when using multiple DC/DC converters.
24.6.
P
ARALLEL
U
SE TO
I
NCREASE
O
UTPUT
P
OWER
DC/DC converters can be paralleled to increase the output power. The output voltage shall be adjusted to the same
value (±100mV) with the same load conditions on all units, or the units can be left with the factory settings. The
ambient temperature is not allowed to 60°C.
If more than three units are connected in parallel, a fuse or circuit breaker with a rating of 15A or 16A is required on
each output. Alternatively, a diode or redundancy module can also be utilized.
Fig. 24-5
Parallel use to increase the output power
Instructions for parallel use:
Unit A
Unit B
-
+
-
+
Load
+
-
Input
Output
Input
Output
- Keep an installation clearance of 15mm (left / right)
between two DC/DC converters and avoid installing the
DC/DC converters on top of each other.
- Do not parallel DC/DC converters in orientations other
than the standard mounting orientation (input terminals
on bottom of the unit) or in any other condition where a
derating of the output current is required (e.g. altitude,
temperature, input voltages).
- Pay attention that EMI and inrush current will increase
when using multiple DC/DC converters.
May 2017 / Rev. 0.1 DS-QS10.241-60-EN preliminary
All parameters are typical values specified at 24V, 8.3A output, 110Vdc input, 25°C ambient and after a 5 minutes run-in time
unless otherwise noted.
www.pulspower.com Phone +49 89 9278 0 Germany