CD5.051 Installation Manual
Product Description
The CD5.051 is a DIN-rail mountable DC/DC converter, which provides a floating, stabilized and
galvanically separated SELV/PELV output voltage.
Intended Use
This device is designed for installation in an enclosure and is intended for commercial use, such as in
industrial control, process control, monitoring, measurement equipment or the like.
Do not use this device in equipment, where malfunctioning may cause severe personal injury or
threaten human life without additional appropriate safety devices, that are suited for the end-
application.
If this device is used in a manner outside of its specification, the protection provided by the device may
be impaired.
Installation Instructions
Install device in an enclosure providing protection against electrical, mechanical and fire hazards.
Install the device onto a DIN-rail according to EN 60715 with the input terminals on the bottom of the
device. Other mounting orientations require a reduction in output current.
Make sure that the wiring is correct by following all local and national codes. Use appropriate copper
cables that are designed for a minimum operating temperature of 60°C for ambient temperatures up to
+45°C, 75°C for ambient temperatures up to +60°C and 90°C for ambient temperatures up to +70°C.
Ensure that all strands of a stranded wire enter the terminal connection. Unused screw terminals
should be securely tightened.
The device is designed for pollution degree 2 areas in controlled environments. No condensation or
frost is allowed.
The enclosure of the device provides a degree of protection of IP20. The enclosure does not provide
protection against spilled liquids.
The isolation of the device is designed to withstand impulse voltages of 1.5kV according to IEC 60664-
1.
The input can be powered from batteries or similar DC sources. The voltage between the input
terminals and ground must not exceed 60Vdc continuously.
The input must be powered from a PELV or SELV source or an "Isolated Secondary Circuit" in order to
maintain a SELV or PELV output.
Check for correct input polarity. The device will not operate when the voltage is reversed.
A disconnecting means shall be provided for the input of the device.
The device is designed as “Class of Protection III” equipment according to IEC 61140. A PE (ground)
connection is not required. However, connecting the chassis ground terminal to ground can be
beneficial to gain a high EMI immunity.
The device is designed for convection cooling and does not require an external fan. Do not obstruct
airflow and do not cover ventilation grid!
The device is designed for altitudes up to 5000m (16400ft). Above 2000m (6560ft) a reduction in
output current is required.
Keep the following minimum installation clearances: 40mm on top, 20mm on the bottom, 5mm left and
right side. Increase the 5mm to 15mm in case the adjacent device is a heat source. When the device
is permanently loaded with less than 50%, the 5mm can be reduced to zero.
The device is designed, tested and approved for branch circuits up to 50A without additional protection
device. If an external fuse is utilized, do not use circuit breakers smaller than 10A B- or 8A C-
Characteristic to avoid a nuisance tripping of the circuit breaker.
The maximum surrounding air temperature is +70°C (+158°F). The operational temperature is the
same as the ambient or surrounding air temperature and is defined 2cm below the device.
The device is designed to operate in areas between 5% and 95% relative humidity.
Functional Description
The output is electronically protected against no-load, overload and short circuit and can supply any
kind of loads, including unlimited inductive or capacitive loads.
Do not apply return voltages from the load to the output terminals higher than 6.5V.
The output voltage can be adjusted with a small flat-blade screwdriver on the front of the unit.
The green DC OK LED reports a voltage on the output terminals above 2Vdc, which is produced by the
device itself.
The device is equipped with an over-temperature protection. In case of a high temperature, the output
shuts down and starts automatically again after cooling off.
Devices can be paralleled to increase the output power. The ambient temperature is not allowed to
45°C. The output voltage shall be adjusted to the same value (±100mV) with the same load
conditions on all devices, or the devices can be left with the factory settings. If more than three
devices are connected in parallel, a diode, fuse or circuit breaker with a rating of 20A is required on
each output.
Same devices can be connected in series for higher output voltages. It is allowed to connect as many
devices in series as needed, providing the sum of the output voltage does not exceed 150Vdc.
In case of an internal defect, a redundant circuit limits the maximum output voltage to 6.1V. The output
shuts down and automatically attempts to restart.
Technical Data
All values are typical figures specified at 24Vdc input voltage, 5V, 10A
output load,
25°C ambient and after a 5 minutes run-in time unless
otherwise noted.
Output voltage
DC 5V
Nominal
Adjustment range
5
– 5.5Vdc
Factory setting 5.1V
Output current
12A
Below
+45°C ambient
10A
A
t +60°C ambient
7.5A
A
t +70°C ambient
Derate linearly
b45 and +70°C
Input voltage
DC 24V
-25% / +35%
Input current
2.6A
Input inrush current
1.2A pk
Temp. independent
Efficiency
81.5%
Power losses
11.3W
Hold-up time
10ms
Temperature range
-
25°C to +70°C
Max. wire size (litz wire)
4mm²
For all terminals
Wire size AWG
AWG 20-10
For all terminals
Max. wire diameter
2.8mm
For all terminals
Wire stripping length
7mm / 0.28inch
For all terminals
Tightening torque
1Nm / 9lb.inch
For all terminals
Size
(wxhxd)
32x124x102mm
Without DIN-rail
Weight
425g / 0.94lb
Functional Diagram
+
+
-
-
V
OUT
Input
Fuse
&
Input
Filter
Output
Voltage
Regulator
Output
Filter
DC-
OK
Output
Over-
Voltage
Protection
Reverse
Polarity
Protection
&
Inrush
Limiter
Chassis
Ground
+
-
Power
Converter
Output Characteristic
Output voltage
16A
4V
Output current
2V
0V
2A
6A
10A
12A
0A
6V
4A
14A
8A
5.1V
Temperature Range
Allowed output current
Ambient temperature
0A
-25
12A
0
+70°C
7.5A
+45
+60
10A