CD5.051 Installation Manual 

 

 

 

 

Product Description 

The CD5.051 is a DIN-rail mountable DC/DC converter, which provides a floating, stabilized and 
galvanically separated SELV/PELV output voltage. 
 

Intended Use

 

This device is designed for installation in an enclosure and is intended for commercial use, such as in 
industrial control, process control, monitoring, measurement equipment or the like. 
Do not use this device in equipment, where malfunctioning may cause severe personal injury or 
threaten human life without additional appropriate safety devices, that are suited for the end-
application. 
If this device is used in a manner outside of its specification, the protection provided by the device may 
be impaired. 
 

Installation Instructions 

Install device in an enclosure providing protection against electrical, mechanical and fire hazards. 
Install the device onto a DIN-rail according to EN 60715 with the input terminals on the bottom of the 
device. Other mounting orientations require a reduction in output current. 
Make sure that the wiring is correct by following all local and national codes. Use appropriate copper 
cables that are designed for a minimum operating temperature of 60°C for ambient temperatures up to 
+45°C, 75°C for ambient temperatures up to +60°C and 90°C for ambient temperatures up to +70°C. 
Ensure that all strands of a stranded wire enter the terminal connection. Unused screw terminals 
should be securely tightened. 
The device is designed for pollution degree 2 areas in controlled environments. No condensation or 
frost is allowed. 
The enclosure of the device provides a degree of protection of IP20. The enclosure does not provide 
protection against spilled liquids. 
The isolation of the device is designed to withstand impulse voltages of 1.5kV according to IEC 60664-
1. 
The input can be powered from batteries or similar DC sources. The voltage between the input 
terminals and ground must not exceed 60Vdc continuously. 
The input must be powered from a PELV or SELV source or an "Isolated Secondary Circuit" in order to 
maintain a SELV or PELV output. 
Check for correct input polarity. The device will not operate when the voltage is reversed. 
A disconnecting means shall be provided for the input of the device. 
The device is designed as “Class of Protection III” equipment according to IEC 61140. A PE (ground) 
connection is not required. However, connecting the chassis ground terminal to ground can be 
beneficial to gain a high EMI immunity. 
The device is designed for convection cooling and does not require an external fan. Do not obstruct 
airflow and do not cover ventilation grid! 
The device is designed for altitudes up to 5000m (16400ft). Above 2000m (6560ft) a reduction in 
output current is required. 
Keep the following minimum installation clearances: 40mm on top, 20mm on the bottom, 5mm left and 
right side. Increase the 5mm to 15mm in case the adjacent device is a heat source. When the device 
is permanently loaded with less than 50%, the 5mm can be reduced to zero. 
The device is designed, tested and approved for branch circuits up to 50A without additional protection 
device. If an external fuse is utilized, do not use circuit breakers smaller than 10A B- or 8A C-
Characteristic to avoid a nuisance tripping of the circuit breaker. 
The maximum surrounding air temperature is +70°C (+158°F). The operational temperature is the 
same as the ambient or surrounding air temperature and is defined 2cm below the device. 
The device is designed to operate in areas between 5% and 95% relative humidity. 
 

Functional Description 

The output is electronically protected against no-load, overload and short circuit and can supply any 
kind of loads, including unlimited inductive or capacitive loads. 
Do not apply return voltages from the load to the output terminals higher than 6.5V. 
The output voltage can be adjusted with a small flat-blade screwdriver on the front of the unit. 
The green DC OK LED reports a voltage on the output terminals above 2Vdc, which is produced by the 
device itself. 
The device is equipped with an over-temperature protection. In case of a high temperature, the output 
shuts down and starts automatically again after cooling off. 
Devices can be paralleled to increase the output power. The ambient temperature is not allowed to 
45°C. The output voltage shall be adjusted to the same value (±100mV) with the same load 
conditions on all devices, or the devices can be left with the factory settings. If more than three 
devices are connected in parallel, a diode, fuse or circuit breaker with a rating of 20A is required on 
each output. 
Same devices can be connected in series for higher output voltages. It is allowed to connect as many 
devices in series as needed, providing the sum of the output voltage does not exceed 150Vdc. 
In case of an internal defect, a redundant circuit limits the maximum output voltage to 6.1V. The output 
shuts down and automatically attempts to restart. 
 

 

Technical Data

 

All values are typical figures specified at 24Vdc input voltage, 5V, 10A 
output load, 

25°C ambient and after a 5 minutes run-in time unless 

otherwise noted. 

Output voltage 

DC 5V 

Nominal 

Adjustment range 

– 5.5Vdc 

Factory setting 5.1V 

Output current 

12A 

Below 

+45°C ambient 

 

10A 

A

t +60°C ambient 

 

7.5A 

A

t +70°C ambient 

 

Derate linearly 

b45 and +70°C 

Input voltage 

DC 24V 

-25% / +35% 

Input current 

2.6A 

 

Input inrush current 

1.2A pk 

Temp. independent 

Efficiency 

81.5% 

 

Power losses 

11.3W 

 

Hold-up time 

10ms 

 

Temperature range 

-

25°C to +70°C 

 

Max. wire size (litz wire) 

4mm² 

For all terminals 

Wire size AWG 

AWG 20-10 

For all terminals 

Max. wire diameter 

2.8mm 

For all terminals 

Wire stripping length 

7mm / 0.28inch 

For all terminals 

Tightening torque 

1Nm / 9lb.inch 

For all terminals 

Size 

(wxhxd)

 

32x124x102mm 

Without DIN-rail 

Weight 

425g / 0.94lb 

 

 
 
 

Functional Diagram 

+

+

-
-

V

OUT

Input
Fuse
&
Input
Filter

Output

Voltage

Regulator

Output

Filter

DC-

OK

Output

Over-

Voltage

Protection

Reverse
Polarity
Protection
&
Inrush
Limiter

Chassis

Ground

+

-

Power

Converter

 

 
 

Output Characteristic 

Output voltage

16A

4V

Output current

2V

0V

2A

6A

10A

12A

0A

6V

4A

14A

8A

5.1V

 

 
 

Temperature Range 

Allowed output current

Ambient temperature

0A

-25

12A

0

+70°C

7.5A

+45

+60

10A

 

 