Hurricane 5000 NEMA 4X Series Installation
f. Ensure proper color codes:
g. Tighten and re-check all connections.
h. If remote monitoring is employed, connect the form “C” contacts to the building monitor system or independent alarm, i.e. addressable
relay. Contact relays will accept up to 1A/220VAC. The dry contact terminals are N.O. (normally open), N.C. (normally closed) and COM
(common).
i. Switch MAIN power ON. Check all front panel indicator lamps for illumination.
Wire
Wire Size
Color
Circuit Breaker
Ground
#12 AWG
Hot
#8 AWG
Hot
Neutral
#10 AWG
Hot
#6 AWG
Green or Green/Yellow
20A rms
Red
50A rms
Blue
White
30A rms
Black
60A rms
Alarm Conditions – Contact Status
N/C
Connection: #24-16 AWG (0.2 mm – 1.5 mm²)
Rating: 0.5 A, 125 Vac, 1A 30 Vdc
COM
N/O
N/C
COM
N/O
1. TVSS de-energized
2. TVSS energized, fault
3. NC-COM (White-Black)
4. NO-COM (White-Red)
1. TVSS energized, Status OK (All Green LEDs)
2. NC-COM (White-Red)
3. NO-COM (White-Black)
NOTES
To run a test of the relay contact by turning MAIN power OFF and then back ON.
a. Wire TVSS to Service Panel - Minimize conductor lead length by cutting back excess cabling. Recommended lead length is less than 3 feet.
In addition, conductors should be tightly taped together for the entire run. Refer to figure 1 for connecting surge suppressor to AC power
network.
b. Circuit Breakers - A circuit breaker should be coordinated to protector wire size. The primary function of this breaker is to provide a
means of removing power from the unit for maintenance. The circuit breakers will not trip during normal surge suppression since the
response time of the circuit breaker is much longer than the duration of a transient voltage.
4. Phase Connections