ML60.122
MiniLine-2
12V,
4.5A,
S
INGLE
P
HASE
I
NPUT
6.
H
OLD
-
UP
T
IME
AC 100V
AC 120V
AC 230V
Hold-up Time
typ.
37ms
56ms
229ms
at 12V, 2.25A, see Fig. 6-1
typ.
16ms
25ms
113ms
at 12V, 4.5A, see Fig. 6-1
Note: At no load, the hold-up time can be up to several seconds. The green DC-ok lamp is also on during this time
Fig. 6-1
Hold-up time vs. input voltage
Fig. 6-2
Shut-down behavior, definitions
0
20
40
100
120ms
85
120
155
190
230Vac
Input Voltage
Hold-up Time
60
80
a) 12V 2.25A typ.
b) 12V 2.25Amin.
c) 12V 4.5A typ.
d) 12V 4.5A min.
a
b
c
d
- 5%
Hold-up Time
Zero Transition
Output
Voltage
Input
Voltage
7.
DC-I
NPUT
The power supply can also be supplied from a DC source. Use a battery or similar DC source. For other sources contact
PULS. Connect the + pole to L and the – pole to N. Connect the PE terminal to an earth wire or to the machine ground.
DC input
nom.
DC 110-300V
-20%/+25%
DC input range
min.
88-375Vdc
continuous operation, reduce output power according
Fig. 7-2 at voltages below 130Vdc
Allowed Voltage L/N to Earth
max.
375Vdc
IEC 62103
DC input current
typ.
0.57A / 0.2A
110Vdc / 300Vdc, at 12V, 4.5A
Turn-on voltage
typ.
90Vdc
steady state value
Shut-down voltage
typ.
57Vdc
similar behavior as shown in Fig. 3-1
Fig. 7-1
Wiring for DC Input
Fig. 7-2
Allowable output current below
110Vdc input voltage
7/23
+
-
Load
L
N
PE
+
-
Power Supply
AC
DC
Battery
internal
fused
0
10
80
90
100
110
130Vdc
20
30
40
60W
Output Power
50
Input Voltage Vdc
(b)
(a)
(a) Continuous
120
(b) Short-term
Nov. 2015 / Rev. 1.4 DS--ML60.122-EN
All parameters are specified at 12V, 4.5A, 230Vac 50Hz input, 25°C ambient and after a 5 minutes run-in time unless otherwise noted.